Table 5. Magnetic field of the power transmission lines in Malaysia.
Type of power lines | Conducting ground | Phasing | Magnetic flux densities (μT) | Compliance to exposure limit? | |||||
---|---|---|---|---|---|---|---|---|---|
Yes | No | Untransposed | Transposed | Under the line | ROW boundary | ICNIRP | EU | Slovenia/Italy | |
132 kV double circuit | ✓ | ✓ | 4.794284 | 0.253069 | Yes | Yes | Yes | ||
✓ | ✓ | 0.545671 | 0.624946 | Yes | Yes | Yes | |||
✓ | ✓ | 2.6043 | 1.4302 | Yes | Yes | Yes | |||
✓ | ✓ | 1.3384 | 0.4673 | Yes | Yes | Yes | |||
275 kV double circuit | ✓ | ✓ | 3.928109 | 0.960835 | Yes | Yes | Yes | ||
✓ | ✓ | 0.443016 | 1.074408 | Yes | Yes | Yes | |||
✓ | ✓ | 2.088845 | 1.494544 | Yes | Yes | Yes | |||
✓ | ✓ | 1.263348 | 0.636509 | Yes | Yes | Yes | |||
132/132 kV quadruple circuit | ✓ | ✓ | 13.62006 | 2.978469 | Yes | Yes | Yes | ||
✓ | ✓ | 1.13004 | 0.340224 | Yes | Yes | Yes | |||
✓ | ✓ | 7.28901 | 4.670191 | Yes | Yes | Yes | |||
✓ | ✓ | 1.493262 | 0.676831 | Yes | Yes | Yes | |||
275/132 kV quadruple circuit | ✓ | ✓ | 10.13539 | 2.489524 | Yes | Yes | Yes | ||
✓ | ✓ | 0.909531 | 0.18436 | Yes | Yes | Yes | |||
✓ | ✓ | 5.405135 | 3.546732 | Yes | Yes | Yes | |||
✓ | ✓ | 1.113876 | 0.588538 | Yes | Yes | Yes | |||
500 kV double circuit | ✓ | ✓ | 18.43185 | 4.860459 | Yes | Yes | Yes | ||
✓ | ✓ | 2.857379 | 4.293753 | Yes | Yes | Yes | |||
✓ | ✓ | 9.693522 | 6.762919 | Yes | Yes | Yes | |||
✓ | ✓ | 4.852491 | 2.516856 | Yes | Yes | Yes |