Minimum required ventilation flow rates (Q) in dm³/s and air change rates per hour (n) for an indoor sports center and a shop of 1000 m2 floor area, 5 m height and 100 persons present, according to Ref. [49,[[54], [55]]].

Function Indoor sports center
Shop
Q (dm³/s) n (h−1) Q (dm³/s) n (h−1)
Building Code (new buildings) [49] 650 0.47 400 0.29
Building Code (existing buildings) [49] 344 0.25 212 0.15
Sports Guidelines [[54], [55]]
 General (11.11 dm³/s/person) 1111 0.80
 Fitness area 8333 6
 Aerobics and martial sports area 11111 8
 Indoor cycling area 13889 10