Table 14.3.

Particle concentration in local clean area of the operating room

Sampling position On the ceiling 0.9 m above the floor
Particle concentration with diameter ≥0.5 μm (pc/L) Particle concentration with diameter ≥5 μm (pc/L) Particle concentration with diameter ≥0.5 μm (pc/L) Particle concentration with diameter ≥5 μm (pc/L)
Before starting up 31,500 60 31,500 60
20 min after starting up (without surgery operation) 1 0 0 3.5 0
3 0 0 3.2 0
5 0 0 5 0.6
7 16 2.5 7 0.6
8 16 1.4 5.3 0
At the return air grille
10 9.5 0.6
12 11 0.9