Table 14.3.
Particle concentration in local clean area of the operating room
Sampling position | On the ceiling | 0.9 m above the floor | |||
---|---|---|---|---|---|
Particle concentration with diameter ≥0.5 μm (pc/L) | Particle concentration with diameter ≥5 μm (pc/L) | Particle concentration with diameter ≥0.5 μm (pc/L) | Particle concentration with diameter ≥5 μm (pc/L) | ||
Before starting up | 31,500 | 60 | 31,500 | 60 | |
20 min after starting up (without surgery operation) | 1 | 0 | 0 | 3.5 | 0 |
3 | 0 | 0 | 3.2 | 0 | |
5 | 0 | 0 | 5 | 0.6 | |
7 | 16 | 2.5 | 7 | 0.6 | |
8 | 16 | 1.4 | 5.3 | 0 | |
At the return air grille | |||||
10 | 9.5 | 0.6 | |||
12 | 11 | 0.9 |