Table 13.11.
Values of β
| Area corresponding with one filter on the ceiling (larger value could be used if air supply outlet is not in the middle /m2) | In unidirectional flow cleanroom, air is supplied with air supply outlets fully on the ceiling and air is returned at two lower bottom sides | 0.97 | |
| ≥15 | 0.3 | In unidirectional flow cleanroom, filters are placed fully (the ratio of blowing area ≥ 80 %) | 0.99 |
| >10 | 0.4 | Side supply and side return mode | 0.5–0.7 (small value can be used when the distance between air supply outlets is more than 3 m) |
| >5 | 0.5–0.7 | ||
| >2 | 0.7–0.8 | Orifice plate: when placed in the middle with area ≤ 1/2 of the ceiling area; | 0.4 |
| >1 | 0.8–0.9 | when placed at both sides with area ≤ 2/3 of the ceiling area | |
| In unidirectional flow cleanroom, filters are placed in between (the ratio of blowing area ranges from 40 to 80 %) | 0.9–0.99 | Placed fully at the ceiling | 0.9–0.95 |