Performances of all kinds of fire FEAs to extinguish class B fire.

Type of FEA Fire extinguishing time (s) Mean time to extinguish (s) Consumption of fire FEA (g) Average FEA consumption (g) Fire situation
Pure water dry water FEA 2.94, 3.12 3.02 132.23, 135.78 134.01 Out, out
PVA dry water FEA 2.88, 2.96 2.92 129.58, 134.42 132.00 Out, out
Ammonium dihydrogen phosphate dry water FEA 2.62, 2.68 2.65 108.74, 115.63 112.19 Out, out
Sodium chloride dry water FEA 2.84, 2.72 2.78 121.58, 127.93 124.76 Out, out
Dry powder dry water FEA 2.44, 2.51 2.48 117.52, 121.69 119.61 Out, out