. 2021 Feb 10;7(2):e06156. doi: 10.1016/j.heliyon.2021.e06156

Performance of a domestic refrigerator in varying ambient temperatures, concentrations of TiO2 nanolubricants and R600a refrigerant charges

DS Adelekan a,, OS Ohunakin a,b, MH Oladeinde c, Gill Jatinder d, OE Atiba a, MO Nkiko e, AA Atayero a,f
PMCID: PMC7892924  PMID: 33659731

Abstract

This study investigates the effect of varying test conditions including ambient temperature (19, 22, and 25 °C), mass charges of R600a refrigerant (40, 50, 60, and 70 g), and concentrations of TiO2 nanolubricant (0, 0.2 and 0.4 g/L) on the performance of a slightly modified 100g R134a domestic refrigeration system. The investigated parameters include evaporator air temperature, energy consumption, coefficient of performance, and second law efficiency of the system. The results showed that the performance of the refrigeration system at 0.2 and 0.4 g/L concentrations of TiO2 nanolubricant, improved at optimum ambient temperature and R600a mass charge conditions. At optimum conditions, the evaporator air temperature and energy consumption reduced within the range 5.26 to 26.32 %, and 0.13 to 14.09 % respectively, while the coefficient of performance and second law efficiency increased within the range 0.05 to 16.32 %, and 2.8 to 16 %, respectively. However, at other conditions (non-optimum), the energy consumption and evaporator air temperature were higher and within the range 0.28 to 8.26 %, and 5 to 40 % respectively, while the coefficient of performance and second law efficiency reduced within the range 2.99 to 10.94 %, and 0.55 to 13.43 % respectively. In conclusion, we observed variations in the performance of the refrigerator with varying test conditions.

Keywords: R600a, Refrigerator, TiO2 nanoparticle, Ambient temperature


R600a, Refrigerator, TiO2 nanoparticle, ambient temperature.

1. Introduction

Replacement of conventional refrigerants such as R134a and R12, in domestic refrigerators is essential and currently ongoing. This effort is to reduce: (i) the impact of conventional refrigerants on climate change (especially Ozone depletion and/or high global warming) [1], (ii) high energy consumption and exergy destruction [2], thereby enabling compact design of refrigerator systems [3], and (iii) rate of refrigerant leakage to the environment [4]. Design simplicity and economic advantage of domestic refrigerators are increasing their applications in households, and commercial buildings. According to International Institute of Refrigeration (IIR), more than 17 % of energy consumption globally are from refrigeration and air conditioning systems [5]. Therefore, environmental protection protocols and directives have commenced the restrictions of conventional refrigerants such as hydrochlorofluorocarbons (HCFCs), chlorofluorocarbons (CFCs) and hydrofluorocarbons (HFCs). Interest in the adoption of hydrocarbon (HC) compounds as working fluids is rapidly growing in recent decades, despite their flammability side-effects [6]. Many studies discussed the safe and efficient applications of hydrocarbon refrigerants in domestic refrigerators [4, 7, 8]. The work of Corberán et al. [9], considered the safety of using charges of hydrocarbon-based refrigerants that are less than or equal to 150g in any domestic refrigerator when their operating temperature, pressure, and ventilation/airflow conditions were reached. Fire incidence in hydrocarbon-based refrigerators can only occur under the following conditions: (i) fire sources should be greater than 290 kJ and 768K, (ii) concentration of the leaked hydrocarbon refrigerant in the enclosed space must be higher than its low flammability limit, and (iii) proper air-hydrocarbon mixture [6]. Across many European countries, the use of hydrocarbon refrigerants in domestic refrigerators is prohibited. However, effort to model the flammability of hydrocarbon refrigerant is increasing. Rasti et al. [8] concluded that charges and flammability limit of hydrocarbon refrigerants correlate directly. Hydrocarbon refrigerants are also found to be suitable retrofits to conventional refrigerants. They are environmentally benign with neutral reaction with the Ozone layer and having low global warming potential [6]. Hydrocarbon refrigerants are compatible with non-hygroscopic mineral-based compressor oils and existing vapor compression refrigeration sub-components [6]. An attempt to improve the performance of a deliberately lowered (i.e., 40g charge) liquefied petroleum gas (LPG) refrigerant in a domestic refrigerator infused with TiO2 based nano-lubricants, was effective in the work of Adelekan et al. [4]. A review of the adoption of hydrocarbon refrigerants in heating, ventilation and air conditioning systems (HVAC) was carried out in the work of Harby [6]. Improvement in the environmental efficiency, energy efficiency, coefficient of performance, reduction in refrigerant mass charges and drop in compressor discharge temperature were observed in the systems. However, the work of Fatouh and Kafafy [10] observed some shortcomings in domestic refrigerators being substituted experimentally and theoretically with LPG and R600a refrigerants. In the work of McLinden et al. [11], similar deficiencies were described as factors limiting hydrocarbon refrigerant applications in refrigeration and air conditioning systems. The need to efficiently optimized safety, performance and economy of hydrocarbon refrigeration systems operated across wide range of ambient temperatures have recently increased the consideration of pure and mixture of R600a refrigerant (See Table 1). In addition, the need for increased efficiencies in hydrocarbon R600a refrigerant driven refrigeration systems, has justified the applications of nanofluids.

Table 1.

Application and Performance of Pure and Mixture of R600a refrigerant.

S/N Refrigerant Author(s) Description Conclusion
1 R600a Hossain et al. [12] Development of a solar-powered R600a refrigerator The SAR system attained at least -15 °C and functioned adequately as a vaccine storage device
2 R600a and R290 Zhongcheng et al. [13] Theoretical evaluation of parallel compression refrigeration system The system considerably minimized the evaporator heat transfer irreversibility.
3 R600a Susanto et al. [14] Investigated the influence of R600a refrigerant mass charge on a refrigerator The optimum mass charge (38g) of R600a gave energy conservation of 28 %–38 % in the refrigerator.
4 R600a, R1234yf, R1234ze and R717 Zhaohu et al. [15] Performance investigation of refrigerants in an oil-free compression refrigeration system The refrigerants worked safely in the system
5 R600a Shono et al. [16] Evaluated the initiations of wear based on low viscosity lubricant Proposed an innovative methodology for limiting wear frictions in a compressor using R600a refrigerant

Recently, applications of nanofluids in domestic refrigerators have shown numerous prospects [17, 18]. Nanofluids are stable suspensions of nanoparticles within suitable base fluids (e.g., engine oil, compressor lubricants, ethylene glycol, water, refrigerant, etc.); they are ensured to be homogenous when dispersed in the base fluid. Nanoparticles are solids with a maximum size range of 1–100nm, and their small dimensions and large specific surface areas enhance efficiencies of thermal systems [19]. Applications of nanoparticles in fluids improve the thermodynamic properties of many base-fluids, and these leads to the initiation of molecular scale thermophoresis and Brownian motion [19]. Since nanoparticles are solids with higher thermal conductivities than liquids or gaseous fluids, their mixture produce improve fluids known as nanolubricants or nanorefrigerants. While nanolubricant is a mixture of nanoparticles and compressor lubricant, nanorefrigerant is a mixture of nanoparticles and refrigerant. Nanolubricant induces rolling friction effects within compressors thereby increasing the durability and efficiency of refrigerators [18]. In the work of Ohunakin et al. [20], the energetic performance of a domestic refrigerator infused with SiO2 based nanolubricants was found to improve considerably. Nanofluids in domestic refrigerators found applications: (i) to enhance the energetic and exergetic performances of refrigerators [21], (ii) refrigerants forced boiling and convective heat transfer [22], (iii) reduction in discharge temperature [4], (iv) compressor lubricant tribology characteristics in [23]; and (v) reduction in refrigerant charges [4]. In the work of Gill et al. [21], an experimental substitution of R134a working fluid with LPG refrigerant using TiO2, Al2O3, and SiO2 nanolubricants in a domestic refrigerator was found to improve the energetic and exergetic performance of the system. Similarly, the application of selected concentrations of TiO2 nano-lubricants in a domestic refrigerator using R600a refrigerant were observed to work safely and also enhance the energetic performance in Bi et al. [7].

In this study, the authors investigated the influence of TiO2 nanolubricants, ambient temperature, and mass charges of R600a refrigerant in a domestic refrigeration system. This study aims to examine the effect of these factors on energy and exergy characteristics like evaporator air temperature, energy consumption, coefficient of performance, and second law efficiency, respectively. The sparse investigations on the influence of the selected factors on the performance of refrigeration systems is the major justification for this work (See Table 2).

Table 2.

Nanolubricants Performance in Pure and Mixture of R600a refrigerant driven refrigerator.

S/N Refrigerant Author(s) Description Conclusion
1 R600a Okotie et al. [24] Investigated influence of TiO2 nanolubricants on the energy performance of a refrigerator The use 0.6 g/L gave the best energy performance in the system
2 R600a and LPG Gill et al. [25] Evaluated performance of TiO2 nanolubricant in a refrigerator using R600a and LPG refrigerant The nanolubricant improved tribological and energy performance
3 R600a Adelekan et al. [26] Graphene-based nanolubricant was tested in a refrigerator using R600a refrigerant The nanolubricant worked safely and efficiently
4 R600a and LPG Ajuka et al. [27] Energy and exergy performance of a refrigerator using TiO2 nanolubricant was studied The nanolubricant improved the energy and exergy performance of the system at optimal charges of the refrigerant
5 R600a Lou et al. [28] Evaluated the performance of graphite nanolubricants on a domestic refrigerator using R600a Pull downtime, and suction, discharge, cabinet temperature, and pressures of the system reduced considerably.

2. Materials and method

2.1. Experimental test rig and instrumentation

In this work, the test rig was a modified 100g R134a domestic refrigerator having appropriate valves along the compressor suction and discharge lines. These modifications enabled fitting of digital pressure gauges and charging and discharging of spent refrigerant from the system. Digital type K thermocouples (Victor DM 1502) having measurement accuracy of ±0.2 °C and a wattmeter (RoHS-D02A) with (±0.4 W) were attached to the system (See Figures 1 and 2 for experimental schematic diagram and setup respectively). HONGSEN HS-5100L and HS-5100H digital pressure gauges were used to measure the refrigerant suction (P1) and discharge (P2) pressures respectively, while the installed thermocouples monitored the suction (T1), discharge (T2), condensing (T3) and cabinet air (Tair) temperatures of the refrigerant. Watt meter was connected to capture the instantaneous energy consumption of the system (See Table 3 for test rig description and measuring instrument details).

Figure 1.

Figure 1

Schematic of the refrigeration system (Source: Gill et al. [21]).

Figure 2.

Figure 2

Experimental Setup of Test Rig (Source: Ohunakin et al. (2018)).

Table 3.

Test Rig Description and Measuring Instrument Details.

S/N Detail Description Specification
A Test Rig Evaporator Plate type
Refrigerant R134a
Refrigerant Mass Charge 100g
Condenser Fin on tube Air cooled
Compressor Oil POE
Dryer Non-Adiabatic
Capillary tube Length 2m
Compressor HFC
Number of Doors 1
B Measuring Instrument Pressure Gauge Digital
Thermocouple Digital (Victor DM1502)
Refrigerant Weighing Scale Camry (ASC-10-ZC)
Nanoparticle Weighing Scale OHAUS PA114
Wattmeter 1 - 3000 W
Refrigerant Flow meter Coriolis

The modified test rig consists of built-in evaporator, R134a compressor, air-cooled condenser, a non-adiabatic dryer, and a capillary tube. The compressor of the test rig receives the refrigerant at low pressure and temperature saturated vapor state from the evaporator, and delivers it as compressed superheated high pressure and temperature vapor state to the condenser. Heat rejection to the environment occurs as the superheated vapor state refrigerant moves through the condenser at constant pressure (that is an isobaric process). At the exit of the condenser, the working fluid flows to the dryer as a saturated liquid. The dryer then expands the high pressure saturated liquid refrigerant to low pressure saturated liquid/vapor mixture at constant enthalpy (an isenthalpic process). The evaporator receives the low pressure uniformly flowing saturated liquid/vapor mixture refrigerant from the capillary tube. The refrigerant absorbs heat at constant pressure as it moves through the evaporator, where it changes to a saturated vapor state. The refrigerant undergoes a continuous repetition of the process cycle as it enters the compressor. The test environment is a closed door environment equipped with a 2-horsepower air-conditioning system to stabilize the required ambient temperature. The environment also had surface thermometers for monitoring the average ambient tempetrature of the test environment during the investigation. The relative humidity condition of the test environment is 75%.

2.2. Nanolubricant preparation

In preparing the nanolubricants, 15nm TiO2 nanoparticle (procured from Aldrich Chemistry) is dispersed in locally purchased mineral-based compressor lubricants. Figures 3 and 4 shows the scanning electron micrograph and distribution of the TiO2 nanoparticle. As illustrated in Figure 3, the TiO2 nanoparticle is spherical in shape and agglomerate naturally. Since agglomeration initiate clustering and sedimentation of nanoparticles within nanofluids, ultrasonicating the TiO2 nanoparticle-compressor lubricant mixtures is necessary. Figure 4 confirms that the nanoparticle contains very high purity of TiO2 compound. Sonification is a known method of eliminating clustering and sedimentation within nanofluids [25]. Sonification of the respective nanoparticles and compressor lubricant mixtures were carried out using Branson M2800H ultrasonicator. Prior to sonification, mass fractions of nanoparticles were obtained using a digital weighing balance (Ohaus Pioneer TM PA114) while a measuring cylinder was used to measure the required volume of mineral oil compressor lubricant. We evaluated the stability of the nanofluids after sonification using sedimentation and spectral analysis. Sedimentation observation results of the sonicated samples at 0 and 24 h is shown in Figures 5 and 6. The high resolution digital camera image of the sonicated samples shows stability with negligible nanoparticle sedimentation. Furthermore, the absorbance spectral of the nanolubricants over a range of wavelengths were obtained from UV visible spectrometer (HELIOS ZETA UV VIS). The standard deviations in the respective absorbance coefficients of the prepared nanolubricants were found to be less than 5 % during the test investigation period. Inference from estimating the standard deviations of the absorbance coefficient substantiates stability within the nanolubricants. Authors’ previous study of the stability of nanolubricants in accordance to Beer law, authenticate high stability (See Figure 7 and Gill et al [29]).

Figure 3.

Figure 3

TiO2 nanoparticles Image from Scanning Electron Microscope.

Figure 4.

Figure 4

EDX analysis of the TiO2 nanoparticle (Source: Gill et al. [21]).

Figure 5.

Figure 5

Ultrasonificated nanolubricants After 24 h.

Figure 6.

Figure 6

Ultrasonificated nanolubricants at 0 h.

Figure 7.

Figure 7

Variation of the nanolubricant absorbance.

2.3. Theory/calculation

The equation adopted to calculate performance of the TiO2 nanolubricants, mass charges and ambient temperatures in the test refrigerator are given as Eqs. (1), (2), and (3):

Energetic Characteristics

CoefficientofPerformance=COPc=qw=m˙(h1h3)m˙(h2h1)=(h1h3)(h2h1) (1)
CarnotCoefficientofPerformane=COPcarnot=TeTcTe (2)
Secondlawefficiency=COPcCOPcarnot (3)

where m˙ is the refrigerant mass flow rate (kJ/m3), h1 is saturated vapor enthalpy (kJ/kg), h2 is superheated vapor enthalpy (kJ/kg), h3 is the saturated liquid enthalpy (kJ/kg), Te is the refrigerant evaporating temperature (K), Tc is the refrigerant condensing temperature (K). All estimations were carried out under the following assumptions: (i) steady state condition, (ii) an equal discharge, and condensing pressures, and (iii) equal condensing and evaporator inlet enthalpies.

2.4. Experimental procedure

In conducting this experiment, a slightly modified 100g R134a refrigerator is retrofitted with charges of R600a refrigerant ranging from 40 to 70 g at varying concentrations of TiO2 nanolubricants (0. 0.2 and 0.4 g/L) and selected ambient temperatures (19, 22 and 25 °C). All experimental trials were under a no-load, continuous operation of the compressor. Variation of pressures (P1, P2), temperatures (Tair, T1, T2, T3), mass flow rates, and compressor power consumptions of the system is observed at 4 h of steady-state condition. After obtaining relevant refrigerant properties (i.e., suction vapor enthalpy (h1), superheated vapor enthalpy (h2), and saturated liquid enthalpy (h3)) from NIST Ref-Prop 9.1 software, the required energy characteristics and second law efficiency were estimated. Furthermore, each trial was carried out three times to ascertain the integrity of the experiments.

2.5. Uncertainty of measured parameters

In this study, the uncertainties of the measured parameters were estimated using methodology of measurement uncertainties in Schultz and Cole (1979). Methods described in Schultz and Cole method [30] and Ohunakin et al. [31] defined uncertainty of the desired parameter like UF using Eq. (4):

UF=[i=1n(FViUwi)2]0.5 (4)

where UF is the total uncertainty, Uwi is the uncertainty of each independent variable and n is the number of total variables (see Gill et al. [25]). Table 4 illustrates the uncertainties of the parameters. For all the parameters, the maximum percentage uncertainty was less than 3%in accordance to all range of experimental conditions described in Table 5.

Table 4.

Uncertainty analysis of measuring instruments.

Parameter T1 T2 T3 Tair P1 P2
Uncertainty (±) 0.2OC 0.2OC 0.2OC 0.2OC 2kPa 4kPa

Table 5.

Range and condition of experiment.

S/N Test Details Range and Condition
1 Nanoparticle Type TiO2
Size 15nm
Shape Spherical
Nanolubricant concentration 0, 0.2, and 0.4 g/L
2 Refrigerant Type R600a
Mass charge 40, 50, 60 and 70 g
3 Compressor Lubricant Mineral Oil 250 ml
4 Environment Temperature 19, 22, and 25 °C
Relative humidity 75 %

2.6. Regression model

The need for the significances of the test conditions (that is nanolubricant concentration, R600a mass charge and ambient temperature) in determining the investigated parameters (evaporator air temperature, power consumption, coefficient of performance and second law efficiency) for the refrigeration system, justified the analysis of variance and regression model estimations provided in Table 6a-d. The developed regression models validity was determined by respective statistical coefficient of correlation R2 and hypothetical P values (where maximum R2 and P value ≤ 0.05 are desirable). It was observed from the result provided in Table 6a-d that the output evaporator air temperature, power consumption, coefficient of performance and second law efficiency of the refrigeration system were significantly influenced by the test conditions.

Table 6a.

Evaporator air temperature statistical summary.

Evaporator Air Temperature
Source DF Adj SS Adj MS F-Value P-Value
Regression 6 179.592 29.932 12.88 0.000
Mass charge 1 35.260 35.260 15.17 0.001
Concentration 1 23.328 23.328 10.04 0.004
Ambient temperature 1 9.600 9.600 4.13 0.051
Mass charge∗Mass charge 1 40.111 40.111 17.26 0.000
Concentration∗Concentration 1 21.125 21.125 9.09 0.005
Concentration∗Ambient temperature 1 12.250 12.250 5.27 0.029
Error 29 67.408 2.324
Total
35
247.000



Coefficients
Term
Coef
SE Coef
T-Value
P-Value
VIF
Constant 1.41 8.31 0.17 0.867
Mass charge -1.092 0.280 -3.89 0.001 152.25
Concentration -47.7 15.1 -3.17 0.004 93.67
Ambient temperature 0.333 0.164 2.03 0.051 2.50
Mass charge∗Mass charge 0.01056 0.00254 4.15 0.000 152.25
Concentration∗Concentration 40.6 13.5 3.01 0.005 13.00
Concentration∗Ambient temperature 1.458 0.635 2.30 0.029 83.17

Regression Equation:

Evaporator Air Temperature = 1.41–1.092 Mass charge - 47.7 Concentration +0.333 Ambient temperature +0.01056 Mass charge∗Mass charge +40.6 Concentration∗Concentration +1.458 Concentration∗Ambient temperature.

Table 6b.

Coefficient of performance statistical summary.

Coefficient of Performance
Source DF Adj SS Adj MS F-Value P-Value
Regression 6 0.64282 0.10714 5.52 0.001
Mass charge 1 0.39270 0.39270 20.23 0.000
Concentration 1 0.15291 0.15291 7.88 0.009
Ambient temperature 1 0.01080 0.01080 0.56 0.462
Mass charge∗Mass charge 1 0.40111 0.40111 20.66 0.000
Concentration∗Concentration 1 0.10967 0.10967 5.65 0.024
Concentration∗Ambient temperature 1 0.07701 0.07701 3.97 0.056
Error 29 0.56297 0.01941
Total
35
1.20579



Coefficients
Term Coef SE Coef T-Value P-Value VIF

Constant 0.320 0.760 0.42 0.676
Mass charge 0.1153 0.0256 4.50 0.000 152.25
Concentration 3.86 1.38 2.81 0.009 93.67
Ambient temperature 0.0112 0.0150 0.75 0.462 2.50
Mass charge∗Mass charge -0.001056 0.000232 -4.55 0.000 152.25
Concentration∗Concentration -2.93 1.23 -2.38 0.024 13.00
Concentration∗Ambient temperature -0.1156 0.0581 -1.99 0.056 83.17

Regression Equation.

Coefficient of Performance = 0.320 + 0.1153 Mass charge +3.86 Concentration +0.0112 Ambient temperature - 0.001056 Mass charge∗Mass charge - 2.93 Concentration∗Concentration - 0.1156 Concentration∗Ambient temperature.

Table 6c.

Energy consumption statistical summary.

Energy consumption
Source DF Adj SS Adj MS F-Value P-Value
Regression 4 219.87 54.97 5.39 0.002
Mass charge 1 167.10 167.10 16.40 0.000
Concentration 1 43.80 43.80 4.30 0.047
Mass charge∗Mass charge 1 170.30 170.30 16.71 0.000
Concentration∗Concentration 1 48.51 48.51 4.76 0.037
Error 31 315.90 10.19
Total
35
535.77



Coefficients
Term
Coef
SE Coef
T-Value
P-Value
VIF
Constant 136.4 15.7 8.70 0.000
Mass charge -2.378 0.587 -4.05 0.000 152.25
Concentration -24.4 11.7 -2.07 0.047 13.00
Mass charge∗Mass charge 0.02175 0.00532 4.09 0.000 152.25
Concentration∗Concentration 61.6 28.2 2.18 0.037 13.00

Regression Equation.

Energy Consumption = 136.4–2.378∗Mass charge - 24.4∗Concentration +0.02175 Mass charge∗Mass charge.

+ 61.6 Concentration∗Concentration.

Table 6d.

Second law efficiency statistical summary.

Second law efficiency
Source DF Adj SS Adj MS F-Value P-Value
Regression 4 0.048897 0.012224 6.77 0.000
Mass charge 1 0.029785 0.029785 16.49 0.000
Concentration 1 0.009816 0.009816 5.43 0.026
Mass charge∗Mass charge 1 0.031211 0.031211 17.28 0.000
Concentration∗Concentration 1 0.013612 0.013612 7.54 0.010
Error 31 0.056003 0.001807
Total
35
0.104900



Coefficients
Term
Coef
SE Coef
T-Value
P-Value
VIF
Constant -0.178 0.209 -0.85 0.401
Mass charge 0.03174 0.00782 4.06 0.000 152.25
Concentration 0.365 0.156 2.33 0.026 13.00
Mass charge∗Mass charge -0.000294 0.000071 -4.16 0.000 152.25
Concentration∗Concentration -1.031 0.376 -2.75 0.010 13.00

Regression Equation.

Second law efficiency = -0.178 + 0.03174 Mass charge +0.365 Concentration.

- 0.000294 Mass charge∗Mass charge - 1.031 Concentration∗Concentration.

3. Results and discussion

The steady state experimental and regression model results of the modified domestic refrigerator across selected ambient temperatures, TiO2 nanolubricant concentrations and R600a refrigerant mass charges is shown in Table 7.

Table 7.

Experimental Performance of the modified domestic refrigerator in the selected operating conditions.

S/N Ambient temperature Nano. Conc. R600a Mass Experimental
Regression Model
Evap. air Temp. COP Power 2nd % Evap. air Temp. COP Power 2nd %
1 19 0 40 -19 3.42 77.4 0.62 -19.05 3.46 76.08 0.62
2 19 0.2 40 -24 3.66 74 0.68 -21.42 3.67 73.66 0.65
3 19 0.4 40 -20 3.8 73.8 0.6 -20.55 3.65 76.18 0.6
4 19 0 50 -20 3.73 72.7 0.65 -20.46 3.66 71.88 0.67
5 19 0.2 50 -21 4.03 65.7 0.75 -22.84 3.87 69.46 0.71
6 19 0.4 50 -22 3.81 72.9 0.64 -21.97 3.85 71.97 0.66
7 19 0 60 -20 3.65 74.3 0.63 -19.77 3.65 72.02 0.67
8 19 0.2 60 -20 3.7 70.7 0.7 -22.14 3.86 69.6 0.7
9 19 0.4 60 -22 3.83 72 0.66 -21.27 8.85 72.12 0.65
10 19 0 70 -19 3.32 82 0.56 -16.96 3.43 76.52 0.6
11 19 0.2 70 -16 3.64 75.3 0.58 -19.33 3.64 74.1 0.64
12 19 0.4 70 -20 3.47 82.4 0.52 -18.46 3.63 76.61 0.58
13 22 0 40 -17 3.55 76.1 0.6 -18.05 3.49 76.08 0.62
14 22 0.2 40 -19 3.67 73.5 0.64 -19.55 3.63 73.66 0.65
15 22 0.4 40 -18 3.55 75 0.63 -17.8 3.55 76.18 0.6
16 22 0 50 -20 3.56 74.1 0.66 -19.46 3.69 71.88 0.67
17 22 0.2 50 -22 3.69 74 0.65 -20.96 3.84 69.46 0.71
18 22 0.4 50 -19 3.63 73 0.66 -19.22 3.75 71.97 0.66
19 22 0 60 -18 3.61 73.1 0.65 -18.77 3.68 72.02 0.67
20 22 0.2 60 -20 4.2 62.8 0.78 -20.27 3.83 69.6 0.7
21 22 0.4 60 -19 3.78 70.8 0.67 -18.52 3.74 72.12 0.65
22 22 0 70 -18 3.59 72.2 0.68 -15.96 3.46 76.52 0.6
23 22 0.2 70 -19 3.7 70.4 0.7 -17.46 3.61 74.1 0.64
24 22 0.4 70 -16 3.59 74.9 0.6 -15.71 3.52 76.61 0.58
25 25 0 40 -16 3.41 75.2 0.64 -17.05 3.52 76.08 0.62
26 25 0.2 40 -18 3.71 71.8 0.65 -17.68 3.6 73.66 0.65
27 25 0.4 40 -15 3.31 80.9 0.55 -15.05 3.44 76.18 0.6
28 25 0 50 -18 3.67 67.9 0.75 -18.47 3.72 71.88 0.67
29 25 0.2 50 -21 3.78 70 0.71 -19.09 3.8 69.46 0.71
30 25 0.4 50 -17 3.72 70 0.68 -16.47 3.64 71.97 0.66
31 25 0 60 -17 3.95 70.2 0.62 -17.77 3.72 72.02 0.67
32 25 0.2 60 -19 3.52 76 0.62 -18.4 3.79 69.6 0.7
33 25 0.4 60 -17 3.73 71.1 0.66 -15.77 3.64 72.12 0.65
34 25 0 70 -15 3.51 74.3 0.63 -14.96 3.5 76.52 0.6
35 25 0.2 70 -16 3.43 76.4 0.61 -15.59 3.57 74.1 0.64
36
25
0.4
70
-9
3.46
74
0.59
-12.97
3.42
76.61
0.58
R2 0.85 0.27 0.64 0.68
MPE (%) 0.51 0.0074 0.51 0.005
RMSE 1.22 0.125 2.96 0.039

Where MPE is mean percentage error, RMSE is root mean square error, R2 coefficient of correlation.

3.1. Variation of evaporator air temperature

The effect of varying TiO2 nanolubricants concentrations (0, 0.2 and 0.4 g/L), mass charges of R600a refrigerant (40, 50, 60 and 70 g) and ambient temperatures (19, 22 and 25 °C) on the evaporator air temperatures of the system is shown in Figure 8(a-c). It can be observed that the interactions between the selected mass charges of R600a refrigerant, ambient temperatures, and nanolubricant concentrations significantly influenced the evaporator air temperature of the system. Increasing the mass charge of R600a refrigerant and TiO2 nanolubricant concentrations, brought about a reductions and increase in the evaporator air temperature of the system. But, increasing the ambient temperature increased the evaporator air temperature of the refrigerator. The least evaporator air temperature of the system is -24 °C at 40g R600a, 0.2 g/L nanolubricant and 19 °C ambient temperature, while the maximum is got as -9 °C at 70g R600a, 0.4 g/L and 25 °C ambient temperature. The use of 0.2 g/L nanolubricant resulted in lower evaporator air temperatures than other concentrations regardless of the charge of refrigerant. However, at ambient temperature of 19 °C, more concentration of TiO2 nanolubricant (i.e., 0.4 g/L) gave the least evaporator air temperatures. Overall, infusion of TiO2 nanolubricant to the refrigeration system reduced the evaporator air temperatures by 5.26 to 26.32 % when compared to the pure lubricant. This result affirms that nanorefrigerant heat transfer rate varies with temperature and nanorefrigerant concentration. As established in the work of Ohunakin et al. (2017), adding TiO2 nanoparticles to the compressor lubricant enhanced the evaporator boiling heat transfer rate via thermophoresis and Brownian motion initiation. These conditions were primarily driven by improved refrigerant–compressor oil solubility and working fluid thermal conductivity. However, at high ambient temperature, intensified thermal penetration or infiltration through the refrigerator walls increased the heat gain and evaporator air temperature of the system (see Harrington et al. 2018). In addition, increasing the R600a refrigerant mass charge increased the evaporator pressure and decreased the degree of superheating due to refrigerant flooding of the evaporator; thus resulting to increasing evaporator air temperature (see Belman-Flores et al, (2017)).

Figure 8.

Figure 8

(a–c): Variation of evaporator air temperature across 19, 22 and 25 °C ambient temperatures.

3.2. Variation of energy consumption

Figure 9(a-c) describes the steady-state energy consumption of the system. The energy consumptions of the refrigeration system vary differently across the selected ambient temperatures, nanolubricant concentrations, and charges of R600a refrigerant. Increasing the mass charges of R600a refrigerant decreased and increased the energy consumption of the refrigerator regardless of the selected ambient temperature and TiO2 nanolubricant concentrations. Furthermore, reducing ambient temperature, will increase energy consumption of the refrigeration system. We observed a reduction in the energy consumptions with applications of TiO2 nanolubricants within the test rig especially at ambient temperatures of 19 °C and 22 °C. More energy was required at 25 °C of ambient temperature operation of the refrigerator with 0.2 g/L and 0.4 g/L concentrations of TiO2 nanolubricants, when compared to that of the pure lubricant (i.e., 0 g/L). The least energy consumption within the refrigeration system was obtained as 62.80 W at 60 g charge of R600a, 0.2 g/L nanolubricant concentration, and at 22 °C of ambient temperature condition, while 70g charge of R600a, 0.4 g/L nanolubricant concentration, at 19 °C ambient temperature condition gave the highest energy consumption of 82.4 W. A reduction in energy consumption was observed within the range 0.13 to 14.09 % at appropriate concentration of TiO2 nanolubricant, ambient temperature and R600a charge respectively. A slightly higher energy consumptions ranging within 0.28 to 8.26 % were observed at non-optimum conditions. Regardless of the mass charges of R600a refrigerants within the refrigeration system, the use of 0.2 g/L of TiO2 nanolubricant gave the least energy consumption at 19 °C and 22 °C of ambient temperatures. However, the refrigeration system with 0.2 g/L and 0.4 g/L nanolubricants, consumed more energy than the pure lubricant at 25 °C ambient temperature. These results obtained show that energy consumption of refrigerators are influenced by varying ambient temperatures, nanolubricant concentrations and refrigerant mass charges. Conventionally, energy consumption of refrigerators varies directly with pressure ratio as established in the work of Gill et al. (2018). Thus, results indicate that increasing the R600a mass charge slightly decrease and increase with both pressure ratio and energy consumption of the system. While, increasing the surrounding ambient temperature of the refrigerator invariably increased the condensing temperature, and condenser and evaporator pressures. As reported by Harrington et al. [32], these increased pressures invariably reduce the compressor volumetric efficiency and mass flow rate of flowing refrigerant; thus prolonging compressor run time and increasing energy consumption. Application of TiO2 nanoparticles to the system further reduced the pressure ratio and energy consumption of the refrigerator. Inference from existing studies attributed these reductions to minimized friction, rubbing and wear effects within the compressor. As suggested by Jia et al. [33], the nanolubricants induced mending, lubricating, polishing, coating and balling bearing effects on moving components of the compressor. This invariably leads to minimized pressure drop and energy consumption within the system.

Figure 9.

Figure 9

(a–c): Variation of energy consumption across 19, 22 and 25 °C ambient temperatures.

3.3. Variation of coefficient of performance

Figure 10(a-c) illustrates variations in the coefficient of performance of the system. The coefficient of performance of the system increased and decreased with increasing R600a refrigerant mass charges, and TiO2 nanolubricant concentrations. Comparing the effects of the selected TiO2 nanolubricant concentrations showed that 0.2 and 0.4 g/L TiO2 nanolubricants improved the coefficient of performance of the test refrigeration system only at ambient temperatures of 19 °C and 22 °C. At 25 °C ambient temperature, the coefficient of performance of the nanolubricants based refrigerator were lower at charges of R600a refrigerant greater than 50g. The observed enhancement in coefficient of performance of the system was due to the higher cooling capacities and lower compressor work done at steady state conditions. The percentage improvements in coefficient of performance of the system with increasing concentrations of TiO2 nanolubricants ranged between 0.05 % and 16.32 % when compared to the pure lubricants. On the other hand, reductions within the range of 1.31%–10.94 % in coefficient of performance of the system were observed only at ambient temperature of 25 °C, and non-optimum concentration of TiO2 nanolubricant, and selected charges of R600a refrigerant, when compared with the base fluids (see Figure 10c). The highest coefficient of performance within the refrigerator was 4.20 for 60g R600a using 0.2 g/L concentration of TiO2 nanolubricant at 22 °C, while the least coefficient of performance is 3.31 for 40g R600a using 0.4 g/L concentration of TiO2 nanolubricant at 25 °C ambient temperature. Overall, the highest and least coefficient of performance of the refrigerator was obtained using 0.2 g/L and 0 g/L respectively, at 22 °C ambient temperature. Observation revealed that the cumulative effects of lowered energy consumptions and evaporator air temperatures impacted by the TiO2 nanolubricants yielded higher cooling capacity which invariably increased the coefficient of performance of the system.

Figure 10.

Figure 10

(a–c): Variation of coefficient of performance across 19, 22 and 25 °C ambient temperatures.

3.4. Variation of second law efficiency

Variation of second law efficiency of the refrigeration system is shown in Figure 11(a-c). Increasing the mass charge of the refrigerant in the system, increased and decreased the second law efficiency of the refrigerator. The second law efficiency of the system at 0.2 g/L and 0.4 g/L TiO2 concentrations of nanolubriants was found to be better than the baseline (0 g/L) at ambinet temperatures of 19 °C and 22 °C, and worse at 25 °C. The comparison of the second law efficiencies of the nanolubricants increase within the range 2.8 to 16 %, and reduce within the range 0.5 to 11 %, when compared to the baseline. Improvements in the second law efficiency of the system were due to higher actual coefficient of performance and lower Carnot coefficient of performance. The lowest coefficient of performance of the system was 0.52 at 40g of R600a, 0.4 g/L TiO2 nanolubricant concentration at 25 °C ambient temperature, and the maximum given as 0.78 at 60g charge of R600a, 0.2 g/L concentration of TiO2 nanolubriant, at 22 °C. Overall, the use of 0.2 g/L concentration of nanolubicant gave the best performance within the refrigerator.

Figure 11.

Figure 11

(a–c): Variation of second law efficiency across 19, 22 and 25 °C ambient temperatures.

4. Conclusion

In this study, the performance of a slightly modified domestic refrigerator subjected to varying mass charges of R600a refrigerant, TiO2 nanoparticle concentrations and ambient temperatures was carried out. The following were concluded:

  • 1. The varying charges of R600a, TiO2 concentrations and ambient temperatures influenced significantly, the performance of the refrigerator. The evaporator air temperature of the refrigerator decreased and later increased with increasing R600a mass charge. The least evaporator air temperature were achieved at 22 °C using 0.2 g/L TiO2 nanolubricant concentration.

  • 2. The energy consumption of the system at 0.2 g/L and 0.4 g/L concentrations of TiO2 nanolubricant, reduced within the range 0.13 to 14.09 % when compared to the baseline concentration (0 g/L). The lowest value of energy consumption in the system was found to be 62.80 W using 60g charge of R600a refrigerant at 0.2 g/L and 22 °C, while the highest value was obtained as 82.40 W using 70g charge of R600a refrigerant at 0.4 g/L and 19 °C.

  • 3.

    The highest coefficient of performance in the refrigerator was obtained using 60g charge of R600a, with 0.2 g/L concentration of nanolubricant at 22 °C ambient temperature. The application of 0.2 g/L and 0.4 g/L nanolubricant was found to improve the second law efficiency of the refrigeration system at ambient temperatures of 19 °C and 22 °C, respectively.

Declarations

Author contribution statement

Adelekan D.S: Conceived and designed the experiments; Performed the experiments; Analyzed and interpreted the data; Contributed reagents, materials, analysis tools or data; Wrote the paper.

Ohunakin O.S, Nkiko M. O & Atayero A.A: Contributed reagents, materials, analysis tools or data; Wrote the paper.

Oladeinde M.H & Gill Jatinder: Conceived and designed the experiments; Analyzed and interpreted the data.

Atiba O.E: Contributed reagents, materials, analysis tools or data.

Funding statement

This research did not receive any specific grant from funding agencies in the public, commercial, or not-for-profit sectors.

Data availability statement

Data included in article/supplementary material/referenced in article.

Declaration of interests statement

The authors declare no conflict of interest.

Additional information

No additional information is available for this paper.

Acknowledgements

Authors are grateful to Covenant University and to Covenant University Centre for Research, innovation and Discovery (CUCRID) for providing necessary support for this work.

References

  • 1.Calm J.M. The next generation of refrigerants - historical review, considerations, and outlook. Int. J. Refrig. 2008;31:1123–1133. [Google Scholar]
  • 2.Bolaji B.O., Huan Z. Ozone depletion and global warming: case for the use of natural refrigerant - a review. Renew. Sustain. Energy Rev. 2013;18:49–54. [Google Scholar]
  • 3.Ghadiri F., Rasti M. The effect of selecting proper refrigeration cycle components on optimizing energy consumption of the household refrigerators. Appl. Therm. Eng. 2014;67:335–340. [Google Scholar]
  • 4.Adelekan D.S., Ohunakin S., Gill J., Atayero A., Diarra C.D., Asuzu A. Experimental performance of a safe charge of LPG refrigerant enhanced with varying concentrations of TiO2 nano-lubricant in a domestic refrigerator. J. Therm. Anal. Calorim. 2018;136:2439–2448. [Google Scholar]
  • 5.Coulomb D., Dupont J.L., Pichard A. The Role of Refrigeration in the Global Economy; IIR Document. IIR (International Institute of Refrigeration); Paris, France: 2015. 29th Informatory note on refrigeration technologies. [Google Scholar]
  • 6.Harby K. Hydrocarbons and their mixtures as alternatives to environmental unfriendly halogenated refrigerants: an updated overview. Renew. Sustain. Energy Rev. 2017;73:1247–1264. [Google Scholar]
  • 7.Bi S., Guo K., Liu Z., Wu J. Performance of a domestic refrigerator using TiO2-R600a nano-refrigerant as working fluid. Energy Convers. Manag. 2011;52:733–737. [Google Scholar]
  • 8.Rasti M., Aghamiri S., Hatamipour M.S. Energy efficiency enhancement of a domestic refrigerator using R436A and R600a as alternative refrigerants to R134a. Int. J. Therm. Sci. 2013;74:86–94. [Google Scholar]
  • 9.Corberán J.M., Segurado J., Colbourne D., Gonzálvez J. Review of standards for the use of hydrocarbon refrigerants in A/C, heat pump and refrigeration equipment. Int. J. Refrig. 2008;31:748–756. [Google Scholar]
  • 10.Fatouh M., Kafafy M. Experimental evaluation of a domestic refrigerator working with LPG. Appl. Therm. Eng. 2006;26:1593–1603. [Google Scholar]
  • 11.McLinden M.O., Kazakov A.F., Steven B., A Domanski P. A thermodynamic analysis of refrigerants: possibilities and tradeoffs for Low-GWP refrigerants. Int. J. Refrig. 2014;38:80–92. [Google Scholar]
  • 12.Hossain S., Saha, Rahman M.A., Himel M.A. ICASERT; 2019. Low Power Consuming Solar Assisted Vapor Compression Refrigerator to Preserve Emergency Medicines and Vaccines in Rural Areas, 1st International Conference on Advances in Science, Engineering and Robotics Technology; p. 8934783. 2019. [Google Scholar]
  • 13.Zhongcheng F., Chaochao F., Gang Y., Jianlin Y. Performance evaluation of a modified refrigeration cycle with parallel compression for refrigerator-freezer applications. Energy. 2019;188:116093. [Google Scholar]
  • 14.Susanto E., Alhamid M.L., Nasruddin B., Budiyanto M.A. An experimental investigation on mass effect of hydrocarbon refrigerant (R600a) on household refrigerator energy consumption. AIP Conference Proceedings. 2019;2062 [Google Scholar]
  • 15.Zhaohu L., Hanying J., Xinwen C., Kun L. Comparative study on energy efficiency of low GWP refrigerants in domestic refrigerators with capacity modulation. Energy Build. 2019;192:93–100. [Google Scholar]
  • 16.Shono Y., Nara F., Okido T., Sakamoto K. Investigation into low viscosity refrigeration oil for refrigerators. Refrigeration Science and Technology. 2019;1014:1329–1334. [Google Scholar]
  • 17.Alawi O.A., Sidik N.A.C., Kherbeet A.S. Nanorefrigerant effects in heat transfer performance and energy consumption reduction: a review. Int. Commun. Heat Mass Tran. 2015;69:76–83. [Google Scholar]
  • 18.Azmi W.H., Sharif M.Z., Yusof T.M., Mamat R., Redhwan A.A.M. Potential of nanorefrigerant and nanolubricant on energy saving in refrigeration system – a review. Renew. Sustain. Energy Rev. 2017;69:415–428. [Google Scholar]
  • 19.Malvandi S., Heysiattalab S., Ganji D.D. Thermophoresis and Brownian motion effects on heat transfer enhancement at film boiling of nanofluids over a vertical cylinder. J. Mol. Liq. 2016;216:503–509. 2016. [Google Scholar]
  • 20.Ohunakin O.S., Adelekan D.S., Gill J., Atayero A.A., Atiba O.E., Okokpujie I.P., Abam F.I. Performance of a hydrocarbon driven domestic refrigerator based on varying concentration of SiO2 nano-lubricant. Int. J. Refrig. 2018;94:59–70. [Google Scholar]
  • 21.Gill J., Singh J., Ohunakin O.S., Adelekan D.S. Energetic and exergetic analysis of a domestic refrigerator system with LPG as a replacement for R134a refrigerant , using POE lubricant and mineral oil based TiO2 - , SiO2 - and Al2O3 -lubricants. Int. J. Refrig. 2018;91:122–135. [Google Scholar]
  • 22.Alawi O.A., Sidik N.A.C., Kherbeet A.S. The effects of nanolubricants on boiling and two phase flow phenomena: a review. Int. Commun. Heat Mass Tran. 2016;75:197–205. [Google Scholar]
  • 23.Xing M., Wang R., Yu J. Application of fullerene C60 nano-oil for performance enhancement of domestic refrigerator compressors. Int. J. Refrig. 2014;40:398–403. [Google Scholar]
  • 24.Okotie T.E., Adelekan D.S., Ohunakin O.S., Gill J., Atayero A.A. Performance evaluation of hydrocarbon based nanorefrigerants subjected to periodic door openings. J. Phys. Conf. 2019;1378(4) [Google Scholar]
  • 25.Gill J., Singh J., Ohunakin O.S., Adelekan D.S. Energy analysis of a domestic refrigerator system with ANN using LPG/TiO2–lubricant as replacement for R134a. J. Therm. Anal. Calorim. 2019;135:475–488. [Google Scholar]
  • 26.Adelekan D.S., Ohunakin O.S., Gill J., Okokpujie I.P., Atiba O.E. Performance of an iso-butane driven domestic refrigerator infused with various concentrations of graphene based nanolubricants. Procedia Manufacturing. 2019;35:1146–1151. [Google Scholar]
  • 27.Ajuka L.O., Odunfa M.K., Ohunakin O.S., Oyewola M.O. Energy and exergy analysis of vapour compression refrigeration system using selected eco-friendly hydrocarbon refrigerants enhanced with tio2-nanoparticle. Int. J. Eng. Technol. 2017;6(4):91–97. [Google Scholar]
  • 28.J, Lou H., Zhang R Wang. Performance evaluation of graphite nanolubricant in domestic refrigerator employing R600a refrigerant. Huagong Xuebao/CIESC Journal. 2014;65(2):516–521. [Google Scholar]
  • 29.Gill J., Ohunakin O.S., Adelekan D.S., Atiba O.E., Ajulibe D., Singh J., Atayero A.A. Performance of a domestic refrigerator using selected hydrocarbon working fluids and TiO2–MO nanolubricant. Appl. Therm. Eng. 2019;160:114004. [Google Scholar]
  • 30.Schultz R., Cole R. AICHE Symposium Series; 1979. Uncertainty Analysis in Boiling Nucleation. [Google Scholar]
  • 31.Ohunakin O.S., Adelekan D.S., Babarinde T.O., Leramo R.O., Abam F.I., Diarra C.D. Experimental investigation of TiO2-, SiO2-and Al2O3-lubricants for a domestic refrigerator system using LPG as working fluid. Appl. Therm. Eng. 2017;127:1469–1477. [Google Scholar]
  • 32.Harrington L., Aye L., Fuller B. Impact of room temperature on energy consumption of household refrigerators: lessons from analysis of field and laboratory data. Appl. Energy. 2018;211:346–357. [Google Scholar]
  • 33.Jia Tao, Wang Ruixiang, Xu Rongji. Performance of MoFe2O4-NiFe2O4/Fullerene-added nano-oil applied in the domestic refrigerator compressors. Int. J. Refrig. 2014;45:120–127. [Google Scholar]