TABLE 3.
Analysis of productivity properties of GVPC manufactured without O2 and autoclaved at 115°C, 15 min (conditions 3 vs conditions 1) using real samples from cooling towersa
Type of sample | Phaseb | CFU/L Legionella spp. |
|
---|---|---|---|
GVPC Condition 1 |
GVPC Condition 3 |
||
Water sample n°1 | Phase A | 0 | 0 |
Phase B | 100 | 50 | |
Phase C | 0 | 0 | |
Phase D | 50 | 0 | |
Water sample n°1 + Legionella inoculation | Phase A | 0 | 0 |
Phase B | 100 | 50 | |
Phase C | 0 | 0 | |
Phase D | 0 | 0 | |
Water sample n°2 | Phase A | 0 | 0 |
Phase B | 0 | 50 | |
Phase C | 0 | 0 | |
Phase D | 0 | 0 | |
Water sample n°2 + Legionella inoculation | Phase A | 0 | 50 |
Phase B | 200 | 300 | |
Phase C | 50 | 0 | |
Phase D | 50 | 0 |
Legionella colony count (CFU/L) of water samples from cooling waters.
Phase A, direct plating; Phase B, plating of concentrated water from filtration; Phase C, heat treatment (50°C, 30 min); Phase D, acid treatment (HCl-ClK buffer, pH 2.2. for 5 min). The colony reading was performed after 5 incubation days at 37°C.