Table 1. Characteristics of included studies.
Reference | Author | year | Microbiological count type | Hospital locations tested | Ventilation method | ACH | Filter type | Type of ventilation system |
---|---|---|---|---|---|---|---|---|
[36] | Fu Shaw et al. | 2018 | BC | restricted areas | enhanced HVAC system | 40 air changes of filtered air per hour | HEPA | LAF |
[33] | Hansen et al. | 2005 | BC | restricted areas | conventional HVAC system | unclear | F7 or F9 | without LAF |
BC | restricted areas | without HVAC system | NA | NA | NA | |||
BC | restricted areas | enhanced HVAC system | unclear | HEPA | LAF | |||
[28] | Kedjarune et al. | 2000 | BC | inpatient facilities | conventional HVAC system | unclear | unclear | unclear |
[37] | Khawcharoenporn et al. | 2013 | FC | inpatient facilities | natural ventilation | NA | NA | NA |
FC | inpatient facilities | natural ventilation | NA | NA | NA | |||
FC | inpatient facilities | conventional HVAC system | unclear | unclear | unclear | |||
FC | inpatient facilities | conventional HVAC system | unclear | unclear | unclear | |||
[38] | Wan et al. | 2011 | BC | restricted areas | enhanced HVAC system | 15–23 air changes per hour | HEPA | LAF |
[39] | Stocks et al. | 2010 | BC | restricted areas | enhanced HVAC system | a minimum of 15 exchanges per hour | Varicell filter (95% effective at removing particles ≥0.3μm) | TAF |
[40] | Sautour et al. | 2009 | FC | inpatient facilities | conventional HVAC system | unclear | Plasmair™ | unclear |
[31] | Napoli et al. | 2012 | BC | restricted areas | enhanced HVAC system | unclear | HEPA | TAF |
[41] | Perdelli, Sartini et al. | 2006 | FC | inpatient facilities | without HVAC system | NA | NA | NA |
BC | inpatient facilities | without HVAC system | NA | NA | NA | |||
FC | inpatient facilities | conventional HVAC system | 6 exchanges per hour | minimum efficiency reporting value (80% to 85% efficiency) | TAF | |||
BC | inpatient facilities | conventional HVAC system | 6 exchanges per hour | minimum efficiency reporting value (80% to 85% efficiency) | TAF | |||
FC | inpatient facilities | enhanced HVAC system | 6 exchanges per hour | HEPA | TAF | |||
BC | inpatient facilities | enhanced HVAC system | 6 exchanges per hour | HEPA | TAF | |||
[42] | Pasquarella et al. | 2012 | BC | restricted areas | enhanced HVAC system | 15 air changes per hour | HEPA | unclear |
FC | restricted areas | enhanced HVAC system | 15 air changes per hour | HEPA | unclear | |||
[43] | Ortiz et al. | 2009 | FC | restricted areas | enhanced HVAC system | unclear | HEPA | unclear |
[44] | Napoli et al. | 2012 | BC | restricted areas | enhanced HVAC system | 19.3 air changes per hour | HEPA | TAF |
[45] | Landrin et al. | 2005 | BC | restricted areas | enhanced HVAC system | 30 air changes per hour | HEPA | unclear |
[30] | Cristina et al. | 2012 | BC | restricted areas | enhanced HVAC system | 20 efficacious air exchanges were carried out per hour | HEPA | TAF |
[46] | Brun et al. | 2013 | FC | publicly accessible areas | conventional HVAC system | unclear | without HEPA | unclear |
FC | inpatient facilities | conventional HVAC system | unclear | without HEPA | unclear | |||
FC | inpatient facilities | enhanced HVAC system | unclear | HEPA | unclear | |||
[4] | Bozic et al. | 2019 | BC | inpatient facilities | without HVAC system | NA | NA | NA |
FC | inpatient facilities | without HVAC system | NA | NA | NA | |||
BC | inpatient facilities | conventional HVAC system | unclear | unclear | unclear | |||
FC | inpatient facilities | conventional HVAC system | unclear | unclear | unclear | |||
[32] | Albertini et al. | 2020 | BC | restricted areas | enhanced HVAC system | unclear | HEPA | MAF |
BC | restricted areas | enhanced HVAC system | unclear | HEPA | TAF | |||
FC | restricted areas | enhanced HVAC system | unclear | HEPA | MAF | |||
FC | restricted areas | enhanced HVAC system | unclear | HEPA | TAF | |||
[47] | Dougall et al. | 2019 | BC | restricted areas | enhanced HVAC system | unclear | HEPA | Unclear |
[48] | Sossai et al. | 2011 | BC | restricted areas | conventional HVAC system | 12.5 air changes per hour | unclear | TAF |
BC | restricted areas | enhanced HVAC system | 12.5 air changes per hour | HEPA | additional LAF screen | |||
[49] | Cristina et al. | 2016 | BC | restricted areas | enhanced HVAC system | 19 efficacious air exchanges per hour | HEPA | TAF |
[18] | Andersson et al. | 2014 | BC | restricted areas | conventional HVAC system | unclear | F9 | displacement ventilation |
BC | restricted areas | enhanced HVAC system | unclear | HEPA | LAF | |||
[50] | Perdelli, Cristina et al. | 2006 | FC | restricted areas | enhanced HVAC system | at least 15 air exchanges per hour | HEPA | unclear |
FC | inpatient facilities | conventional HVAC system | 6 air exchanges per hour | filters with 80%-85% efficiency | unclear | |||
FC | publicly accessible areas | conventional HVAC system | 2 air exchanges per hour | filters with 80%-85% efficiency | unclear | |||
[51] | Sixt et al. | 2007 | FC | inpatient facilities | enhanced HVAC system | unclear | HEPA | LAF |
FC | inpatient facilities | conventional HVAC system | unclear | PlasmairTM | without LAF | |||
FC | inpatient facilities | without HVAC system | NA | NA | NA | |||
[52] | Agodi et al. | 2015 | BC | restricted areas | enhanced HVAC system | 18 ± 4.5 air changes per hour | HEPA | LAF |
[52] | Agodi et al. | 2015 | BC | restricted areas | enhanced HVAC system | 18 ± 4.5 air changes per hour | HEPA | MAF |
BC | restricted areas | enhanced HVAC system | 18 ± 4.5 air changes per hour | HEPA | TAF | |||
[21] | Alsved et al. | 2018 | BC | restricted areas | enhanced HVAC system | unclear | HEPA | turbulent mixed air flow |
BC | restricted areas | enhanced HVAC system | unclear | HEPA | LAF | |||
BC | restricted areas | enhanced HVAC system | unclear | HEPA | temperature controlled air flow | |||
[53] | Cho et al. | 2018 | FC | inpatient facilities | conventional HVAC system | unclear | without HEPA | unclear |
FC | inpatient facilities | enhanced HVAC system | unclear | HEPA | unclear | |||
[54] | Curtis et al. | 2005 | FC | inpatient facilities | conventional HVAC system | 2.9 ± 2.7 air changes per hour | without HEPA | unclear |
FC | inpatient facilities | conventional HVAC system | 8.1 ± 7.9 air changes per hour | without HEPA | unclear | |||
FC | inpatient facilities | conventional HVAC system | 3.8 ± 4.0 air changes per hour | without HEPA | Unclear | |||
[54] | Curtis et al. | 2005 | FC | inpatient facilities | enhanced HVAC system | 26.6 ± 13.2 air changes per hour | HEPA | unclear |
[55] | Dehghani et al. | 2018 | FC | restricted areas | enhanced HVAC system | unclear | HEPA | LAF |
[56] | Kabir et al. | 2012 | BC | inpatient facilities | conventional HVAC system | unclear | unclear | unclear |
[57] | Falvey et al. | 2007 | FC | publicly accessible areas | conventional HVAC system | unclear | 65% filtering efficiency of fan | unclear |
FC | publicly accessible areas | conventional HVAC system | unclear | 65% filtering efficiency of fan | unclear | |||
FC | publicly accessible areas | conventional HVAC system | unclear | 90–95% filtering efficiency of fan | unclear | |||
FC | publicly accessible areas | conventional HVAC system | unclear | 90–95% filtering efficiency of fan | unclear | |||
FC | inpatient facilities | conventional HVAC system | 3 air exchanges per hour | 90–95% filtering efficiency of fan | unclear | |||
FC | inpatient facilities | conventional HVAC system | 3 air exchanges per hour | 90–95% filtering efficiency of fan | unclear | |||
FC | inpatient facilities | conventional HVAC system | 6 air exchanges per hour | 90–95% filtering efficiency of fan | unclear | |||
FC | inpatient facilities | conventional HVAC system | 6 air exchanges per hour | 90–95% filtering efficiency of fan | unclear | |||
FC | inpatient facilities | enhanced HVAC system | 12 air exchanges per hour | HEPA | Unclear | |||
[57] | Falvey et al. | 2007 | FC | inpatient facilities | enhanced HVAC system | 12 air exchanges per hour | HEPA | Unclear |
[58] | Friberg et al. | 2001 | BC | restricted areas | enhanced HVAC system | unclear | HEPA | LAF |
BC, bacterial count; FC, fungal count; NA, not applicable; HEPA, high efficiency particulate air; LAF, laminar air flow; TAF, turbulent air flow; MAF, mixed air flow.