Table 4.4.
Judgment criterion of unqualified leakage for air filter with qualitative and quantitative tests
| Type | Efficiency at nominal flow rate | Local leakage limit with qualitative test, sampling period | Local leakage limit with quantitative test |
|---|---|---|---|
| % | % | ||
| A | 99.9 (sodium flame method) | Downstream particle sampling count for diameter ≥0.5 μm is ≥3 pc/min (corresponding upstream concentration must ≥3 × 104pc/L) | 1 |
| B | 99.99 (sodium flame method) | 0.1 | |
| C | 99.999 (sodium flame method) | 0.01 | |
| D | 99.999 (particle counting method, 0.1–0.3 μm) | Downstream particle sampling count for diameter ≥0.1 μm is ≥3 pc/min (corresponding upstream concentration must ≥3 × 106pc/L) | 0.01 |
| E | 99.999 9 (particle counting method, 0.1–0.3 μm) | 0.001 | |
| F | 99.999 99 (particle counting method, 0.1–0.3 μm) | 0.0001 |