Table 3.

Decay constants for 0.3 μm particles and time needed to remove 95 % and 100 % aerosol particles accumulated from incense burn without room ventilation and with the portable air cleaner off and on.

RM # Qe (#/m3)
ACHpac Ko Kpac Time to 95 % removal
Time to 100 % removal
pac off pac on pac off pac on pac off pac on
022 7.8 × 107 6.3 × 107 18 0.4 20.2 >30 8 >30 9
031 7.3 × 107 6.0 × 107 16 1.1 16.8 >30 9 >30 11
032 6.6 × 107 3.4 × 107 22 −0.4 23.2 >30 5 >30 5
033 5.9 × 107 5.4 × 107 15 −0.6 14.7 >30 9 >30 9
Mean 6.9 × 107 5.2 × 107 17.5 0.1 18.7 8 9
SD 8.3 × 106 1.3 × 107 3.2 0.8 3.7 2 3

Qe– number of 0.3 μm particles per cubic meter (#/m3) accumulated from 5 min of incense burn with portable air cleaner (pac) off or on. ACHpac – equivalent air change per hour provided by the portable air cleaner. Ko – decay constants with portable air cleaner off. Kpac – decay constants with portable air cleaner on.