Clinical and environmental L. pneumophila serogroup 6 isolates from the hospital under survey, by time of isolation and origin

Strain no. Date (mo/yr) Source of isolate Location (block/ward) Heating tank pressurea Legionella count (cfu/liter)
1 April/1989 Patient 1 C/cardiology, medicine
2 April/1989 Sink tap water C/cardiology MP 3 × 103
3 April/1989 Sink tap water C/medicine MP  NDb
4 April/1989 Bath tub water C/cardiology MP 1 × 103
5 July/1995 Shower water C/pediatric hematology HP ND
6 August/1995 Shower water C/pediatric hematology HP 8 × 102
7 July/1995 Patient 2 C/pediatric hematology, room 5
8 July/1995 Patient 2 C/pediatric hematology
9 July/1995 Patient 2 C/pediatric hematology
10 January/1996 Sink tap water C/pediatric hematology, room 5 HP 1 × 102
11 January/1996 Sink tap water C/pediatric hematology, room 1 HP 5 × 102
12 January/1996 Sink tap water C/pneumology MP 2 × 102
13 January/1996 Sink tap water B/hematology HP 1 × 103
14 January/1996 Heating tank B MP >1 × 104
15 January/1996 Heating tank B LP 7 × 102
16 January/1996 Heating tank A HP 4 × 103
17 January/1996 Heating tank A MP 1 × 104
18 January/1996 Sink tap water A/radiology LP 3 × 103
19 January/1996 Sink tap water D/ICU LP 2 × 102
a

HP, high pressure; MP, medium pressure; LP, low pressure. 

b

ND, not determined.