TABLE I.

Implementation of painting facility parameters in CFD simulations

Bay Velocity m/s (fpm) Interior Surface Boundary Type Velocity m/s Contaminant mass fraction Turbulence intensity Turbulence length-scale Turbulence Model
0.549 (108) SUPPLY FILTER VELOCITY INLET 0.6338 zero 10% 1 m Standard k- ε
EXHAUST FILTER VELOCITY INLET −1.465 Not specified Not specified Not specified
SPRAYER HAND VELOCITY INLET 1.71 0.5 10% 0.1 m
0.440 (86.6) SUPPLY FILTER VELOCITY INLET 0.4754 zero 10% 1 m Standard k- ε
EXHAUST FILTER VELOCITY INLET −1.174 Not specified Not specified Not specified
SPRAYER HAND VELOCITY INLET 1.71 0.5 10% 0.1 (m)
0.330 (65.0) SUPPLY FILTER VELOCITY INLET 0.381 zero 10% 1 m Standard k- ε
EXHAUST FILTER VELOCITY INLET −0.8816 Not specified Not specified Not specified
SPRAYER HAND VELOCITY INLET 1.71 0.5 10% 0.1 m
0.220 (43.3) SUPPLY FILTER VELOCITY INLET 0.2540 10% 1 m Standard k- ε
EXHAUST FILTER VELOCITY INLET −0.5877 Not specified Not specified Not specified
SPRAYER HAND VELOCITY INLET 1.71 0.5 10% 0.1 (m)
0.549/0.330 (108/65.0) SUPPLY FILTER VELOCITY INLET 0.6338 zero 10% 1 m Standard k- ε
EXHAUST FILTER VELOCITY INLET −0.8816 Not specified Not specified Not specified
SPRAYER HAND VELOCITY INLET 1.71 0.5 10% 0.1 (m)
0.508 (100) SUPPLY FILTER VELOCITY INLET 0.5865 zero 10% 1 m RNG k-ε
EXHAUST FILTER VELOCITY INLET −1.3563 Not specified Not specified Not specified
SPRAYER HAND VELOCITY INLET 1.71 0.5 10% 0.1 m
0.381 (75) SUPPLY FILTER VELOCITY INLET 0.4399 zero 10% 1 m RNG k- ε
EXHAUST FILTER VELOCITY INLET −1.017 Not specified Not specified Not specified
SPRAYER HAND VELOCITY INLET 1.71 0.5 10% 0.1 m
0.254 (50) SUPPLY FILTER VELOCITY INLET 0.2933 zero 10% 1 m RNG k- ε
EXHAUST FILTER VELOCITY INLET −0.6782 Not specified Not specified Not specified
SPRAYER HAND VELOCITY INLET 1.71 0.5 10% 0.1 m

Notes: The grid of 9,476,802 cells was adapted to a fine grid of 16,241,731 cells (a 42% increase) to test grid independence. Spray nozzle velocity was taken from the manufacturer’s specification of 11 cfm: V = Q/A = 11 cfm/0.00304 m2. Aircraft surfaces and hangar wall, floor, and ceiling were modeled as no-slip walls, except that for the unbalanced flow condition, the ceiling was modeled as a zero-gauge pressure boundary.