Table 3.
HAZOP table based on (CCPS, 2001).
| Pos. | Deviation | Causes | Identified | Consequence | Identified | Safeguard/Recommendations | Identified |
|---|---|---|---|---|---|---|---|
| 0 |
High level |
Flow from tank truck not discontinued before tank capacity has been reached |
Yes |
High pressure |
Indirect |
Level indication with high-level alarm (audible in the control room) |
Yes |
| Inventory control error – truck arrives before needed |
Yes |
Hexane unloading procedures with a checklist that includes checking field reading of tank before unloading |
Other |
||||
| 1 |
Low level |
Inventory control error – truck arrives too late |
Yes |
No safety consequences – potential process interruption if not refilled before the downstream feed tank is empty |
Yes |
– |
Other |
| Low flow or no flow – line from the tank truck to hexane storage tank T-301 through hexane unloading pump |
Yes |
||||||
| 2 |
High temperature |
No credible causes identified |
Other |
– |
Other |
– |
Other |
| 3 |
Low temperature |
Low ambient temperature while there is water contamination in the tank |
Indirect |
Possible freezing of accumulated water in the heel of the tank or the tank's drain line or instrument lines, resulting in fracture of the drain line and loss of containment |
Indirect |
– |
Other |
| 4 |
High pressure |
High level |
Other |
Release of hexane through the relief valve into the tank's dike |
Yes |
– |
Other |
| Fire hazard affecting a large area if not contained by the dike |
Yes |
||||||
| Loss of containment (if the overpressure cause exceeds the tank pressure rating) |
Yes |
||||||
| 5 |
Low pressure |
Tank blocked in before cooldown, following steam-out |
Yes |
Equipment damage resulting in a collapse of the tank under a vacuum |
Yes |
Standard procedures for steam-out of vessels |
Other |
| 6 |
High concentration of contaminants (Other than composition) |
Water not completely drained following a steam-out or washout |
Yes |
Possible freezing of accumulated water in the tank during a period of low ambient temperature |
Yes |
– |
Other |
| High concentration of contaminants – line from the tank truck to hexane storage tank T-301 through hexane unloading pump |
Yes |
||||||
| 7 | Loss of containment (Elsewhere flow) | Corrosion |
Partially | Release of hexane |
Yes |
Operation/maintenance response as required, including isolation if needed |
No |
| Erosion | |||||||
| External fire |
Capability to manually isolate the tank |
No |
|||||
| External impact | |||||||
| Gasket, packing or seal failure |
Periodic non-destructive inspection per API recommended practice and ASME code |
Yes |
|||||
| Improper maintenance | |||||||
| Instrument or instrument line failure |
Fire hazard affecting a large area particularly if the capacity of the dike is exceeded | Yes | Relief valve that discharges to the tank's dike |
Yes |
|||
| Material defect | |||||||
| Sample station valve leaking |
Dike sized for 1.5 times the capacity of the tank |
Yes |
|||||
| Vent or drain valve leaking | |||||||
| Low temperature |
Emergency response procedures | No | |||||
| High pressure (if the overpressure cause exceeds the equipment pressure rating) |