Table 4.

Comparison of Lagrangian modeling and EPA experiment (600/R-06/051) measurement.

Microorganisms Z value (m−2·J) Average UV dose Davg (J·m−2)
Disinfection efficacy η (%)
EPA [49] Ref. [50] Ref. [42] Present EPA [49] Ref. [42] Present
S. marcescens 0.92 18b 99.8 99.99 100
MS2 bacteriophage 0.038–0.048 18b 15.82c 16.63c 46 49.35 54.43
B. atrophaeus 0.016 2.95a 18b 15.82c 20.36c 0 13.68 0.00
a

Calculated by Davg = lnFs/Z, where Davg was average UV dose, Fs was the survival fraction of airborne microorganisms, Z was Z value of airborne microorganisms.

b

Calculated by Davg = Iravg·tf, where Iravg was average spatial irradiance of whole duct, tf was the time particle pass through duct, tf = V/Q, where V was the volume of duct, Q was air flow rate.

c

Calculated by Davg=(D1+D2+ … +Di)/n, where n was the total number of particles sampled in outlet plane, Di was the UV dose of particle i.