Table 1.
Room No. | Volume, ft3 | SAF, ft3/min | EAF, ft3/min | ACHS | ACHE | ACHVENT | Floor |
---|---|---|---|---|---|---|---|
002 | 815 | 82 | 27 | 6.0 | 2.0 | 6.0 | 0 |
003 | 787 | 69 | 27 | 5.3 | 2.1 | 5.3 | 0 |
008 | 1,221 | 149 | 103 | 7.3 | 5.1 | 7.3 | 2 |
012 | 1,015 | 152 | 64 | 9.0 | 3.8 | 9.0 | 2 |
019 | 686 | 59 | 400 | 5.2 | 35.0 | 35.0 | 1 |
021 | 861 | 75 | 51 | 5.3 | 3.6 | 5.3 | 1 |
022 | 833 | 55 | 46 | 3.9 | 3.3 | 3.9 | 1 |
031 | 962 | 337 | 210 | 21.0 | 13.1 | 21.0 | 2 |
032 | 667 | 289 | 220 | 26.0 | 19.8 | 26.0 | 2 |
033 | 970 | 211 | 220 | 13.1 | 13.6 | 13.6 | 2 |
Mean | 882 | 148 | 137 | 10.2 | 10.1 | 13.2 | N/A |
SD | 166 | 101 | 122 | 7.6 | 10.6 | 10.6 | N/A |
ACHE, air change per hour based on exhaust airflow rate; ACHS, air change per hour based on supply airflow rate; ACHVENT, air change per hour based on mechanical ventilation; EAF, exhaust airflow rate in cubic feet per minute; N/A, not applicable; SAF, supply airflow rate in cubic feet per minute.