Skip to main content
. 2013 Aug 8:649–696. doi: 10.1007/978-3-642-39374-7_14

Table 14.2.

Particle concentration in local clean area of the operating room (0.4 m above the floor)

Particle concentration with diameter ≥0.5 μm (pc/L)
Mainstream area Vortex region
Before starting up 4,350 4,200
After starting up/min 1 2,750 4,260
2 225 4,060
3 76 1,840
4 20 480
5 0.4 98
6 0.035 6.2
7 0 1.7
8 0 0.25
9 0 0.12
10 0 0.035
11 0 0.07
12 0 0