Table 4.

Mean Legionella concentration in three hospitals before and after the replacement of sensor-activated faucets with Thermostatic Mixer Valves (TMVs).

ID
Hospitals
Number of SHWOs
(Total Samples)
Time of Renovation Works of SHWOs
(Total Samples)
Mean Temperature Samples
(°C)
Number of Legionella Positive Samples/Total of Samples
(%)
Number of Legionella Samples Over Risk Value/Positive Samples
(%)
Mean Legionella Concentration ± SD
(Log cfu/L)
t-Student and Wilcoxon Test
p-Value
(p)
1 5 (28) Before (14) 42.73 1.98 ± 1.34 0.046 *
5/28 (17.9) 4/5 (80.0)
After (14) 49.15 1.23 ± 0.13
1/28 (3.6) 0
8 3 (50) Before (25) 42.89 2.59 ± 1.34 0.001 *
19/50 (38.0) 13/19 (68.4)
After (25) 46.98 1.3 ± 0.20
5/50 (10.0) 0
11 14 (32) Before (16) 48.96 3.03 ± 1.04 0.001 *
15/32 (46.9) 15/15 (100.0)
After (16) 49.50 9/32 (28.1) 5/9 (55.6) 1.8 ± 0.86

* Values are statistically significant at p ≤ 0.05.