Table 2.
Comparison of signal filtering methods in the saturation mode of current transformers when determining the angle and the effective value of signals according to M2.
| Method and Reference |
Computational Experiment 1 |
Computational Experiment 22 |
Computational Experiment 3 |
Computational Experiment 4 |
||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| , % | , ° | , % | , ° | , % | , ° | , % | , ° | |||||||||
| Max | Avg. | Max | Avg. | Max | Avg. | Max | Avg. | Max | Avg. | Max | Avg. | Max | Avg. | Max | Avg. | |
| A1 [11,12] | 3.7 | 2.5 | 0.7 | 0.2 | 45 | 43 | 12 | 6.6 | 4.3 | 1.7 | 3 | 1.7 | 43 | 42 | 14 | 8 |
| A2 [15,16,17] | 1 | 0.4 | 0.7 | 0.3 | 0.7 | 0.3 | 0.4 | 0.16 | 27 | 15 | 19 | 11 | 48 | 26 | 27 | 15 |
| A3 [18] | 37 | 26 | 30 | 24 | 37 | 25 | 30 | 24 | 84 | 78 | 109 | 93 | 84 | 78 | 110 | 93 |
| A4 [19,20,21,22,23,24,25] | 2 | 0.4 | 3.5 | 2 | 1 | 0.2 | 1 | 0.7 | 2 | 1 | 1.6 | 1.3 | 2 | 0.8 | 1.5 | 1.2 |
| A5 [28,29,30] | 7.6 | 5.6 | 2 | 1 | 9 | 7 | 2 | 1 | 6.5 | 5 | 1.3 | 0.4 | 10 | 7 | 8 | 2 |