Skip to main content
. 2020 Aug 26;20(17):4830. doi: 10.3390/s20174830

Table 2.

Protection class accuracy requirements [5]. In the table, Up and Upn are the primary voltage and nominal (rated) primary voltage, respectively; εu and φe are the voltage (ratio) and phase errors, respectively.

Accuracy Class Up/Upn
2 5 X (1)
εu
%
±
φe
Minutes
±
φe
Centiradians
±
εu
%
±
φe
Minutes
±
φe
Centiradians
±
εu
%
±
φe
Minutes
±
φe
Centiradians
±
3P 6 240 7 3 120 3.5 3 120 3.5
6P 12 480 14 6 240 7 6 240 7