Skip to main content
. 2021 May 23;21(11):3623. doi: 10.3390/s21113623

Table 1.

Some real data from power supply companies in some provinces of China diagnosing power transformer fault types by DGA method.

Fault Type Dissolved Gas (µL/L) Sources
CH4 C2H2 C2H4 C2H6 TH
LT (<150 ℃) 83 53 13 1.2 150.2 Jiujiang PSC
LT (150–300 ℃) 6.5 98 16 1.5 122 Fuzhou PSC
LT (150–300 ℃) 193 191 28 16 428 Yingtan PSC
LT (150–300 ℃) 12 46 11 1.8 70.8 Nanchang PSC
LT (150–300 ℃) 3.5 31 8.2 1 43.7 Yichun PSC
AD 61 307 105 6 479 Yingtan PSC