Skip to main content
. 2021 Feb 4;193:107659. doi: 10.1016/j.buildenv.2021.107659

Table 1.

Minimum required ventilation flow rates for different building usage types in the Dutch Building Code [76].

Function Requirement in dm³/s/person
New buildings Existing buildings
Childcare 6.5 3.44
Meeting 4 2.12
Healthcare, bed area 12 3.44
Healthcare, other areas 6.5 3.44
Industrial 6.5 3.44
Office 6.5 3.44
Hotel, dormitory 12 6.40
Education 8.5 3.44
Sports 6.5 3.44
Shopping 4 2.12