Table 2.
Design conditions of the full-outer-air-intake natural air-conditioning system for negative pressure isolation wards.
| Item | Name | Data |
|---|---|---|
| 1 | Ward bulk (m3) | 33.97 |
| 2 | Indoor temp. (°C) | 23∼25 |
| 3 | RH (%) | 50∼60 |
| 4 | CO2 concentration (ppm) | 600 |
| 5 | Negative pressure (Pa) | 8∼12 |
| 6 | Air exchange per hour | 12 |