Table 4.5.

IEST-RP-CC001.4-2005

Test with photometer (test aerosol with mass median diameter 0.3 μm and count median diameter <0.2 μm) Filtration efficiency Leakage detection Test with particle counting method (0.1–0.2/0.2–0.3 μm)
Grade A ≥99.97 % Leakage detection not needed Grade H
Grade B Test efficiency with two flowrates Grade I
Grade E Test efficiency with two flowrates for nuclear application
Grade C ≥99.99 % Leakage detection needed Grade J
≥99.995 % Leakage detection needed Grade K
Grade D ≥99.999 % Leakage detection needed Grade F
≥99.9999 % Leakage detection needed Grade G (MPPS efficiency)