TABLE 3.
Concentrations of total airborne fungal spores during disturbance sampling within AHUs before and after installation of germicidal UV lamps
| Fungal taxon isolated | Concn (103 spores/m3)
|
|||
|---|---|---|---|---|
| Study floora
|
Control floor
|
|||
| Mayb | September | Mayb | September | |
| Alternaria | 0.04 (0.03)c | |||
| Cladosporium | 29.54 (8.75) | 5.43 (3.35)d | 19.00 (14.16) | 68.42 (30.91)d |
| Penicillium- Aspergillus | 27.49 (20.92) | 6.69 (2.09)d | 5.63 (2.55) | 185.56 (52.51)d |
| Ascospores | 0.01 (0.01) | 0.01 (0.01) | 0.03 (0.01) | |
| Basidiospores | 0.12 (0.06) | 0.04 (0.02) | 0.05 (0.03) | 0.06 (0.04) |
| Smuts | 0.03 (0.01) | 0.01 (0.01) | 0.04 (0.02) | |
| Other | 0.70 (0.25) | 0.24 (0.06) | 0.47 (0.2) | 1.46 (1.09) |
| Total | 57.92 (25.09) | 12.41 (4.47)d | 25.19 (16.73) | 255.54 (82.27)d |
UV lamps were used only on the study floor.
May concentrations were measured before the UV lamps were turned on.
Mean (standard error).
Concentrations on the control floor and the study floor were significantly different after the use of germicidal UV lamps (P < 0.05).