Insulator condition dependent on experimentally determined indicators values.

Indicator Normal range Abnormal range Critical range Pre-flashover value
C1  < 1.165  > 1.165and < 2.86  > 2.86  > 10
C2  > 59.3  > 18.7 and < 59.3  < 18.7 ≈ 0
C3  < 1.53  > 1.53 and < 5.1  > 5.1  > 28
C4  < 1.6  > 1.6 and < 2  > 2  > 2.8
C5  < 15  > 15 and < 45  > 45  > 65
C6  > 3  > 1 and < 3  < 1  < 0.4
C7  < 0.62  > 0.62 and < 0.73  > 0.73  > 0.85