Table 4.

Rated performance values for Bard WH-B and WH-C systems [24,25]. Fan power data estimated from field measurements of fan power intensity [26]. Supply airflow rates per person assume 27 occupants.

Units W18HB W24HB W36HB W48HC W60HC
Cooling Capacity kW 5.1 6.9 10.6 13.9 16.0
Cooling COP 3.31 3.31 3.25 3.22 3.22
Heating Capacity kW 4.9 6.6 9.3 12.1 15.0
Heating COP 3.5 3.5 3.3 3.24 3.25
Supply Airflow l/s 283.2 377.6 542.7 731.5 825.9
Supply Airflow l/(s.person) 10.5 14.0 20.1 27.1 30.6
Fan Power W 261 347 499 673 760
Auxiliary Heat kW 4.0–15.0 4.0–15.0 4.0–20.0 4.0–20.0 4.0–20.0
Filter Face Area m2 0.26 0.26 0.31 0.52 0.52