Skip to main content
. 2023 Jan 11;23(2):859. doi: 10.3390/s23020859

Table 8.

A comparison of the real situation and system recognition.

Fire Types Experiments/n Alarms/n Missed Alarms/n Accuracy/%
Polyurethane fire 50 49 1 98%
Alcohol fire 50 48 2 96%
Beech wood smolder 50 48 2 96%
Cotton rope smolder 50 49 1 98%