. 2021 Apr 13;18(8):4085. doi: 10.3390/ijerph18084085

Table 1.

Hourly average indoor and outdoor PM2.5 concentrations and infiltration efficiencies (Finf) calculated with portable HEPA filter air cleaners operating and not operating in the library’s media room.

Date Range (s) Median Outdoor Conc., µg/m3
(25%–75%) 1
Indoor Location Median Indoor Conc., µg/m3
(25%–75%) 1
Infiltration Efficiency N 1
8/24/19 to 10/16/19 23.3 (12.0–49.1) Inside library 15.0 (9.8–21.2) 0.45 140
Media room (HEPA operating) 5.7 (5.5–8.5) 0.17
8/20/19 to 8/22/19 &
10/18/19 to 11/26/19
30.7 (12.2–85.9) Inside library 19.6 (9.8–36.2) 0.31 609
Media room (HEPA not operating) 20.0 (10.5–39.0) 0.32

1 Number of hours included. Used only hours with paired indoor-outdoor data.