Skip to main content
. 2022 Feb 24;10:1136. Originally published 2021 Nov 10. [Version 2] doi: 10.12688/f1000research.73067.2

Table 5. Magnetic field of the power transmission lines in Malaysia.

Type of power lines Conducting ground Phasing Magnetic flux densities (μT) Compliance to exposure limit?
Yes No Untransposed Transposed Under the line ROW boundary ICNIRP EU Slovenia/Italy
132 kV double circuit 4.794284 0.253069 Yes Yes Yes
0.545671 0.624946 Yes Yes Yes
2.6043 1.4302 Yes Yes Yes
1.3384 0.4673 Yes Yes Yes
275 kV double circuit 3.928109 0.960835 Yes Yes Yes
0.443016 1.074408 Yes Yes Yes
2.088845 1.494544 Yes Yes Yes
1.263348 0.636509 Yes Yes Yes
132/132 kV quadruple circuit 13.62006 2.978469 Yes Yes Yes
1.13004 0.340224 Yes Yes Yes
7.28901 4.670191 Yes Yes Yes
1.493262 0.676831 Yes Yes Yes
275/132 kV quadruple circuit 10.13539 2.489524 Yes Yes Yes
0.909531 0.18436 Yes Yes Yes
5.405135 3.546732 Yes Yes Yes
1.113876 0.588538 Yes Yes Yes
500 kV double circuit 18.43185 4.860459 Yes Yes Yes
2.857379 4.293753 Yes Yes Yes
9.693522 6.762919 Yes Yes Yes
4.852491 2.516856 Yes Yes Yes