Abstract
The influencing mechanism of droplet transmissions inside crowded and poorly ventilated buses on infection risks of respiratory diseases is still unclear. Based on experiments of one-infecting-seven COVID-19 outbreak with an index patient at bus rear, we conducted CFD simulations to investigate integrated effects of initial droplet diameters(tracer gas, 5 μm, 50 μm and 100 μm), natural air change rates per hour(ACH = 0.62, 2.27 and 5.66 h−1 related to bus speeds) and relative humidity(RH = 35% and 95%) on pathogen-laden droplet dispersion and infection risks. Outdoor pressure difference around bus surfaces introduces natural ventilation airflow entering from bus-rear skylight and leaving from the front one. When ACH = 0.62 h−1(idling state), the 30-min-exposure infection risk(TIR) of tracer gas is 15.3%(bus rear) - 11.1%(bus front), and decreases to 3.1%(bus rear)-1.3%(bus front) under ACH = 5.66 h−1(high bus speed).The TIR of large droplets(i.e., 100 μm/50 μm) is almost independent of ACH, with a peak value(∼3.1%) near the index patient, because over 99.5%/97.0% of droplets deposit locally due to gravity. Moreover, 5 μm droplets can disperse further with the increasing ventilation. However, TIR for 5 μm droplets at ACH = 5.66 h−1 stays relatively small for rear passengers(maximum 0.4%), and is even smaller in the bus middle and front(<0.1%). This study verifies that differing from general rooms, most 5 μm droplets deposit on the route through the long-and-narrow bus space with large-area surfaces(L∼11.4 m). Therefore, tracer gas can only simulate fine droplet with little deposition but cannot replace 5–100 μm droplet dispersion in coach buses.
Keywords: Computational fluid dynamics (CFD) simulation, Droplet dispersion, infection risk (IR), Natural air change rate (ACH), Aerosol inhalation transmission, COVID-19
Graphical abstract
Abbreviations
- ACH
Air change rates per hour [h−1]
- ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Conditioning Engineers
- C
Particle concentration [μg/m3]
- C2H6
Ethane
- Cc
Cunningham slip correction factor
- CCTV
Closed-circuit television
- Cd
Quantum concentration of droplets [quanta/m3]
- Ce
Particle concentration at exhaust [μg/m3]
- CFD
Computational fluid dynamics
- Cg
Tracer gas concentration [ppm]
- Cg,p
Tracer gas concentration at passenger's nose [ppm]
- Cg,q
Quantum concentration of tracer gas [quanta/m3]
- Cg,s
Tracer gas concentration at index patient [ppm]
- Ci,s
Vapor concentration at droplet surface [kg·mol·m−3]
- Ci,sr
Vapor concentration of bulk air [kg·mol·m−3]
- Cinfected
Number of infected cases
- COVID-19
Corona virus disease 2019
- Cs
Particle concentration at inlet [ppm] [μg/m3]
- Cv
Virus concentration
- D
Dilution ratio
- dp
Initial droplet diameter [μm]
- Fa,i
Additional forces [N]
- FB
Fractional bias
- fD
Stoke's drag modification function
- Fdrag,i
Drag force [N]
- Fg,i
Gravitational force [N]
- g
Gravitational acceleration [m/s2]
- H
Height [m]
- HVAC
Heating, Ventilation and Air Conditioning
- I
Number of infectors
- kc
Mass transfer coefficient [m/s]
- L
Length [m]
- N
Total released droplet number
- n
Number of droplets
- NMSE
Normalized mean square error
- Ni
Passenger inhaled droplet number
- NS
Passenger inhaled pathogen-laden droplet number
- p
Pulmonary ventilation rate [m3/s]
- P
Infection risk
- PLD
Pathogen-laden droplets
- ps
Pulmonary ventilation rate of index patient [m3/s]
- q
Quanta generation rate [quanta/s]
- Q
Ventilation rate [m3/s]
- Rep
Reynolds number
- RH
Ambient relative humidity
- RNG
Renormalization group
- SARS-CoV-2
Severe acute respiratory syndrome coronavirus 2
- Ssusceptible
Number of susceptible people
- t
Time [s]
- T
Temperature [K]
- t0
Exposure period [s]
- Te
Temperature at exhaust [K]
- TIF
30-min-exposure intake fraction
- TIR
30-min-exposure infection risk
- Ts
Temperature at inlet [K]
- U
Normalized velocity
- up,i
Droplet velocity (m/s)
- us
Supply air velocity [m/s]
- V
Velocity [m/s]
- VBus
Speed of bus [m/s]
- Vol
Volume [m3]
- W
Width [m]
- WHO
World Health Organization
- WIR
Whole-journal-exposure infection risk
- xp,i
Droplet displacement [m]
- Z
Poles height [m]
- μt
Turbulent viscosity [kg·m−1·s−1]
- ϵ
Normalized particle concentration
- θ
Normalized temperature
- λ
Molecular mean free path of air [m]
- ρ
Density of air [kg/m3]
- ρp
Density of droplets [kg/m3]
- τp
Aerosol characteristic response time [s]
1. Introduction
Respiratory infectious diseases, such as influenza, severe acute respiratory syndrome (SARS) and coronavirus disease 2019 (COVID-19), have threatened public health in the last two decades [1]. In particular, the recent COVID-19 pandemic is caused by severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2). By 27 January 2022, more than 352 million people had been diagnosed with COVID-19, of whom more than 3.5 million had died [2]. Most of the human-to-human infections may occur in various indoor environments via droplet transmissions.
Numerous studies have demonstrated that respiratory infections may occur through the transmission of virus-laden droplets or droplet nuclei [[3], [4], [5]]. Pathogen-laden droplets (PLD) exhaled from the infected people may be the medium of human-to-human infection, because the pathogens can survive in the air for a period of time. Taking the current prevalence of COVID-19 for instance, the half-life of SARS-CoV-2 virus in the air is reported to be on the order of magnitude of 1 h [6]. Recent studies have redefined that there are three main transmission routes of respiratory infection: surface touch transmission, drop spray transmission and aerosol inhalation transmission [7,8]. Among them, aerosol inhalation transmission happens when air-suspended PLD are inhaled by a susceptible person. Ventilation modes and hourly air change rates (ACH) have been verified as the key factors affecting aerosol inhalation transmission and indoor infection risks [[9], [10], [11]].
There have been numerous studies on indoor ventilation, droplet/tracer gas dispersion and exposure analysis in inter-unit residential buildings [[12], [13], [14], [15], [16]], general indoor environments with mixing or displacement ventilation [[17], [18], [19]], and specific indoor space, for instance, restaurants [10,20] and hospital wards [21,22]. Particularly, for the indoor environment of public transportation, most previous researches focused on airplane cabins [[23], [24], [25]] and high-speed trains [26,27].
Although the coach bus is one of the most popular transportation modes for inter-city and suburban transportation, investigations on their indoor environments and infection risk are limited so far [28,29]. Due to the unopenable windows, the crowded coach bus often obtains fresh air from the skylight suppliers which is related to the running conditions. When the HVAC (Heating, Ventilation and Air Conditioning) is on, there is only indoor circulation, resulting in an insufficiently ventilated indoor environment. Therefore, the coach bus is conducive to the transmission of respiratory infectious diseases, which is worthy of study.
Our previous researches [11] reported that there was a COVID-19 outbreak with 7 non-associated infected passengers on a coach bus with insufficient natural ventilation in January 2020 (winter) in Hunan Province, China. In this study, we first conducted field experiments, and then numerically simulated the tracer gas dispersion under the measured mean ventilation condition [11]. However, since the coach bus was driving in three states (high bus speed, low bus speed and idling), corresponding to different natural ventilation rates, a further detailed case study is required to investigate the influence of different natural ventilation rates on droplet dispersion and resulting infection risk. In addition, the initial diameter of exhaled droplets is in a large range (0.1–100 μm) [30,31]. Moreover, numerous studies [18,32,33] have indicated that the droplet evaporation correlated to initial droplet diameters and RH significantly influence their gravity force and deposition effects, which integrates with turbulent diffusion, drag force, Saffman's lift force, and so on. Such complicated processes should be considered for more comprehensive investigations on transmission mechanisms and assessments of human-to-human exposure and infection risk.
Many studies have confirmed that the transport behavior of droplets smaller than 5 μm is similar to that of tracer gas in a room [[34], [35], [36], [37]]. However, the indoor environment of the bus is different from that of ordinary rooms, because the bus is long and narrow with more obstacles and more complex indoor airflow. In addition, RH is considered to influence droplet dispersion in indoor environments [17,32,38]. Therefore, two questions need to be answered: does tracer gas still have a similar transmission with droplets smaller than 5 μm in the bus environment? does RH still obviously affect droplet dispersion in the buses? For the bus environments, the feasibility of adopting tracer gas to replace fine droplets and the effect of RH on droplet dispersion need further exploration.
In the present study, by performing computational fluid dynamics (CFD) simulations, we further investigate the integrated impacts of RH (35%, 95%), initial droplet diameters (tracer gas, 5 μm, 50 μm, 100 μm), natural ventilation rates (ACH = 0.62 h−1, 2.27 h−1, 5.66 h−1 respectively related to idling, low bus speed, and high bus speed), and body thermal plumes on the evaporation and dispersion of exhaled droplets in this enclosed coach bus. We also predict the difference of exposure/infection risk for various pathogen-laden expiratory droplets under different conditions.
2. Methodology
2.1. Full-scale experimental bus
Fig. 1 shows the detailed model descriptions of the target coach bus with a cabin size of 11.4 m × 2.5 m × 2 m (L × W × H), where occcured a COVID-19 epidemic during the 200-min long-route journey on January 22, 2020 [11]. It was a double-deck 47-seat bus with the passenger cabin on the upper deck and the driver zone on the lower deck. Only the radiator at the index-patient side was functional and turned on during the whole journey, the other side was broken. As shown in Fig. 1b, the cabin was fully occupied except Seat 8C (46 passengers in total). An index patient (in scarlet) at seat 12D returned home from Changsha city, Hunan province, China, eventually infecting seven of the passengers. These infected passengers (in pink) were respectively located at seats 1D, 5C, 6A, 6D, 9C, 9D and 13D. Among them, the passenger at seat 1D is farthest away from the index patient, at a distance of 9.46 m.
Fig. 1.
(a) Bus photos and 3D bus model, (b) Bus top view and size information, (c) Grid arrangements of model.
All the windows could not be opened with the skylights (as shown in Fig. 1a) for natural ventilation. Fresh air entered the bus through the skylight inlet at the rear ceiling, and contaminated air escaped from the skylight outlet at the front ceiling (Fig. 1a). The measured ACH could change with the various air pressure difference between the indoor and outdoor of the bus due to the various running speeds. More detailed information about the experimental setup can be found in our previous study [11].
2.2. Numerical modeling of bus ventilation and droplet dispersion
2.2.1. Descriptions of bus model and case studies
We utilized Gambit to build the bus cabin and manikin models (Fig. 1). We created a refined grid with 0.005 m size on mouth and nose, which is smaller than the grid of 0.03 m size around the human body, 0.01 m mesh size on the skylight inlet/outlet and heat radiator, and 0.05 m for the bus body (Fig. 1c). A total number of 5,379,993 unstructured meshes were generated, which was verified to ensure grid-independent requirements.
Twenty-one cases were considered as shown in Table 1 . We investigated the influence of ACH (0.62, 2.27 and 5.66 h−1) related to bus speed (0, 30 and 80–90 km/h), initial droplet diameters (tracer gas, d p = 5, 50 and 100 μm), and ambient relative humidity (RH = 35%, 95%) on the transmission of the index patient's exhaled droplets and the exposure/infection risk of other passengers. Ethane (C2H6) was adopted as the tracer gas to explore the dispersion difference between droplets and tracer gas in the coach bus.
Table 1.
Parameters and setups in all 21 test cases.
| Experimental variables | Setup | Notes |
|---|---|---|
| Ventilation rate (ACH/h−1) | 0.62 h−1 | Bus is at idling (VBus = 0 km/h). |
| 2.27 h−1 | Bus is running at low speed (VBus = 30 km/h). | |
| 5.66 h−1 | Bus is running at high speed (VBus = 80–90 km/h). | |
| Initial droplet diameter (dp/μm) | Tracer gas | As a surrogate for fine droplets and droplet nuclei. |
| 5 μm | For effect of initial diameter on droplet dispersion. | |
| 50 μm | ||
| 100 μm | ||
| Ambient relative humidity (RH/%) | 35% | For effect of RH on droplet dispersion. |
| 95% |
2.2.2. Numerical simulation of airflow model
The renormalization group (RNG) k-ϵ model [39] has been verified to effectively simulate indoor airflows and tracer gas dispersion with considerable accuracy and computing efficiency [[40], [41], [42]]. Thus, we adopted Ansys FLUENT with RNG k-ϵ model to solve the conservation equations for mass, momentum, energy, humidity and turbulence variables. All the governing equations were discretized by the finite volume method in the second-order upwind scheme. SIMPLE scheme was selected to couple the pressure and velocity. Boussinesq hypothesis was adopted to consider the influence of thermal buoyancy.
To simulate the airflow field, we assumed that the variables were unchanging (steady) in the bus. CFD simulations were run until residuals became constant, for all cases the iterations were over 100,000 times. Convergence was achieved after non-dimensional residuals for continuity equation, velocity components, energy, k and ε were below 10−3, 10−4, 10−6, 10−4 and 10−4, respectively and the monitored variables at specific surfaces were stable. We also checked energy balance and mass balance to help determine the convergence.
2.2.3. Droplet dispersion modeling
After the steady airflow field calculation was solved, we started the simulation of tracer gas dispersion and particle tracking, separately. The second-order upwind scheme was adopted in the tracer gas simulation. The mass fraction of C2H6 in the index patient's exhalation flows was 0.32 in CFD simulations according to Ou et al. [11]. Lagrangian method with the Discrete Phase Modeling (DPM) was adopted to simulate the droplet dispersion with initial diameters of 5 μm, 50 μm and 100 μm [28,43]. Lagrangian equations of the droplets for i direction are as follows:
| (1) |
| (2) |
| (3) |
| (4) |
where x p,i and u p,i are the droplet displacement (m) and velocity (m/s) in i direction, respectively; F drag,i is the drag force (Eq. (3)), F g,i is the gravitational force (Eq. (4)). In addition, F a,i is the additional forces (Eq. (2)) for which we only considered Brownian force and Saffman's lift force [28,44]. ρ p and ρ are the density of droplets and air, respectively. f D is the Stoke's drag modification function of Reynolds number for large aerosol (Re p) [45].
| (5) |
In Eq. (3), is the aerosol characteristic response time, which is defined as:
| (6) |
where is the turbulent viscosity (kg m−1 s−1) and is the droplet diameter. C c is the Cunningham slip correction factor, which is defined as [46]:
| (7) |
where is the molecular mean free path of air.
In CFD simulations, the mass ratio of liquid (water) and solid element (sodium chloride) in droplets is assumed as 9 [47]. The densities of water liquid and sodium chloride are respectively 998.2 kg/m3 and 2170 kg/m3. The evaporation process will continue until the droplets’ volatile composition (i.e., water) is completely consumed. The vaporization rate is governed by the gradient of the vapor concentrations between the droplet surface and the bulk gas. The molar flux of vapor is defined as:
| (8) |
where is the mass transfer coefficient (m/s) which can be obtained by Sherwood relationship [48]. The vapor concentrations at both droplet surface (kg·mol·m−3) and bulk air (kg·mol·m−3) are calculated by the assumption of the ideal gas.
2.2.4. Boundary conditions
Table 2 shows the relevant boundary condition settings in CFD simulations [11]. At the skylight inlet, the ambient air temperature was set as 11 °C, and the inlet velocity was set as 0.57, 2.09 and 5.37 m/s according to the measured ACH. At the skylight outlet, the air temperature was set as 24, 23, 21 °C according to the experiment. Non-slip wall with standard wall function was applied at all wall surfaces. The effects of human respiration and body surface heat fluxes were considered, with convective heat fluxes of 50 W for each sedentary passenger. To simplify the calculations, it was assumed that the droplets were exhaled from the mouth of the index patient, while the other passengers only inhaled through noses. A value of heat flux determined by the energy balance estimates was set on the bus window glasses [11].
Table 2.
Boundary condition setups in CFD simulation.
| Boundary name | Boundary condition |
|---|---|
| Skylight inlet | Velocity inlet, velocity is different with various running conditions (idling: 0.57 m/s, low bus speed: 2.09 m/s, high bus speed: 5.37 m/s), temperature is 11 °C, turbulent intensity is 5%. |
| Skylight outlet | Outflow, velocity is same as skylight inlet, temperature is different with various running conditions (idling: 24 °C, low bus speed: 23 °C, high bus speed: 21 °C), turbulent intensity is 5%. |
| Glass at wall surface | No slip wall, heat flux is determined by energy balance estimates (idling: 92.89 W/m2, low bus speed: 79.00 W/m2, high bus speed: 56.63 W/m2). |
| Index-patient side radiator | Standard wall function, no slip wall, heat flux is 100 W/m2, surface area is 3.38 m2. |
| Opposite side radiator (closed) | Standard wall function, no slip wall, heat flux is 0 W/m2, surface area is 3.38 m2. |
| Wall of bus, luggage rack, seat | Standard wall function, no slip wall, heat flux is 0 W/m2. |
| Nose (except index patient) | Mass-flow-outlet, mass flow rate is 9.23 × 10−5 kg/s, Nostril area is 2.87 × 10−4 m2. |
| Mouth of index patient | Velocity inlet, exhaled airflow velocity is 1.5 m/s (in a direction paralleling to Y-axis), temperature is 32 °C. |
| Other body surface | Standard wall function, no slip wall, convective heat is 50 W for each person. |
After the steady airflow field with water vapor was solved, the single-diameter droplets were uniformly released from the mouth of the index patient at a rate of 20 droplets per time step (t = 0.1s, 18,000 iterations in total). The initial velocity of exhaled droplets was 1.5 m/s and the initial temperature was 32 °C. After 30 min continuous releasing, we got a fully-developed droplet distribution with a total droplet number of 360, 000. When a droplet encountered a surface, it would have three different fates: trap, reflect and escape. As shown in Table 3 , different droplet sizes, surface roughness and other factors would lead to different boundary conditions of droplets on the surfaces [28,49]. The trap condition was utilized for the floor, human surfaces and seats, which means droplets were trapped once they touched the objects and the trajectory calculations were terminated. While for the glass, roof, luggage racks and vertical walls, the reflect condition was applied due to smooth surfaces or gravity, which means droplets rebound off the surface and continue dispersion [28,44,50]. Escape condition was adopted to the skylight outlet and passengers’ noses (except the index patient). Some of the CFD simulations in this study were completed on the Tianhe II supercomputer with the support of the National Supercomputer Center in Guangzhou.
Table 3.
Boundary conditions of each boundary in Discrete Phase Model.
| Boundary name | Boundary conditions |
|---|---|
| Skylight, nose of passenger (except index patient) | Escape (trajectory calculations terminated) |
| Glass at wall surface, roof, luggage rack, vertical wall | Reflect (droplets suspended in air) |
| Floor, air conditioning, radiator, human body surface, seat | Trap (trajectory calculations terminated) |
2.3. Calculation of infection risk
We adopted the Wells-Riley equation to calculate each passenger's infection risk of aerosol inhalation transmission, which represented the probability of infection through inhaling PLD. This method has been verified to effectively predict the infection risk [[51], [52], [53]]. The Wells-Riley equation is defined as follows [54]:
| (9) |
where P is the probability of infection risk; C infected is the number of infected cases; S susceptible is the number of susceptible people; I is the number of people in the infectious stage or infectors; q is the quanta of PLD produced per infector per second (quanta/s); p is the pulmonary ventilation rate of each susceptible (m3/s); Q is the room ventilation rate with virus-free air (m3/s); t is the exposure time (s); is the number of PLD inhaled by susceptible person, which was calculated for droplets and tracer gas by using different equations.
For droplets, is defined as [54]:
| (10) |
where C v is the concentration of the virus in the exhaled droplets; C d (t) is the quanta concentration in an indoor environment at the time t (quanta/m3); t 0 is the exposure period; N i is the total number of droplets (exhaled from the index patient) inhaled by passengers.
For tracer gas, is defined as Eq. (11) according to the dilution-based evaluation method [55]:
| (11) |
where C g,q is the airborne quanta concentration at the target position (quanta/m3), and defined as , where p s is the breathing rate of the infector (m3/s); C g,s and C g,p are the airborne contaminant concentrations (ppm) at the source and target position, respectively.
Despite a critical parameter for calculating the infection risk, the value of q from a COVID-19 infector is currently not officially established. In this realistic bus outbreak, there were one infector (I = 1) and 45 susceptible passengers (S susceptible = 45), seven of whom were infected (C infected = 7). According to the travel history, this bus drove for 145 min at high speed (Q = 5.69 m3/min, t = 145 min), 45 min at low speed (Q = 2.28 m3/min, t = 45 min) and 10 min at idling (Q = 0.62 m3/min, t = 10 min). Substituting these data into Eq. (9) could back-calculate the value of q as 0.61 min−1 (36.6 h−1). This value agrees well with the range of 14–48 h−1 obtained by Dai and Zhao [56] who adopted a reproductive number-based fitting approach.
Ansys FLUENT was employed to simulate the number of droplets inhaled by each passenger (N i) and the concentration of tracer gas (C g,s and C g,p). Then the for droplets and tracer gas were respectively obtained by Eq. (10) and Eq. (11). Finally, the infection risk of each passenger was calculated by Eq. (9) for both droplets and tracer gas. In order to compare the infection risk under various ventilation rates, we carried out a 30-min simulation for each vehicle driving situation.
2.4. Validation of numerical modeling
Firstly, we performed a set of dispersion tests for validating the CFD predictions of tracer gas dispersion. The evaluation of tracer gas dispersion by this field experimental data can refer to our previous study [11].
In addition, we further carried out a validation study of indoor airflows, temperature and tracer gas/particle dispersion in a hospital ward evaluated by the experiment conducted by Yin et al. [36]. As shown in Fig. 2 a, the experiment was performed in a full-scale one-person patient ward (4.90 m × 4.32 m × 2.72 m). The ventilation rate from the displacement diffuser was 0.054 m3/s (4 ACH) and the temperature was 19.5 °C. The ventilation rates of bathroom exhaust and main exhaust were 0.017 m3/s and 0.037 m3/s, respectively. As shown in Fig. 2b, the air velocity and temperature were measured at seven heights of Poles 1–8. Particle concentration was measured at poles TG1 - TG5 at six heights. More details about the experimental setups could be found in Yin et al. [36].
Fig. 2.
Model setups of single-bed isolation room in CFD validation case (Yin et al. [36]).
In this validation, we adopted 1.8 million and 3.8 million tetrahedral grid cells with fine and coarse grid resolutions, respectively. Then, we selected the measured vertical profiles of normalized velocity (V/u s, u s = 0.14 m/s means the supply air velocity) and temperature (θ = (T-T s)/(T e-T s)) at Pole 2 and Pole 4 to validate CFD results, where T s and T e are the temperatures respectively at diffuser and main exhaust at the normalized height (Z/H, H = 2.72 m is the height of the inpatient ward).
Fig. 3a and b illustrate that CFD results of velocity and temperature agree well with the experimental data. Compared with the coarse grid resolution, fine grid resolution performs better, especially in the velocity at height of Z/H = 0.8. Fig. 3c–f displays the experimental data and CFD simulation results of normalized particle concentration ϵ at TG1, TG3, TG4 and TG5 (ϵ = (C–C s)/(C e–C s), where C, C s and C e are the particle concentrations at the measuring location, ventilation supply inlet and ventilation exhausts, respectively). Particles with a diameter of 1 μm are released from the patient's mouth. In order to quantify the reliability of the validation, we calculated the normalized mean square error (NMSE) and fractional bias (FB), whose ranges were respectively 0.3 to 1.3 and 0.01 to 0.27, which satisfied the recommended criteria ((NMSE≤1.5, 0.3 ≤ FB ≤ 0.3) in Yang et al. [57]. The results indicate that CFD simulation results can reasonably predict the dispersion tendency of indoor particles.
Fig. 3.
Vertical profiles of experiment and CFD simulation at Pole 2 and Pole 4 (a) Normalized temperature, (b) Normalized velocity; (c) Normalized 1 μm particle concentration at TG 1, TG 3, TG 4 and TG 5.
3. Results
3.1. Flow pattern and tracer gas dispersion under various ACH
Our previous study [11] only considered the tracer gas dispersion under the measured mean ventilation condition. In the present study, we emphasize the flow pattern and tracer gas dispersion under different ventilation conditions (i.e., ACH = 0.62, 2.27 and 5.66 h−1).
In order to describe the flow pattern and tracer gas dispersion more clearly, seat locations are shown in Fig. 4 a: 13 rows (Row 1–13) and 5 columns (Column A, B, C, D, E) of seats in the passenger cabin. We regard the 1st to 4th rows as the bus front, the 5th and 8th rows as the bus middle and the 9th to 13th rows as the bus rear. The index patient is located at seat 12D (Row 12, Column D, scarlet).
Fig. 4.
(a) Cross-section line and general flow characteristics; (b) Body thermal plume of 12C at state of idling; (c) Flow field near index patient at state of high bus speed; Flow field in Plane: (d) Y = 1.35 m; (e) X = 1.25 m. 1–3: idling, low bus speed, high bus speed, respectively.
Fig. 4a indicates that when the bus speed is high (ACH = 5.66 h−1), the fresh air enters the skylight inlet at the rear roof, then mixes with the dirty air and moves from the rear to the front. Finally, the mixed air leaves through the outlet at the front roof of the bus. There are body thermal plumes which lead to significant upward airflow near and above human bodies (Fig. 4b). The upward airflow will intertwine with the main flow field and subsequently affect the droplet dispersion. Fig. 4c displays that the airflow exhaled by the index patient first moves forward, then rises up and finally deflects backward to the bus rear. As depicted in Fig. 4d, the body thermal plumes are most obvious under idling condition (ACH = 0.62 h−1). The ventilation flow from bus rear to bus front enhances significantly as ACH rises with the increasing bus speed (Fig. 4e).
Fig. 5 presents the tracer gas concentration distribution of the cross-section at the height of passengers' noses (Z = 1.16 m) under different ACH. Tracer gas concentration in the bus decreases obviously when ACH increases. High tracer gas concentration mainly appears in the bus rear (Rows 9–13), especially at the index patient's side (Columns C and D). Particularly when ACH = 0.62 h−1, the concentration near the index patient is about 7000 ppm, and 5000 ppm in the bus front and middle (Rows 1–8) (Fig. 5a). When ACH = 5.66 h−1, the concentration near the index patient is about 1200 ppm, while around 600 ppm in the bus front and middle. (Fig. 5c).
Fig. 5.
Tracer gas concentration at state of: (a) idling, (b) low bus speed; (c) high bus speed.
3.2. Impacts of RH, ACH and initial diameters on droplet dispersion
3.2.1. Impacts of RH on droplet evaporation and transmission
Fig. 6 displays the temporal variation of droplet diameters (droplet evaporation history) under different RH (35%, 95%) when initial diameter d p is 50 μm and 100 μm. When d p = 5 μm, droplets can evaporate into 1.83 μm nuclei within 0.1 s under both RH conditions, so we don't show its evaporation process here. The results confirm that 50 μm droplets can evaporate into 18.26 μm droplet nuclei in 1.3 s under RH = 35% and 2.1 s under RH = 95%. However, it takes 5 s for 100 μm droplets to evaporate into 36.50 μm nuclei under RH = 35% and longer time (>6 s) under RH = 95%. Although droplets take a longer time to evaporate in more humid environment, the overall impact of RH is not significant in this coach bus with complicated interactions of ventilation airflow and thermal body plumes (Fig. S1).
Fig. 6.
Temporal variation of droplet evaporation (dp = 50 μm, 100 μm; RH = 35%, 95%).
3.2.2. Impacts of ventilation rates on droplet dispersion
We have investigated the impacts of ventilation rates on the dispersion of droplets in different initial diameters (5 μm, 50 μm and 100 μm), and find that the dispersion mechanism is more affected by the gravity force and less influenced by the ventilation airflow for larger droplets. Thus, to better reveal the influence of ventilation rates, we only select 5 μm droplets to display their distribution under RH = 35% at t = 5s, 30 s, 60 s and 300 s with three ACH, as shown in Fig. 7 .
Fig. 7.
Distribution of 5 μm droplets with RH = 35% at state of: (a) idling, (b) high bus speed.
As verified in Fig. 7a1-b1, after being exhaled by the index patient, droplets first move forward due to the initial exhalation flow, then rise up following the upward flow near the index patient, and spread with the main airflow routes (Fig. 7a2-b2). Due to the variation in ventilation rates, the spatial distribution of droplets also differs significantly (Fig. 7a3-a4). When ACH = 5.66 h−1 with larger supply airflow blowing to the bus front, more droplets move forward and escape from the skylight outlet, leaving relatively fewer droplets in the bus rear (Fig. 7a4-b4). The results show that increasing the ventilation rate is beneficial to droplet dilution and excretion, and significantly reduces the droplet concentration near the index patient (i.e., seats 11D, 12C and 13D).
3.2.3. Impacts of droplet initial diameters on droplet dispersion
Fig. 8 indicates the evaporation and dispersion of droplets with different initial diameters when RH = 35% and ACH = 2.27 h−1. 5 μm droplets can evaporate rapidly into nuclei, so they are more significantly affected by the airflow field, and spread wider in the whole bus (Fig. 8a1-a3). Due to the combined action of airflow pattern and gravity force, 50 μm droplets mainly concentrate at the bus rear (Fig. 8b1-b3). With the dominance of gravity force, 100 μm droplets rapidly settle down from the exhalation jet after being exhaled from the index patient's mouth (Fig. 8c1-c3). Basically, the larger the initial diameter is, the quicker the droplets deposit, and hence the smaller range they propagate and the more they remain in the bus.
Fig. 8.
Droplets distribution in low bus speed with RH = 35%: (a) dp = 5 μm, (b) dp = 50 μm, (c) dp = 100 μm.
3.3. Intake fraction and infection risk of each passenger
Fig. 9 depicts the 30-min-exposure intake fraction (TIF) of each passenger which is defined as dividing the number of droplets a passenger inhaled by the total number of droplets released from the index patient (360,000). Fig. 10 depicts the 30-min-exposure infection risk (TIR) of each passenger which is calculated by Wells-Riley equation (Eq. (9)). The X-axes represent the row of each passenger, where 12D is the location of the index patient and 8C is unoccupied. Passengers without data indicate that they did not inhale PLD released by the index patient.
Fig. 9.
Intake fraction of each passenger in a duration of 30 min under RH = 35% at state of: (a) idling, (b) low bus speed, (c) high bus speed.
Fig. 10.
Infection risk of each passenger under RH = 35%: (a) dp = 5 μm, (b) dp = 50 μm, (c) tracer gas. (Note: infection risk within 30 min was calculated.)
For 5 μm droplets, the ventilation rates influence the TIF and the subsequent TIR, with a higher ventilation rate leading to more passengers at TIR. When ACH = 0.62 h−1, only few 5 μm droplets are inhaled by passengers in the bus front (Fig. 9a), leading to most front passengers at no droplet TIR (Fig. 10a). When ACH increases to 5.66 h−1, even more front passengers are at TIR, and both TIF and TIR of passengers decrease with the distance between the passenger and index patient (Fig. 9c). Although 5 μm droplets disperse more widely with the increasing ventilation, the TIR is quite low (<0.01%) for front passengers. Regardless of ventilation rate, more than 97% of 50 μm droplets deposit near the index patient due to gravity (Table S1), so only the middle and rear passengers are at TIR with the highest infection risk for passenger 12C (3.13% under ACH = 5.66 h−1) (Fig. 10b). While for 100 μm droplets, over 99.5% of them deposit locally due to gravity (Table S1), making nobody at TIF, so we don't display the infection risk.
For the tracer gas, a higher ventilation rate leading to lower TIR. The TIR is 11.10–15.29% under ACH = 0.62 h−1, and decreases to 1.27–3.09% when ACH = 5.66 h−1 (Fig. 10c). The TIR of tracer gas for each passenger is more uniform and distinctly higher under the same condition, compared with that of droplets.
3.4. Infection risk of each passenger in this epidemic outbreak
The total duration of the bus journey is 200 min, and the passenger seating arrangement and driving route are depicted in Fig. 11 a. We adopted the calculated 30-min simulation results to infer the quanta of virus-laden droplets or tracer gas inhaled by each passenger throughout the whole journey. Figs. 11b–d displays the whole-journal-exposure infection risk (WIR) of passengers (except the index patient at seat 12D). Note that the logarithmic coordinate system is employed in Fig. 11c–d.
Fig. 11.
(a) Seating arrangement, journeys, and distribution of index patient and infected passengers, (b) Tracer gas, (c) dp = 5 μm, RH = 35%, (d) dp = 50 μm, RH = 35%. (Note: infection risk is calculated based on this epidemic case.)
Under all conditions, the highest WIR of the tracer gas, 5 μm and 50 μm droplets occurs at seat 12C with 33.85%, 16.99% and 17.40%, and followed by seat 13D with 24.97%, 4.28% and 1.57%, respectively. It can be seen from Fig. 11 that the WIR of front-seat passengers significantly decreases with the increasing initial droplet diameter. However, passengers near the index patient (i.e., seats of 11D, 12C and 13D) are always at comparatively high WIR.
For the tracer gas (Fig. 11b), the WIR of front passengers is relatively even at ∼14.00%. For 5 μm droplets (Fig. 11c), the WIR is quite discrepant for passengers at different locations, and is less than 0.15% for the front passengers (Rows 1–4), while up to 16.99% for the passenger at 12C. For 50 μm droplets (Fig. 11d), no front passengers are at WIR.
4. Discussion
4.1. The unique airflow field characteristics of the coach bus
The strength of this study lies in the investigation of the combined effect of the indoor main airflow and human thermal plumes on the airflow field in this unique in-coach environment. The coach bus only has small roof-opening skylight suppliers to open up for fresh air, but no windows are openable. Fig. 12 depicts the external surface wind pressure coefficient around the running bus. It shows that the pressure on the rear half is higher than the front half of the bus, which leads the air enter the bus from the rear skylight and exit from the front, i.e., the indoor main airflow is moving from the rear to front. This unique rear-to-front airflow pattern makes the pathogen-laden expiratory droplets propagate the entire bus when the index patient is seated at the bus rear (12D) and hence results in large-scale transmission in this outbreak, as was also found in Mesgarpour et al. [58]. If the index patient was in the middle or front of the bus, the rear of the bus will be a low-risk area [59].
Fig. 12.
(a) Pressure coefficient distribution on bus surfaces, (b) External pressure coefficient distribution of bus.
Besides the main airflow, the body thermal plumes cannot be neglected in the crowded coach bus, as they can cause an upward airflow near each human body and hence influence the droplet dispersion in the respiratory region—the last few inches for aerosol transmission to effectuate [17,22,60]. Meanwhile, Yang et al. [61] found that strong main airflow could destroy the thermal plumes. The body thermal plumes are obvious under the small background velocity field and can inhibit droplets from entering the respiratory area. This certain protective effect makes droplet infection risk stay low under ACH = 0.62 h−1. However, the body thermal plumes will be disturbed with the enhancement of the main airflow, leading to an increase of the droplet infection risk under ACH = 2.27 h−1.
4.2. Impacts of RH and initial droplet diameter on droplet dispersion
Redrow et al. [38] demonstrated that 10 μm droplets could evaporate completely in 0.25 s at RH = 20% and 0.55 s at RH = 80%, and RH influenced 0.4–10 μm droplet transport in a simulated room where the mean air velocity was almost zero. Liu et al. [17] revealed that 100 μm droplets took more than 100 s to evaporate at RH = 95% and <2 s at RH = 35%, which made 100 μm droplet dispersion totally distinct under different RH in an empty room. However, our study achieved a completely different finding: RH rarely influences the droplet (5–100 μm) dispersion in the coach bus. The possible reason may lie in the complex indoor environment of the coach bus which is different from those in the above literature. In our study, we found that the interaction of the main airflow and body thermal plumes made the airflow much more complex, which significantly influenced the droplet/tracer gas dispersion. Moreover, Chen and Zhao [62] and Xie et al. [33] indicated that regardless of the RH, small droplets evaporated completely quickly, and big droplets deposited downward immediately before fully evaporating due to gravity dominance. Therefore, there was a tiny difference of droplet ultimate fates and infection risk between different RH (Table S1, Fig. S2), which agreed well with the study on coach bus conducted by Yang et al. [28].
The droplet diameter is the fundamental property that determines its transport characteristics. The transport behavior of a droplet depends on its interaction with the surrounding gas molecules, as well as the force acting on it [63]. When the droplet diameter increases, its dominant influencing mechanism changes into gravity force or drag force [64,65]. Zhu et al. [66] indicated that the droplets of 30 μm or smaller were mostly influenced by indoor airflow, but those of 50–200 μm were significantly affected by the gravity force. Our study found that small droplets (i.e., tracer gas and 5 μm droplets) can follow the airflow and spread throughout the cabin, while large droplets (i.e., 50 μm and 100 μm) deposited near the index patient due to the dominant gravity force. Namely, small droplets can travel farther than large droplets, leading to a larger range of inhalation transmission.
When the droplet is small enough, the behavior of the droplets and the surrounding gas requires the kinetic theory of gases. Therefore, tracer gas was adopted as a surrogate for droplets and droplet nuclei smaller than 5 μm in general room environments, which had been verified by existing studies [36,44,67]. However, unlike general rooms, buses are longer and narrower in shape (11.4 m long and 2.5 m wide in our study) with more obstacles (i.e., human bodies and seats), which provides much more surface for droplets to deposit. Our study verifies that most droplets deposit on the route through the long-and-narrow bus so that only a small fraction can spread to the bus front. Therefore, passengers in the bus front can expose to few droplets and lead to a quite low infection risk. However, tracer gas does not deposit and can disperse in the whole cabin, resulting in distinctly higher infection risk under the same condition. Hence, tracer gas cannot be utilized to mimic the dispersion processes of droplets which can be deposited on the surfaces. Meanwhile, Zhao et al. [68] indicated that the deposition of 0.7 μm particles was insignificant in an aircraft cabin. Lai and Nazaroff [69] reported that droplets in the range of 0.1–0.2 μm has the lowest deposition rate in indoor environments. Hence, we conclude that tracer gas can only be adopted to simulate the dispersion of fine droplets (e.g., 0.1–0.7 μm) with little deposition in coach buses.
4.3. Impacts of ventilation rates on droplet dispersion and infection risk
van Doremalen et al. [6] have found that the SARS-CoV-2 virus can remain infectious in aerosols for hours and up to days on surfaces, leading to probable transmission. Among the three main transmission routes, the aerosol inhalation route is predominant and can occur over a long distance when the ventilation is insufficient [64,70]. Therefore, this study aims to investigate the mechanism of factors affecting the aerosol inhalation transmission and infection risk in a crowded coach bus.
Enhancing the indoor ventilation rates can promote dilution and removal of pathogen-laden expiratory droplets or droplet nuclei, and hence reduce the infection risk [10,67,71]. Our study also confirms that the infection risk is closely related to ventilation rates. When the ventilation rate is small, droplets can only disperse in the bus rear and middle. Larger ventilation airflow drives droplets to disperse more widely in the bus, but the infection risk is relatively low in the bus front (lower than 0.1% when ACH = 5.66 h−1 for 5 μm droplets). While for tracer gas, the inhalation infection risk can be reduced by an order of magnitude as ACH increases from 0.62 h−1 to 5.66 h−1. Thus, for the large range of initial diameters of respiratory droplets, the infection risk decreases with the increasing ventilation rates.
The World Health Organization [72] has indicated that the long-range aerosol inhalation transmission of COVID-19 is opportunistic in specific settings, particularly in crowded and inadequately ventilated indoor environments. Li et al. [10] revealed the long-range aerosol inhalation transmission in an insufficient ventilation restaurant and the longest transmission distance is 4.6 m. In this outbreak, the coach bus was supplied at a time-average ventilation rate of 1.72 L/s per person [11] far lower than the ASHRAE Standard (2019) [73], leading to long-range aerosol inhalation transmission with a longest distance of 9.46 m between the index patient and the infected passenger (1D). Both simulation results and actual outbreak confirm the important role of ventilation on aerosol inhalation transmission and infection risk.
4.4. Infection risk in realistic bus outbreak
Another merit of this study lies in that we utilized the real outbreak data to back-calculate the infection risk of each passenger according to the bus speeds and the corresponding exposure time in this COVID-19 outbreak inside the coach bus. Based on the numerical calculation results, we explained the following three characteristics for the spatial distribution of infected passengers in this realistic epidemic: (1) more infected passengers in the middle and rear of the cabin (six in Row 5–13) than in the front (only one in Row 1–4); (2) more infected passengers on the index patient side (six in Column C-D) than on the opposite side (only one in Column A-B).
The trajectory of droplets is determined by the airflow pattern, gravity force, and the process of evaporation in terms of their diameter. 50 μm droplets can transmit a short distance and then gradually deposit due to the gravity force, so only part of them can be inhaled by passengers in the rear and middle, which leads to short-range aerosol inhalation transmission [7]. Meanwhile, smaller droplets (≤5 μm) can continue spreading to the bus front, leading to both short and long-range aerosol inhalation transmissions. Thus, the infection risk is higher near the index patient and decreases with distance, namely, more passengers in the middle and rear were infected than those in the front.
Higher infection risks for both tracer gas and droplets are found on the index patient's side (Column C and D). The reason may lie in the cold “gravity current” [74] falling to the cabin floor and spreading throughout the entire cabin, established by the skylight inlet above the aisle near the index patient. The cold “gravity current” then rose with the body thermal plume of each passenger and finally exhausted at the bus front skylight outlet. The blockage of the floor-level “gravity current” by the toilet in the lower deck of the cabin made contaminated air spread slightly more to the index patient side than to the opposite side, which brought about a higher infection risk on the index patient side.
It can be found that there are some deviations between the realistic location of the infected person and the calculated location of passengers at high infection risk. The reason may lie in the following aspects. Firstly, we have calculated the infection risk of aerosol inhalation transmission for droplets with some representative diameters (tracer gas, 5 μm, 50 μm, and 100 μm). However, the PLD is in the large range of diameters (0.1–100 μm) which may highly affect the infection risk. Thus, it needs further study on the infection risk distribution of droplets in large range of diameters. Secondly, there are many other factors that may affect passengers being infected, such as other transmission routes (e.g., direct-contact/indirect-contact transmission [75]), immunity of passengers, the activity status of passengers in the bus (wear a mask or not, speak or not, etc). However, our study quantified the impact of natural ventilation on the infection risk of tracer gas and droplets and provided a basis for the prevention and control of respiratory infectious diseases in coach buses.
4.5. Limitations and future research
There are several limitations of the present research that should be acknowledged. Different respiratory activities, including breathing, speaking, coughing, sneezing, etc, can affect the generation and dispersion of droplets [26,58,76]. We only considered the index patient's breathing activity, because the epidemiological survey suggests that the index patient did not cough or talk to anyone during the whole trip. In the future, we will further consider more respiratory activities and more influencing parameters (e.g., natural ventilation modes by opening windows, source location, ambient temperature, different total heat flux for occupant etc). Meanwhile, it deserves further investigation on how the droplet final fates change with various ventilation rates and initial diameters under the combined effect of ambient airflow, gravity and body thermal plumes. Due to the positive pressure at the bus rear and the negative pressure at the bus front, opening the windows at the bus rear is beneficial to increase the ventilation rates, but the specific method needs further evaluation. Additionally, during the epidemic of infectious disease, public vehicles are required to be less than half occupancy in order to reduce the infection risk, which has not only caused great economic losses to the transportation operation companies, but also caused inconvenience to people's travel. Therefore, it is worth further investigating the infection risk under different seat arrangements to give a more specific suggestion for arranging the occupancy in different coach buses.
5. Conclusions
Based on experiments of one-infecting-seven COVID-19 outbreak with an index patient at bus rear, this paper performed CFD simulations to explore the PLD dispersion and infection risk in a crowded coach bus, which is important but still scarce. The integrated effects of initial droplet diameters, natural air change rates per hour and relative humidity are considered.
Some meaningful conclusions can be stated:
-
(1)
In this bus epidemic, inadequate ventilation, crowded passengers and long exposure time (200 min) are the main reasons for the large number of infected passengers (i.e., seven) with a longest infected distance of 9.46 m.
-
(2)
The pressure difference between the bus rear and front makes the air enter the bus from the rear ceiling-level skylight (inlet), and leave through the bus front ceiling-level skylight (outlet), carrying droplets/tracer gas disperse from the rear to the front. Higher bus speed leads to more ventilation rates.
-
(3)
Tracer gas can only be adopted to simulate fine droplet (e.g., 0.1–0.7 μm) dispersion in coach buses. The gaseous inhalation transmission can occur in the entire cabin, and its infection risk is greatly reduced with the increasig ventilation rates. When ACH increases from 0.62 h−1 to 2.27 h−1 and 5.66 h−1, TIF of tracer gas for each passenger decreases from 11.10-15.29% to 3.20–13.08% and 1.27–3.09%.
-
(4)
Over 99.5%/97.0% of large droplets (i.e., 100 μm/50 μm) deposit locally due to gravity. Thus, the TIF of 100 μm/50 μm droplets is almost independent of ACH, with a peak TIF (∼3.1%) near the index patient. Because gravity is less significant for 5 μm droplets which can spread more widely with the ventilation airflow from bus rear to front and disperse even further with the increasing ventilation.
-
(5)
Unlike ordinary rooms, most droplets will deposit on objects when spread in the long-and-narrow bus, but tracer gas will not deposit. therefore, the infection risk of tracer gas is obviously higher than that of 5–100 μm droplets.
-
(6)
Relative humidity (RH = 35% and 95%) affects the droplet evaporation process, but insignificantly influences the dispersion and infection risk.
For coach buses and other indoor environments, fresh air should be sufficiently supplied for the occupants. When the occupancy rate of vehicles is high, it is recommended to open windows or ceiling-level skylight at the vehicle rear to attain more fresh air into the bus and better natural ventilation. Even for cold winter or hot summer, we should find a balance between energy consumption and human health, i.e., to ensure thermal comfort by air conditioners or heating devices meanwhile provide sufficient external fresh air by opening ceiling-level skylight or small-area windows to reduce the infection risk in the vehicle.
CRediT authorship contribution statement
Qiqi Luo: Writing – review & editing, Writing – original draft, Visualization, Software, Methodology, Formal analysis, Data curation, Conceptualization. Cuiyun Ou: Writing – review & editing, Supervision, Project administration, Methodology, Investigation, Funding acquisition, Conceptualization. Jian Hang: Writing – review & editing, Supervision, Resources, Project administration, Methodology, Funding acquisition. Zhiwen Luo: Writing – review & editing, Supervision, Funding acquisition. Hongyu Yang: Software, Formal analysis, Data curation. Xia Yang: Software, Methodology. Xuelin Zhang: Writing – review & editing. Yuguo Li: Writing – review & editing. Xiaodan Fan: Writing – review & editing.
Declaration of competing interest
The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.
Acknowledgements
This work was supported by Guangdong Major Project of Basic and Applied Basic Research (2020B0301030004), the National Natural Science Foundation of China (grant numbers 41875015, 42005069, 42175095 and 42175180); the Special Fund (International Cooperation) Project for Science and Technology Innovation Strategy of Guangdong Province (China, grant number 2019A050510021); Research and development projects in key areas of Guangdong Province (code 212020012620600004). The support from UK GCRF Rapid Response Grant on ‘Transmission of SARS-CoV-2 virus in crowded indoor environment’, the Opening Fund of State Key Laboratory of Green Building in Western China (No. LSKF202106), the Innovation Group Project of the Southern Marine Science and Engineering Guangdong Laboratory (Zhuhai) (No. 311020001), as well as Guangdong Province Key Laboratory for Climate Change and Natural Disaster Studies (Grant 2020B1212060025) are also gratefully acknowledged. The supports by National Supercomputer Center in Guangzhou, P.R. China are also gratefully acknowledged.
Footnotes
Supplementary data to this article can be found online at https://doi.org/10.1016/j.buildenv.2022.109160.
Appendix A. Supplementary data
The following is the Supplementary data to this article:
References
- 1.World Health Organization (WHO) Modes of transmission of virus causing COVID-19: implications for IPC precaution recommendations: scientific brief. https://apps.who.int/iris/handle/10665/331616
- 2.World Health Organization (WHO) WHO coronavirus (Covid-19) dashboard. 2021. https://covid19.who.int/
- 3.Asadi S., Bouvier N., Wexler A., Ristenpart W. The coronavirus pandemic and aerosols: does COVID-19 transmit via expiratory particles. Aerosol Sci. Technol. 2020;54(6):635–638. doi: 10.1080/02786826.2020.1749229. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 4.Drossinos Y., Stilianakis N. What aerosol physics tells us about airborne pathogen transmission. Aerosol Sci. Technol. 2020;54(6):639–643. doi: 10.1080/02786826.2020.1751055. [DOI] [Google Scholar]
- 5.Kutter J., Spronken M., Fraaij P., Fouchier R., Herfst S. Transmission routes of respiratory viruses among humans. Curr. Opin. Virol. 2018;28:142–151. doi: 10.1016/j.coviro.2018.01.001. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 6.van Doremalen N., Bushmaker T., Morris D., Holbrook M., Munster V. Aerosol and surface stability of SARS-CoV-2 as compared with SARS-CoV-1. N. Engl. J. Med. 2020;382(16):1564–1567. doi: 10.1056/NEJMc2004973. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 7.Li Y. Basic routes of transmission of respiratory pathogens—a new proposal for transmission categorization based on respiratory spray, inhalation, and touch. Indoor Air. 2021;31(1):3–6. doi: 10.1111/ina.12786. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 8.Marr L., Tang J. A paradigm shift to alig n transmission routes with mechanisms. Clin. Infect. Dis. 2021;73(10):1747–1749. doi: 10.1093/cid/ciab722. [DOI] [PubMed] [Google Scholar]
- 9.Hang J., Li Y., Jin R. The influence of human walking on the flow and airborne transmission in a six-bed isolation room: tracer gas simulation. Build. Environ. 2014;77:119–134. doi: 10.1016/j.buildenv.2014.03.029. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 10.Li Y., Qian H., Hang J., Chen X., Cheng P., Ling H., Wang S., Liang P., Li J., Xiao S. Probable airborne transmission of SARS-CoV-2 in a poorly ventilated restaurant, Build. Environ. Times. 2021;196 doi: 10.1016/j.buildenv.2021.107788. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 11.Ou C., Hu S., Luo K., Yang H., Hang J., Cheng P., Hai Z., Xiao S., Qian H., Xiao S. Insufficient ventilation led to a probable long-range airborne transmission of SARS-CoV-2 on two buses. Build. Environ. 2022;207 doi: 10.1016/j.buildenv.2021.108414. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 12.Kang M., Wei J., Yuan J., Guo J., Zhang Y., Hang J., Qu Y., Qian H., Zhuang Y., Chen X. Probable evidence of fecal aerosol transmission of SARS-CoV-2 in a high-rise building. Ann. Intern. Med. 2020;173(12):974–980. doi: 10.7326/M20-0928. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 13.Liu X., Niu J., Kwok K. Analysis of concentration fluctuations in gas dispersion around high-rise building for different incident wind directions. J. Hazard Mater. 2011;192(3):1623–1632. doi: 10.1016/j.jhazmat.2011.06.090. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 14.Liu X., Niu J., Kwok K., Wang J., Li B. Local characteristics of cross-unit contamination around high-rise building due to wind effect: mean concentration and infection risk assessment. J. Hazard Mater. 2011;192(1):160–167. doi: 10.1016/j.jhazmat.2011.04.106. [DOI] [PubMed] [Google Scholar]
- 15.Wang Q., Li Y., Lung D., Chan P., Dung C., Jia W., Miao T., Huang J., Chen W., Wang Z. Aerosol transmission of SARS-CoV-2 due to the chimney effect in two high-rise housing drainage stacks. J. Hazard Mater. 2022;421 doi: 10.1016/j.jhazmat.2021.126799. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 16.Yu I., Li Y., Wong T., Tam W., Chan A., Lee J., Leung D., Ho T. Evidence of airborne transmission of the severe acute respiratory syndrome virus. N. Engl. J. Med. 2004;350(17):1731–1739. doi: 10.1056/nejmoa032867. [DOI] [PubMed] [Google Scholar]
- 17.Liu L., Li Y., Nielsen P., Wei J., Jensen R. Short-range airborne transmission of expiratory droplets between two people. Indoor Air. 2017;27(2):452–462. doi: 10.1111/ina.12314. [DOI] [PubMed] [Google Scholar]
- 18.Liu L., Wei J., Li Y., Ooi A. Evaporation and dispersion of respiratory droplets from coughing. Indoor Air. 2017;27(1):179–190. doi: 10.1111/ina.12297. [DOI] [PubMed] [Google Scholar]
- 19.Liu F., Luo Z., Li Y., Zheng X., Zhang C., Qian H. Revisiting physical distancing threshold in indoor environment using infection-risk-based modeling. Environ. Int. 2021;153 doi: 10.1016/j.envint.2021.106542. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 20.Zhang N., Chen X., Jia W., Jin T., Xiao S., Chen W., Hang J., Ou C., Lei H., Qian H., Su B., Li J., Liu D. Evidence for lack of transmission by close contact and surface touch in a restaurant outbreak of COVID-19. J. Infect. 2021;83:207–216. doi: 10.1016/j.jinf.2021.05.030. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 21.Hang J., Li Y., Ching W., Wei J., Jin R., Liu L., Xie X. Potential airborne transmission between two isolation cubicles through a shared anteroom. Build. Environ. 2015;89:264–278. doi: 10.1016/j.buildenv.2015.03.004. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 22.Qian H., Li Y., Nielsen P., Hyldgaard C., Wong T., Chwang A. Dispersion of exhaled droplet nuclei in a two-bed hospital ward with three different ventilation systems. Indoor Air. 2006;16(2):111–128. doi: 10.1111/j.1600-0668.2005.00407.x. [DOI] [PubMed] [Google Scholar]
- 23.Bogoch I., Watts A., Thomas-Bachli A., Huber C., Khan K. Pneumonia of unknown aetiology in Wuhan, China: potential for international spread via commercial air travel. J. Trav. Med. 2020;27(2):1–3. doi: 10.1093/jtm/taaa008. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 24.Gupta J., Lin C., Chen Q. Transport of expiratory droplets in an aircraft cabin. Indoor Air. 2011;21(1):3–11. doi: 10.1111/j.1600-0668.2010.00676.x. [DOI] [PubMed] [Google Scholar]
- 25.Oztig L., Askin O. Human mobility and coronavirus disease 2019 (COVID-19): a negative binomial regression a nalysis. Publ. Health. 2020;185:364–367. doi: 10.1016/j.puhe.2020.07.002. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 26.Zhang L., Li Y. Dispersion of coughed droplets in a fully-occupied high-speed rail cabin. Build. Environ. 2012;47:58–66. doi: 10.1016/j.buildenv.2011.03.015. [DOI] [Google Scholar]
- 27.Zhao S., Zhuang Z., Ran J., Lin J., Yang G., Yang L., He D. The association between domestic train transportation and novel coronavirus (2019-nCoV) outbreak in China from 2019 to 2020: a data-driven correlational report. Trav. Med. Infect. Dis. 2020;33 doi: 10.1016/j.tmaid.2020.101568. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 28.Yang X., Ou C., Yang H., Liu L., Song T., Kang M., Lin H., Hang J. Transmission of pathogen-laden expiratory droplets in a coach bus. J. Hazard Mater. 2020;397 doi: 10.1016/j.jhazmat.2020.122609. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 29.Zheng R., Xu Y., Wang W., Ning G., Bi Y. Spatial transmission of COVID-19 via public and private transportation in China, Travel Med. Inf. Disp. 2020;34 doi: 10.1016/j.tmaid.2020.101626. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 30.Chao C., Man P., Morawska L., Johnson G., Katoshevski D. Characterization of expiration air jets and droplet size distributions immediately at the mouth opening. J. Aerosol Sci. 2009;40(2):122–133. doi: 10.1016/j.jaerosci.2008.10.003. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 31.Morawska L., Johnson G., Ristovski Z., Hargreaves M., Mengersen K., Corbett S., Chao C., Li Y., Katoshevski D. Size distribution and sites of origin of droplets expelled from the human respiratory tract during expiratory activities. J. Aerosol Sci. 2009;40(3):256–269. doi: 10.1016/j.jaerosci.2008.11.002. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 32.Wei J., Li Y. Enhanced spread of expiratory droplets by turbulence in a cough jet. Build. Environ. 2015;93:86–96. doi: 10.1016/j.buildenv.2015.06.018. [DOI] [Google Scholar]
- 33.Xie X., Li Y., Chwang A., Ho P., Seto W. How far droplets can move in indoor environments-revisiting the Wells evaporation-falling curve. Indoor Air. 2007;17(3):211–225. doi: 10.1111/j.1600-0668.2007.00469.x. [DOI] [PubMed] [Google Scholar]
- 34.Tung Y., Shih Y., Hu S. Numerical study on the dispersion of airborne contaminants from an isolation room in the case of door opening. Appl. Therm. Eng. 2009;29:1544–1551. doi: 10.1016/j.applthermaleng.2008.07.009. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 35.Villafruela J., Olmedo I., José J. Influence of human breathing modes on airborne cross infection risk. Build. Environ. 2016;106:340–351. doi: 10.1016/j.buildenv.2016.07.005. [DOI] [Google Scholar]
- 36.Yin Y., Xu W., Gupta J., Guity A., Marmion P., Manning A., Gulick B., Zhang X., Chen Q. Experimental study on displacement and mixing ventilation systems for a patient ward. HVAC R Res. 2009;15(6):1175–1191. doi: 10.1080/10789669.2009.10390885. [DOI] [Google Scholar]
- 37.Cermak R., Melikov A. Protection of occupants from exhaled infectious agents and floor material emissions in rooms with personalized and underfloor ventilation. HVAC R Res. 2007;13(1):23–38. doi: 10.1080/10789669.2007.10390942. [DOI] [Google Scholar]
- 38.Redrow J., Mao S., Celik I., Posada J., Feng Z. Modeling the evaporation and dispersion of airborne sputum droplets expelled from a human cough. Build. Environ. 2011;46(10):2042–2051. doi: 10.1016/j.buildenv.2011.04.011. [DOI] [Google Scholar]
- 39.Yakhot V., Orszag S. Renormalization group analysis of turbulence. I. Basic theory. J. Sci. Comput. 1986;1(1):3–51. doi: 10.1103/PhysRevLett.57.1722. [DOI] [PubMed] [Google Scholar]
- 40.Zhang T., Chen Q. Identification of contaminant sources in enclosed spaces by a single sensor. Indoor Air. 2007;17(6):439–449. doi: 10.1111/j.1600-0668.2007.00489.x. [DOI] [PubMed] [Google Scholar]
- 41.Zhang Z., Zhang W., Zhai Z., Chen Q. Evaluation of various turbulence models in predicting airflow and turbulence in enclosed environments by CFD: Part 2—comparison with experimental data from literature. HVAC R Res. 2007;13(6):871–886. doi: 10.1080/10789669.2007.10391460. [DOI] [Google Scholar]
- 42.Zhang Z., Chen X., Mazumdar S., Zhang T., Chen Q. Experimental and numerical investigation of airflow and contaminant transport in an airliner cabin mockup. Build. Environ. 2009;44(1):85–94. doi: 10.1016/j.buildenv.2008.01.012. [DOI] [Google Scholar]
- 43.Zhang Z., Chen Q. Comparison of the Eulerian and Lagrangian methods for predicting particle transport in enclosed spaces. Atmos. Environ. 2007;41(25):5236–5248. doi: 10.1016/j.atmosenv.2006.05.086. [DOI] [Google Scholar]
- 44.Qian H., Li Y. Removal of exhaled particles by ventilation and deposition in a multibed airborne infection isolation room. Indoor Air. 2010;20(4):284–297. doi: 10.1111/j.1600-0668.2010.00653.x. [DOI] [PubMed] [Google Scholar]
- 45.Clift R., Grace J., Weber M. Academic Press; 1978. Bubbles, Drops, and Particles. [DOI] [Google Scholar]
- 46.Hinds W. John Wiley & Sons; 1999. Aerosol Technology: Properties, Behavior, and Measurement of Airborne Particles. [Google Scholar]
- 47.Potter J., Matthews L., Lemm J., Spector S. Human pulmonary secretions in health and disease. Ann. N. Y. Acad. Sci. 1963;106(2):692–697. doi: 10.1111/j.1749-6632.1963.tb16677.x. [DOI] [PubMed] [Google Scholar]
- 48.Ranz W., Marshall W. Evaporation from drops, Part II. Chem. Eng. Prog. 1952;48(4):7. [Google Scholar]
- 49.Zhao P., Li Y. Correlation between the normal position of a particle on a rough surface and the van der Waals force. Colloids Surf. A Physicochem. Eng. Asp. 2020;585 doi: 10.1016/j.colsurfa.2019.124096. [DOI] [Google Scholar]
- 50.Magar A., Joshi M., Rajagopal P., Khan A., Rao M., Sapra B. CFD simulation of the airborne transmission of covid-19 vectors emitted during respiratory mechanisms : revisiting the concept of safe distance. ACS Omega. 2021;6:16876–16889. doi: 10.1021/acsomega.1c01489. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 51.Shao X., Li X. COVID-19 transmission in the first presidential debate in 2020. Phys. Fluids. 2020;32:1–9. doi: 10.1063/5.0032847. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 52.Qian H., Li Y., Nielsen P., Huang X. Spatial distribution of infection risk of SARS transmission in a hospital ward. Build. Environ. 2009;44:1651–1658. doi: 10.1016/j.buildenv.2008.11.002. [DOI] [Google Scholar]
- 53.Buonanno G., Stabile L., Morawska L. Estimation of airborne viral emission: quanta emission rate of SARS-CoV-2 for infection risk assessment. Environ. Int. 2020;141 doi: 10.1016/j.envint.2020.105794. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 54.Riley E., Murphy G., Riley R. Airborne spread of measles in a suburba n elementary school. Am. J. Epidemiol. 1978;107:421–432. doi: 10.1093/oxfordjournals.aje.a112560. [DOI] [PubMed] [Google Scholar]
- 55.Zhang S., Lin Z. Dilution-based evaluation of airborne infection risk-Thorough expansion of Wells-Riley model. Build. Environ. 2021;194 doi: 10.1016/j.buildenv.2021.107674. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 56.Dai H., Zhao B. Association of the infection pr obability of COVID-19 with ventilation rates in confined spaces. Build. Simulat. 2020;13:1321–1327. doi: 10.1007/s12273-020-0703-5. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 57.Yang H., Chen T., Lin Y., Buccolieri R., Mattsson M., Zhang M., Hang J., Wang Q. Integrated impacts of tree planting and street aspect ratios on CO dispersion and personal exposure in full-scale street canyons. Build. Environ. 2020;169 doi: 10.1016/j.buildenv.2019.106529. [DOI] [Google Scholar]
- 58.Mesgarpour M., Abad J., Alizadeh R., Wongwises S., Doranehgard M., Ghaderi S., Karimi N. Prediction of the spread of Corona-virus carrying droplets in a bus-A computational based artificial intelligence approach. J. Hazard Mater. 2021;413 doi: 10.1016/j.jhazmat.2021.125358. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 59.Duan W., Mei D., Li J., Liu Z., Ja M., Hou S. Spatial distribution of exhalation droplets in the bus in different seasons. Aerosol Air Qual. Res. 2021;21 doi: 10.4209/aaqr.200478. 200478-200478. [DOI] [Google Scholar]
- 60.Sun S., Li J., Han J. How human thermal plume influences near-human transport of respiratory droplets and airborne particles: a review. Environ. Chem. Lett. 2021;19:1971–1982. doi: 10.1007/s10311-020-01178-4. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 61.Yang C., Yang X., Zhao B. The ventilation needed to control thermal plume and particle dispersion from manikins in a unidirectional ventilated protective isolation room. Build. Simulat. 2015;8(5):551–565. doi: 10.1007/s12273-014-0227-6. [DOI] [Google Scholar]
- 62.Chen C., Zhao B. Some questions on dispersion of human exhaled droplets in ventilation room: answers from numerical investigation. Indoor Air. 2010;20(2):95–111. doi: 10.1111/j.1600-0668.2009.00626.x. [DOI] [PubMed] [Google Scholar]
- 63.Tsuda A., Henry F., Butler J. Particle transport and deposition: basic physics of particle kinetics. Compr. Physiol. 2013;3(4):1437–1471. doi: 10.1002/cphy.c100085. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 64.Chen W., Zhang N., Wei J., Yen H., Li Y. Short-range airborne route dominates exposure of respiratory infection during close contact. Build. Environ. 2020;176 doi: 10.1016/j.buildenv.2020.106859. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 65.Ji Y., Qian H., Ye J., Zheng X. The impact of ambient humidity on the evaporation and dispersion of exhaled breathing droplets: a numerical investigation. J. Aerosol Sci. 2018;115:164–172. doi: 10.1016/j.jaerosci.2017.10.009. [DOI] [Google Scholar]
- 66.Zhu S., Kato S., Yang J. Study on transport characteristics of saliva droplets produced by coughing in a calm indoor environment. Build. Environ. 2006;41(12):1691–1702. doi: 10.1016/j.buildenv.2005.06.024. [DOI] [Google Scholar]
- 67.He Q., Niu J., Gao N., Zhu T., Wu J. CFD study of exhaled droplet transmission between occupants under different ventilation strategies in a typical office room. Build. Environ. 2011;46(2):397–408. doi: 10.1016/j.buildenv.2010.08.003. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 68.Zhao Z., Xi C., Mazumdar S., Zhang T., Chen Q. Experimental and numerical investigation of airflow and contaminant transport in an airliner cabin mockup. Build. Environ. 2009;44(1):85–94. doi: 10.1016/j.buildenv.2008.01.012. [DOI] [Google Scholar]
- 69.Lai A., Nazaroff W. Modeling indoor particle deposition from turbulent flow onto smooth surfaces. J. Aerosol Sci. 2000;31(4):463–476. doi: 10.1016/S0021-8502(99)00536-4. [DOI] [Google Scholar]
- 70.Chen W., Qian H., Zhang N., Liu F., Liu L., Li Y. Extended short-range airborne transmission of respiratory infections. J. Hazard Mater. 2022;422 doi: 10.1016/j.jhazmat.2021.126837. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 71.Mirzaie M., Lakzian E., Khan A., Warkiani M., Mahian O., Ahmadi G. COVID-19 spread in a classroom equipped with partition–A CFD approach. J. Hazard Mater. 2021;420 doi: 10.1016/j.jhazmat.2021.126587. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 72.World Health Organization (WHO) Coronavirus disease (COVID-19): how is it transmitted. https://www.who.int/news-room/q-a-detail/coronavirus-disease-covid-19-how-is-it-transmitted
- 73.American Society of Heating . ASHRAE Standard; Atlanta, USA: 2019. Refrigerating and Air-Conditioning Engineers (ASHRAE) Ventilation for Acceptable Indoor Air Quality. [Google Scholar]
- 74.Etheridge D., Sandberg M. John Wiley & Sons; Chichester, UK: 1996. Building Ventilation: Theory and Measurement. [Google Scholar]
- 75.Cheng P., Luo K., Xiao S., Yang H., Hang J., Ou C., Cowling B., Yen H., Sc D., Hu S., Li Y. Predominant airborne transmission and insignificant fomite transmission of SARS-CoV-2 in a two-bus COVID-19 outbreak origi nating from the same pre-symptomatic index case. J. Hazard Mater. 2022;425 doi: 10.1016/j.jhazmat.2021.128051. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 76.Gupta J., Lin C., Chen Q. Inhalation of expiratory droplets in aircraft cabins. Indoor Air. 2011;21(4):341–350. doi: 10.1111/j.1600-0668.2011.00709.x. [DOI] [PubMed] [Google Scholar]
Associated Data
This section collects any data citations, data availability statements, or supplementary materials included in this article.