Table 14.2.
Particle concentration in local clean area of the operating room (0.4 m above the floor)
Particle concentration with diameter ≥0.5 μm (pc/L) | |||
---|---|---|---|
Mainstream area | Vortex region | ||
Before starting up | 4,350 | 4,200 | |
After starting up/min | 1 | 2,750 | 4,260 |
2 | 225 | 4,060 | |
3 | 76 | 1,840 | |
4 | 20 | 480 | |
5 | 0.4 | 98 | |
6 | 0.035 | 6.2 | |
7 | 0 | 1.7 | |
8 | 0 | 0.25 | |
9 | 0 | 0.12 | |
10 | 0 | 0.035 | |
11 | 0 | 0.07 | |
12 | 0 | 0 |