Skip to main content
. 2020 Nov 7;20(21):6361. doi: 10.3390/s20216361

Table 8.

RMS and frequency measurement results. Distorted voltage signal with 25 harmonics, f1 = 50 Hz.

Supply Values Measured Value Error Maximum Error IEC 61000-4-30 Class A/S
RMS 231.47 (V) 230.70 (V) 0.33% ±0.5% Udin 1 S
Frequency 50.0 (Hz) 50.0000 [Hz] 0.0 (mHz) ±10 mHz A

1Udin is the declared supply voltage.