Table A-2.
Automatically created extended HAZOP worksheet for the deviations ‘high pressure’ and ‘low pressure’
| Pos. | Unit | Id. | Substance | Deviation | Super cause | Cause | Effect | Consequence | Safeguard |
|---|---|---|---|---|---|---|---|---|---|
| 23 | StorageTank-Unit | T-301 | Hexane | High-Pressure | DepositionOf-Impurities | BlockedOutflow-Line | Crack | LossOfPrimaryContainment, Fire | CollectingBasin, PressureReliefValve |
| 24 | StorageTank-Unit | T-301 | Hexane | High-Pressure | DepositionOf-Impurities | BlockedOutflow-Line | Crack | LossOfPrimaryContainment, FormationOfExAtmosphere, Explosion | CollectingBasin, DefineExProtectionZone, PressureReliefValve |
| 25 | StorageTank-Unit | T-301 | Hexane | High-Pressure | DepositionOf-Impurities | BlockedOutflow-Line | Rupture | LossOfPrimaryContainment, Fire | CollectingBasin, PressureReliefValve, PressureVacuumReliefValve |
| 26 | StorageTank-Unit | T-301 | Hexane | High-Pressure | DepositionOf-Impurities | BlockedOutflow-Line | Rupture | LossOfPrimaryContainment, FormationOfExAtmosphere, Explosion | CollectingBasin, PressureReliefValve DefineExProtectionZone, PressureVacuumReliefValve |
| 27 | StorageTank-Unit | T-301 | Hexane | High-Pressure | AbnormalHotIntake, ExternalFire, SolarRadiation |
ThermalExpansion | Rupture | LossOfPrimaryContainment, Fire | CollectingBasin, PressureReliefValve, PressureVacuumReliefValve |
| 28 | StorageTank-Unit | T-301 | Hexane | High-Pressure | AbnormalHotIntake, ExternalFire, SolarRadiation |
ThermalExpansion | Rupture | LossOfPrimaryContainment, FormationOfExAtmosphere, Explosion | CollectingBasin, PressureReliefValve DefineExProtectionZone, PressureVacuumReliefValve |
| 29 | StorageTank-Unit | T-301 | Hexane | Low-Pressure | – | Ambient-Temperature-Change | CollapseOf-Enclosure | LossOfPrimaryContainment, Fire | CollectingBasin, PressureVacuumReliefValve, VacuumProofDesign |
| 30 | StorageTank-Unit | T-301 | Hexane | Low-Pressure | – | Ambient-Temperature-Change | CollapseOf-Enclosure | LossOfPrimaryContainment, FormationOfExAtmosphere, Explosion | CollectingBasin, PressureVacuumReliefValve, VacuumProofDesign, DefineExProtectionZone |
| 31 | StorageTank-Unit | T-301 | Hexane | Low-Pressure | FaultyInstallation, HumanError | Obstructed-VentPath | CollapseOf-Enclosure | LossOfPrimaryContainment, Fire | CollectingBasin, PressureVacuumReliefValve, VacuumProofDesign |
| 32 | StorageTank-Unit | T-301 | Hexane | Low-Pressure | FaultyInstallation, HumanError | Obstructed-VentPath | CollapseOf-Enclosure | LossOfPrimaryContainment, FormationOfExAtmosphere, Explosion | CollectingBasin, DefineExProtectionZone, PressureVacuumReliefValve, VacuumProofDesign |
| 33 | StorageTank-Unit | T-301 | Hexane | Low-Pressure | Malfunction-TransferPump | ExcessiveFluid-Withdrawal | CollapseOf-Enclosure | LossOfPrimaryContainment, Fire | CollectingBasin, PressureVacuumReliefValve, VacuumProofDesign |
| 34 | StorageTank-Unit | T-301 | Hexane | Low-Pressure | Malfunction-TransferPump | ExcessiveFluid-Withdrawal | CollapseOf-Enclosure | LossOfPrimaryContainment, FormationOfExAtmosphere, Explosion | CollectingBasin, VacuumProofDesign DefineExProtectionZone, PressureVacuumReliefValve |