Table 14.4.

Comparison between the experimental and the calculated velocity decay rates

换气次数 (次/h) Number of air suppliers (0.5 m × 0.5 m) Air velocity on the outlet surface (2.46 m) (m/s) Air velocity on the working surface (0.8 m) (m/s) Measured decay rate of velocity Calculated decay rate with Eq. (14.1) Average decay rate
Test Simulated flow field With Eq. (14.1)
15 1 0.54 0.32 0.41 0.61 0.43 0.48 0.53
2 0.27 0.15 0.44 0.46
25 1 1.02 0.55 0.46 0.61 0.45 0.44 0.4
2 0.50 0.28 0.44 0.46
3 0.34 0.20 0.41 0.41
4 0.25 0.13 0.48 0.38