Table 3.

Parameters of typical confined space scenarios.

Scenario Number of seats Length (m) Width (m) Social distance, d (m) Distance index, Pd Pd with 50% occupancy ratio Ventilation rate with clean air, Q/N(m3/h∙p) Air distribution form Ventilation index, Ez PdEz∙Q/N(50%)
Long bus (GB9673-1996, 1996GB9673-, 1996GB9673-1996, 1996) 69 13.7 2.55 0.72 49.3 % 36.7 % 20 Ceiling supply, floor return 1 0.025 (0.018)
Air cabin (GB9673-1996, 1996GB9673-, 1996GB9673-1996, 1996) 350 0.78 48.0 % 35.2 % 25 Ceiling supply, floor return 1 0.019 (0.014)
Public bus (GB9673-1996, 1996GB9673-, 1996GB9673-1996, 1996) 75 8.5 2.5 0.35 62.2 % 49.6 % 15 Ceiling supply, ceiling return 0.8 0.052 (0.041)
Subway (GB50157—2003, 2013GB50157—, 2013GB50157—2003, 2013) 200 22 3 0.57 53.4 % 40.8 % 20 Ceiling supply, ceiling return 0.8 0.033 (0.026)
High-speed train (TB10621-2009, 2009TB10621-, 2009TB10621-2009, 2009) 85 25 3.3 0.99 43.5 % 30.9 % 20 Ceiling supply, floor return 1 0.022 (0.015)
Office (GB50189-2005 2005GB50189—, 2005GB50189-2005 2005; JGJ/T67-2006 2006JGJ/T67-, 2019JGJ/T67-2006 2006; Mu, Yan, & Qian, 2017) 10 2.00 30.7 % 18.1 % 30 Ceiling supply, floor return 1 0.010 (0.006)
Classroom (GB99-86, 2012; Y., J. Y.J., 2019) 50 1.05 42.4 % 29.8 % 14 Ceiling supply, floor return 1 0.030 (0.021)
Restaurant (JG64-89, 1900) 90 1.05 42.4 % 29.8 % 20 Ceiling supply, ceiling return 0.8 0.027 (0.019)