Airborne viral load (# infectious viruses per volume of air) and
relative risk of IAV (A) and SARS-CoV-2 (B) transmission under different
air treatment scenarios. Calculations are for a room (20 °C,
50% RH) with different ventilation rates (ACH) and subject to various
air treatments, assuming the room to accommodate one infected person
per 10 m3 of air, emitting virus-laden aerosol by normal
breathing (solid curve in Figure 4E), and assuming one infectious virus per aerosol particle
irrespective of size (see Figure S18 for
a scenario with a size-dependent virus distribution). Steady-state
viral load (left axes) is calculated as the balance of exhaled viruses
and their removal by ventilation (0.1–10 ACH), deposition,
and inactivation (calculated as for Figure 4D,E, starting from radius 0.05 μm,
the radius of viruses). ACH affects the indoor trace gas-phase concentrations
[at higher ACH, gases with predominantly outdoor sources (HNO3 and HCl) have higher concentration and gases with indoor
sources (NH3, CO2, and CH3COOH) have
lower concentrations]. We assume gas-phase concentrations in Table S4 to refer to 2 ACH and then calculate
the gas-phase concentration for 10 ACH and 0.1 ACH by mixing with
more or less outdoor air (see the Supporting Information for further details). ACH also determines the mixing speed of the
exhalation plume with indoor air (see the Supporting Information). Whiskers show the uncertainty range resulting
from the spread of trace gas concentrations in room air (upper limits
use the least acidic composition in Table S4, i.e., the highest measured NH3 and the lowest for all
acidic gases and lower limits conversely). Right axes show the transmission
risk under these treatments relative to the risk in a room with typical
indoor air (see Table S4) and 2 ACH (thin
horizontal line). A detailed description of the relative risk calculations
is given in the Supporting Information.
Typical indoor air is shown by black bars, filtered air with removal
of trace gases to 20% or to 1% by red bars, air with NH3 removed to 10 ppt by light blue bars, and air enriched to 50 ppb
HNO3 by dark blue bars. The whiskers in the case with NH3 removal include the range of possible HNO3 release
from the background aerosol particles after removing NH3 from the indoor air (see Table S4). Thick
gray horizontal lines indicate the viral load and relative transmission
risk in the absence of any inactivation. Results for 2 and 5 ppb HNO3, see Figure S20, results for HCoV-229E,
and analyses for coughing and speaking/singing, see Figure S19.