Table 1.

Simulation input data to analyze the performance of an integrated, outdoor fan-ventilated cooling device.

Index Base Model Case 1
System configuration DOAS package air conditioner integrated ventilation, cooling device
Nominal Cooling Capacity [W] 12,500
TotCapTempModFac 0.94 + 9.5E−3x + 6.8E−4x2 - 1.1E−2−y + 5.2E−6y2 - 9.7E−6xy (x > 12.78, y < 23.89)
TotCapFlowModFac 0.34 + 3.4E−2x - 6.2E−5x2 + 4.9E−3y - 4.3E−4y2 - 7.2E-4xy (x > 18, y < 46.11)
Condenser location utility room inside system
Condenser process air utility room air relief air of heat recovery
Condensor air flow rate [m3 s-1] 1.9
Nominal COP [−] 3.0
Weather data Inchoen Int’l airport TMYx
Run period 7/1 00:00–9/31 24:00 (92 d)
System operation hours 08:00–19:00 (12 h)
Indoor Set point Temperature [°C] 24
Process air mass flow 1.0 m3 s−1

COP, coefficient of performance; DOAS, dedicated outdoor air system; TotCapTempModFrac, total cooling capacity function of temperature fraction; TotCapFlowModFrac, total cooling capacity function of flow fraction.