Table 13.11.

Values of β

Area corresponding with one filter on the ceiling (larger value could be used if air supply outlet is not in the middle /m2) In unidirectional flow cleanroom, air is supplied with air supply outlets fully on the ceiling and air is returned at two lower bottom sides 0.97
≥15 0.3 In unidirectional flow cleanroom, filters are placed fully (the ratio of blowing area ≥ 80 %) 0.99
>10 0.4 Side supply and side return mode 0.5–0.7 (small value can be used when the distance between air supply outlets is more than 3 m)
>5 0.5–0.7
>2 0.7–0.8 Orifice plate: when placed in the middle with area ≤ 1/2 of the ceiling area; 0.4
>1 0.8–0.9 when placed at both sides with area ≤ 2/3 of the ceiling area
In unidirectional flow cleanroom, filters are placed in between (the ratio of blowing area ranges from 40 to 80 %) 0.9–0.99 Placed fully at the ceiling 0.9–0.95