Table 2.
Element | Input | Output | Quantity/Day | Quantity/FU | Unit | Notes |
---|---|---|---|---|---|---|
Sewage Treatment Unit | Capacity 1.9 × 108 L/year (20 years lifetime) |
2.60 × 10−4 | 5.22 × 10−7 | items | EcoSpold 2 | |
Wastewater Qin | 528 m3/day | 528 | 1.06 | m3 | ||
Influent Pump Electricity | 7.67 kW × 7.34 h/day | 56.3 | 1.13 × 10−1 | kWh | ||
Equalization Tank Mixer Electricity | 1.2 kW × 24 h/day | 28.8 | 5.77 × 10−2 | kWh | ||
Denitrification Mixer Electricity | 1.2 kW × 24 h/day | 28.8 | 5.77 × 10−2 | kWh | ||
Nitrification Blowers Electricity | 2 × 10 kW × 24 h/day | 480 | 9.62 × 10−1 | kWh | ||
Sedimentation Bridge Electricity | 0.75 kW × 24 h/day | 18 | 3.61 × 10−2 | kWh | ||
Sludge Circulation Pump Electricity | 4 kW × 24 h/day | 96 | 1.92 × 10−1 | kWh | ||
Sludge Removal Pump Electricity | 0.25 kW × 6 h/day | 1.5 | 3.01 × 10−3 | kWh | ||
Q Sludge Out | 269.3 Kg/day | 269.3 | 5.40 × 10−1 | Kg | to landfill | |
Sludge Transportation | 35 Km × 29 m3/day | 9425.5 | 1.89 × 101 | Km Kg | Lorry EURO6 10 tons |
|
PAC (flocculent) | 90.6 kg/day | 90.6 | 1.82 × 10−1 | Kg | EcoSpold 2 iron(II) chloride |
|
Polyelectrolyte | 0.966 kg/day | 0.97 | 1.94 × 10−3 | Kg | EcoSpold 2 aluminium sulfate, powder |
|
Mixer Electricity | 0.41 kW × 24 h/day | 9.84 | 1.97 × 10−2 | kWh | ||
Polyelectrolyte Pump Electricity | 0.40 kW × 24 h/day | 9.6 | 1.92 × 10−2 | kWh | ||
Flocculation Mixer Electricity | 0.41 kW × 24 h/day | 9.84 | 1.97 × 10−2 | kWh | ||
Drum Filter Electricity | 0.50 kW × 6 h/day | 3.0 | 6.01 × 10−3 | kWh | ||
Treated Wastewater Qout | 499 m3/day | 499 | 1.00 | m3 |