Skip to main content
. 2022 May 31;8(6):e09624. doi: 10.1016/j.heliyon.2022.e09624

Table 2.

Solar and wind DG and types of fault.

3_phase (KA) LG (KA)
FL Bus 31 Bus 32 Bus 33 Bus 62 Bus 31 Bus 32 Bus 33 Bus 62
31 1.236 1.224 1.212 1.178 0.933 0.886 0.844 0.789
32 1.179 1.217 1.205 1.125 0.859 0.926 0.879 0.735
33 1.125 1.160 1.198 1.075 0.795 0.977 0.918 0.687
62 1.123 1.113 1.103 1.211 0.763 0.731 0.703 0.923
LL (KA) DLG (KA)
FL Bus 31 Bus 32 Bus 33 Bus 62 Bus 31 Bus 32 Bus 33 Bus 62
31 1.080 1.069 1.058 1.028 1.152 1.130 1.111 1.077
32 1.029 1.063 1.052 0.981 1.097 1.137 1.116 1.030
33 0.982 1.013 1.046 0.937 1.046 1.082 1.123 0.986
62 0.980 0.970 0.961 1.058 1.037 1.021 1.008 1.133

An increasing number of DG have great support for the increment of fault current level to the system.