Abstract
Exterior finishes protect reinforced concrete buildings against environmental factors, improve their durability, and enhance their exterior design. In this study, the influence of different metal types used in arc thermal metal spraying on the adhesion between concrete and metal coatings was analyzed. Five metals with different melting points were tested, and the differences between their melting points and surface temperatures immediately after thermal spraying were measured. The bonding strength of each metal was evaluated. Additionally, the interface between the concrete surface and metal coating was analyzed using image analysis and optical microscopy. The results demonstrated that Zn achieved the highest bonding strength (1.84 MPa), which had the lowest melting point and surface temperature immediately after spraying, while Cu/Sn achieved the lowest strength (1.38 MPa), which had the highest temperatures. The bonding strength had a closer relationship (R2 = 0.9946) with the difference between the melting point and surface temperature immediately after spraying than that (R2 = 0.9589) with the surface temperature immediately after spraying. The bonding strength increased as the ratio of the non-interfacial failure area to the total area increased, ensuring a stronger attachment to the concrete surface. Overall, the results showed that the bonding strength was significantly affected by the metal type.
Keywords: metals, arc thermal metal spraying, bonding strength, non-interfacial failure
1. Introduction
The exterior finishes of reinforced concrete buildings provide an important protective element against environmental factors, such as temperature, snow, wind, rain, and external disasters. Furthermore, they can improve the durability and exterior design of buildings. Therefore, sufficient considerations are required for appropriately selecting the exterior finishing materials and methods [1,2,3].
The finishing methods currently applied to building structures include the wet method of directly applying paint and plaster materials to the structure and the dry method of attaching stone materials and panels [4]. The wet finishing method is characterized by simple construction and low initial construction costs. Still, it requires high maintenance costs because the maintenance interval is short, owing to surface contamination and low weather resistance. Moreover, after re-coating, the coating layer becomes thicker, thereby decreasing the bonding performance. Conversely, the dry finishing method ensures high durability but involves difficult maintenance and repair processes due to damage to finishing materials and construction difficulties associated with anchor treatment [3,4,5,6]. To overcome the shortcomings of conventional finishing methods (wet and dry methods), methods that simultaneously serve as a structure and finish material, such as exposed concrete, have been developed. In such methods, cracks propagate in the finished area if the initial construction of the structure is not performed properly, and the durability rapidly decreases without appropriate surface maintenance. The exposed concrete also has limitations in expressing the outer wall color and three-dimensional design of the building. As such, the development of a finishing method that involves simple construction and excellent building design while retaining the benefits of the dry method is required, which uses highly durable metal panels [3,6,7].
Recently, metal-film finishing methods have been developed to apply arc thermal metal spraying (ATMS) to water treatment and electromagnetic wave shielding facilities [6,8,9,10,11]. These new finishing methods apply metal spraying, a conventional technology mainly used in high-durability anti-corrosion applications for steel structures [5,10]. The anti-corrosion lifespan of ATMS is up to approximately 100 years, depending on the metal type, and is approximately three to four times longer than that of the paints used in the wet method [5,12]. These methods involve almost no defects because quality control can be performed during construction. They have high maintenance efficiency because only the damaged section must be repaired in the case of local damage [5,6,8,10,13,14,15]. However, the bond performance between the metal film and substrate is expected to vary significantly depending on the substrate conditions and type of metal-film finishing material [3,5,10,11]. In particular, when a metal film is directly applied to a concrete structure, the bond performance between the metal film and concrete is expected to vary depending on the metal because of property changes, such as the melting point. In previous studies, however, only the surface treatment of concrete, which is the substrate, and change in bonding strength according to moisture conditions have been considered [6]. No studies have been conducted on the influence of the metal type on the bonding strength [5,8,10].
Therefore, this study aims to evaluate the influence of the metal used as a wire material in ATMS on the concrete bonding strength. Metal coatings were formed on the concrete surface using various metals. The surface temperature of the coatings was measured immediately after spraying, as well as the bonding strength. In addition, the interface between the concrete surface and metal coating was evaluated through image analysis of the fracture sections and optical microscopy (OM).
2. Experimental Program
2.1. Experimental Overview
In this study, various experiments were performed to examine the bonding strength between the metal coating and concrete based on the metal type. Table 1 lists the experimental levels, factors, and items considered in this study.
Table 1.
Experimental Factor | Experimental Level | Measure Catalog |
---|---|---|
Types of metals | Zn | Temperature measurement |
Al | Bonding strength | |
Zn/Al | Failure mode analysis | |
Cu/Zn (Brass) | Image analysis | |
Cu/Sn (Bronze) | Optical microscopy | |
Common list | Substrate: Concrete Concrete Strength: 27 MPa Concrete Size: 300 mm × 300 mm × 50 mm Surface treatment: (1) Sand blasting → (2) SH → (3) SRA Coating Thickness: 200 μm |
Typically, concrete with a strength of 27 MPa is used as the substrate. The most efficient surface treatment methods in terms of the bonding strength determined in previous studies (sand blasting → surface hardener (SH) → surface roughness agent (SRA)) were used in this study [2,3]. In the case of sand blasting, silica sands with a particle size of 1.2–1.6 mm were blasted onto the concrete surface using high-pressured air to clean up the concrete surface and achieve a basic roughness.
After surface treatment, metal spraying was performed using five metals. A commonly used metal spray coating thickness of 200 μm was adopted [16]. The bonding strength and failure mode were evaluated as experimental parameters. The temperature of the metal applied to the surface was measured immediately after the spraying. Image analysis was conducted on fracture sections, and the concrete cross-section subjected to metal spraying was observed using a microscope.
2.2. Metals
For the appropriate application of ATMS to concrete surfaces, metals with a low melting point, unique color, and high durability are chosen from the metals that can be sprayed [2,3,4]. Therefore, in this study, Zn (SAMHWA NON-FERROUS METAL IND, Seoul, Republic of Korea), Al (SAMHWA NON-FERROUS METAL IND, Republic of Korea), and a Zn/Al alloy (SAMHWA NON-FERROUS METAL IND, Republic of Korea), which are mainly used in anti-corrosion techniques for steel structures, were used. Brass (Cu/Zn, KORYEO, China) and bronze (Cu/Sn, KORYEO, China), which have excellent color and metal-spraying efficiency with high corrosion resistance, were also used.
Table 2 lists the properties of the metals used in this study. For Zn, 100% pure white Zn with a melting point of 420 °C and density of 7.13 g/cm3 was used. For Al, 100% pure white Al with a melting point of 660 °C and density of 2.70 g/cm3 was used. In the case of the Zn/Al alloy, a gray alloy (Zn 85% and Al 15%) with a melting point of 540 °C and density of 4.91 g/cm3 was used in the experiment. Cu/Zn and Cu/Sn with melting points of 914 and 1018 °C, densities of 8.60 and 8.75 g/cm3, and metal ratios of 8:2 and 9:1, respectively, were used.
Table 2.
Metal | Melting Point (°C) | Density (g/cm3) | Weight Ratio (%) | Color |
---|---|---|---|---|
Zn | 420 | 7.13 | 100 | Light gray |
Zn/Al | 540 | 4.91 | 85/15 (Zn/Al) | Gray |
Al | 660 | 2.70 | 100 | White |
Cu/Zn | 914 | 8.60 | 80/20 (Cu/Zn) | Red brown |
Cu/Sn | 1018 | 8.75 | 90/10 (Cu/Sn) | Red gold |
2.3. Fabrication of Concrete as a Substrate
The cement used in the substrate concrete was ordinary Portland cement (Asia cement, Seoul, Republic of Korea), adhering to the KS L 5201 regulations [17]. Table 3 and Table 4 list the chemical composition and physical properties of the cement used. Table 5 lists the mixing proportions of the concretes used in this study. The water-to-binder (W/B) ratio was set to 0.5. Ordinary crushed stone with a maximum size of 25 mm (specific gravity of 2.64 and water absorption of 0.77%) was used for the coarse aggregate, and sea sand with a fineness modulus of 2.9 (specific gravity of 2.59) was used for the fine aggregate. In addition, a polycarboxylate superplasticizer (HMS, Republic of Korea) was used to improve the workability of concrete. Immediately after mixing, the concrete was poured into a 300 mm × 300 mm × 50 mm mold and compacted using a vibration table. The specimen was left in the mold for one day and subjected to water curing for 27 days. The strength [18], slump [19], and air content [20] of the cured concrete were evaluated according to the KS standards; the results are listed in Table 6.
Table 3.
SiO2
(%) |
Al2O3
(%) |
Fe2O3
(%) |
CaO (%) |
MgO (%) |
Na2O (%) |
K2O (%) |
SO3
(%) |
LOI | |
---|---|---|---|---|---|---|---|---|---|
Cement | 19.5 | 5.2 | 2.7 | 61.8 | 3.7 | 2.5 | 0.1 | 0.8 | 2.6 |
Table 4.
Density (g/cm3) |
Blaine (cm2/g) |
44 μm on Residue (%) | Setting Time (min) | Compressive Strength (MPa) | ||||
---|---|---|---|---|---|---|---|---|
Initial | Final | 3 Day | 7 Day | 28 Day | ||||
Cement | 3.14 | 3200 | 12.5 | 240 | 370 | 22.5 | 30.0 | 39.5 |
Table 5.
Specimen | W/B | Unit Weight (kg/m3) | Superplasticizer (%) | |||
---|---|---|---|---|---|---|
Water | Cement | Fine Aggregate | Coarse Aggregate | |||
Concrete | 0.5 | 175 | 350 | 905 | 835 | 0.8 |
Table 6.
Specimen | Slump (mm) | Air content (%) | 7D-Compressive Strength (MPa) | 28D-Compressive Strength (MPa) |
---|---|---|---|---|
Concrete | 180 | 4.5 | 20 | 27 |
2.4. ATMS
ATMS is a technology that forms a porous, strong, and stable film on the material surface by melting wire or powder metals using gas or electric arcs and spraying the molten metals under a high-pressure environment with six bars or higher [21,22,23,24]. ATMS can be categorized into gas and electrical spraying, according to the heat source. Because gas metal spraying has certain safety concerns owing to using a gas as the heat source, the experiments in this study were performed using high-frequency arc thermal metal spraying, which is an electrical spraying technique, as shown in Figure 1. High-frequency arc thermal metal spraying enables a safe construction, relatively high lamination speed, and a wide range of coatings [5,21,24].
The concrete cured for 28 days was dried at 100 °C for two days and subjected to sand blasting for surface cleaning. Subsequently, SH (TAS, Republic of Korea) was applied to increase the concrete surface strength, which is expected to affect the bonding strength as well [3,25]. SRA (EMS, Republic of Korea) was then applied to increase the roughness of the concrete surface. According to the experimental program, five metals were applied with a thickness of 200 μm. To ensure that metal spraying coatings with a constant thickness were obtained, the coating thickness was measured using a Vernier caliper after the operation. Figure 2 shows the specimen preparation process, and Table 7 lists the physical properties of the SH and SRA used in this study.
Table 7.
Type | Element | Density (g/m3) | Usage (g/m2) |
---|---|---|---|
Surface hardener (SH) | Silicate | 1.10 | 500–700 |
Surface roughness agent (SRA) | Epoxy, silica | 1.30 | 50 |
2.5. Test Methods
2.5.1. Temperature Measurement
Immediately after metal spraying, the surface temperature was measured using an infrared thermometer (FLUKE-62 Mini) on three points at a distance of 300 mm, as shown in Figure 3. Table 8 lists the basic technical specifications of the thermometer. In this study, the three measurements were averaged to evaluate the overall surface temperature. At the time of measurement, the ambient temperature in the laboratory was adjusted to 20 ± 2 °C to minimize the influence of the external temperature.
Table 8.
Temperature Range (°C) |
Distance: Spot Size | Accuracy (°C) | Emissivity | Response Time (ms) |
---|---|---|---|---|
−30–500 °C | 10:0.1 | ±1 | 0.95 | <500 |
2.5.2. Bonding Strength and Failure Mode
The bonding strength was evaluated according to the KS F 4716 [26] and ASTM D 4541 [27]. As shown in Figure 4, a 40 mm × 40 mm square tensile attachment was adhered to the specimen with a metal spraying coating for each experiment using an epoxy adhesive and dried for 24 h. A vertical cut was made on the concrete surface around the attachment, as shown in Figure 4b. The bonding strength was calculated using Equation (1) after measuring the maximum load applied during the tensile bond test. The average of nine bonding strength measurements was evaluated as the overall bonding strength. Thereafter, the bond failure behavior of the metal film was visually observed, and an image analysis was conducted.
(1) |
2.5.3. Image Analysis
After the bonding strength measurements were completed, image analysis was conducted on the fracture sections to examine the failure pattern between the metal spraying coating and concrete surface and quantitatively calculate the non-interfacial failure area. Figure 5 shows the image analysis procedure adopted in this study to calculate the area quantitatively. ImageJ software was used for image analysis [28]. After completing the bonding strength measurements, images of the fracture section were captured using a high-definition camera (Figure 5a). Thereafter, a 2 cm × 2 cm area was set in the center of the fracture section as the measurement area (Figure 5b). Because the SRA used in this study was red, the area that did not exhibit a red color was quantitatively calculated using the color thresholding function (Figure 5c). In the case of non-interfacial failure, concrete failure occurs rather than failure between the metal spraying coating and concrete surface coated with SRA. Therefore, the areas that did not exhibit a red color were quantitatively measured. Finally, the ratio of the non-interfacial failure area to the total area (RN) was calculated using the following equation:
(2) |
2.5.4. OM
An OM (HT004, HiMaxTech) was used to observe the cross-sectional area of the specimen, as shown in Figure 6. To minimize the damage inflicted on the concrete surface and metal coating, OM samples were prepared in two steps. First, samples of 4 cm × 4 cm × 2 cm were cut using a sawing machine, and samples of 1 cm × 1 cm × 0.5 cm were prepared using a diamond cutting machine. The samples were then immersed in low-viscosity epoxy for 24 h. Once the epoxy was completely hardened, the cut surfaces of the samples were polished using a polishing machine (EcoMet 30) in the order of P400 -> P2400 -> P4000 -> 3 μm -> 1 μm using a SiC paper and IPA solution. The SiC paper was first washed in an ultrasonic bath before being replaced to prevent contamination by impurities on the cut surface.
3. Results and Discussions
3.1. Temperature
Figure 7 shows the melting points of the metals used in this study and their surface temperatures immediately after spraying. Zn exhibited the lowest surface temperature of approximately 14.2 °C, whereas Cu/Sn exhibited the highest surface temperature of approximately 44.8 °C. For the sprayed metals, the surface temperature increased in the order of Zn (14.2 °C), Zn/Al (20.2 °C), Al (25.8 °C), Cu/Zn (32.8 °C), and Cu/Sn (44.8 °C), indicating that the surface temperature was higher for metals with higher melting points.
Figure 8 shows the difference between the melting point and surface temperature immediately after spraying for each metal. Cu/Sn exhibited the largest difference (approximately 973.2 °C), followed by Cu/Zn (881.2 °C), Al (634.2 °C), Zn/Al (519.8 °C), and Zn (405.8 °C). ATMS is a technology that applies a coating to a surface by instantly melting a metal wire heated using electric arcs, and then spraying the molten metal using compressed air under six bars or higher. The metal temperature at the concrete surface was significantly lower than its melting point because the metal wire that was melted by the arc point was cooled by compressed air [21,22,23,24].
3.2. Bonding Strength
Figure 9 shows the results of the bonding-strength evaluation for each metal. Zn exhibited the highest bond performance of approximately 1.84 MPa. Zn/Al and Al showed bonding strengths of approximately 1.75 and 1.63 MPa, respectively. These results exceed the performance criterion of KS F 9001 (1.5 MPa). However, it was found that Cu/Zn and Cu/Sn, with bonding strengths of 1.47 and 1.38 MPa, respectively, did not meet the criterion.
Visual inspection of the failure pattern revealed that the non-interfacial or partial non-interfacial failures of Zn, Zn/Al, and Al met the performance criterion of KS F 9001, as shown in Figure 10. In other words, concrete failure (non-interfacial failure) was dominant rather than failure at the interface between the metal spraying coating and concrete surface (interfacial failure). Conversely, the interfacial failures of Cu/Zn and Cu/Sn did not meet the performance criterion. Therefore, within the scope of this study, non-interfacial failure was determined to occur at approximately 1.63 MPa based on the bonding strength.
Figure 11 shows the correlation between the surface temperature and bonding strength when metals were sprayed. Figure 12 shows the correlation between the bonding strength and the difference between the melting point and surface temperature. The bonding strength decreased as the surface temperature increased immediately after metal spraying. Moreover, an increase in the surface temperature immediately after metal spraying had a negative impact on the bonding strength. Similarly, the bonding strength decreased as the difference between the melting point and surface temperature increased immediately after metal spraying. Because the bonding strength was found to have a closer correlation (R2 = 0.9946) with the difference between the melting point and surface temperature immediately after metal spraying compared to its correlation (R2 = 0.9589) with the surface temperature immediately after metal spraying, the difference between the melting point and surface temperature immediately after metal spraying was assessed to have a more significant effect on the bonding strength. Voids are generated in the metal spraying coating because of the shrinkage between the metal particles as the sprayed metal rapidly cools. Furthermore, the bonding strength is decreased by the voids between the concrete surface and metal spraying coating [29].
3.3. Image Analysis
Figure 13 shows the interfacial and non-interfacial failure areas of the samples in black and white. RN results were calculated using image analysis. The RN values for Zn, Zn/Al, Al, Cu/Zn, and Cu/Sn were 90.56%, 86.51%, 55.66%, 42.41%, and 4.32%, respectively. Zn exhibited the highest RN value. This indicates that non-interfacial failure was dominant in the failure area. Moreover, Zn exhibited the highest bonding strength because non-interfacial failure was dominant. In contrast, Cu/Sn exhibited the lowest RN value, which indicates that interfacial failure was dominant compared to non-interfacial failure. The interfacial failure is judged to have a negative impact on the bonding strength rather than the concrete failure itself.
Figure 14 shows the correlations between RN and bonding strength and temperature difference. As the RN value increased, the bonding strength of the samples also increased. This indicates that the bonding strength increased because non-interfacial failure was more dominant than interfacial failure. Conversely, as shown in Figure 14b, the difference between the melting point and surface temperature immediately after metal spraying tended to decrease as the RN value increased. The temperature difference and bonding strength showed a close correlation (R2 = 0.99), as mentioned in the previous section. In other words, the significant difference between the melting point of the metal and surface temperature immediately after metal spraying had a negative impact on the bonding strength because it induced more failures at the interface between the concrete surface and metal coating (interfacial failure) than that of the concrete (non-interfacial failure).
3.4. OM
Figure 15 shows the cross-sections of Zn, which exhibited the highest bonding strength, and Cu/Sn, which showed the lowest bonding strength. The application of SRA to the concrete surface, followed by ATMS using different metals while preparing the specimens, allowed the red epoxy (SRA) between the metal coating and the concrete surface to be observed in the two cross-sectional images.
As shown in Figure 15a, the concrete and SRA were in close contact, and the SRA was closely attached to the metal coating in the Zn specimen. Conversely, in the case of Cu/Sn, the concrete and SRA were in close contact, as shown in Figure 15b; however, the metal coating and SRA were not closely attached to each other, which confirmed the gap between them.
Concrete surface treatment was conducted for the application of ATMS (SHA and SRA were applied). Metal coatings were generated on the concrete surface by applying ATMS. In this instance, only the metal type differed, whereas the distance between the concrete and metal spraying gun (300 mm) and the ambient temperature (20 ± 2 °C) were kept constant. Therefore, the adhesion between the concrete surface and metal coating was only affected by the metal type. During the application of ATMS, rapid cooling occurred because of the temperature difference between the ambient environment and metal particles when the metal particles collided with the concrete surface, causing the deposited metal particles to contract [29]. Therefore, the amount of contraction is expected to be larger for metals with high melting points than those with low melting points because of the larger temperature difference. For this reason, Cu/Sn, with the highest melting point, could not develop sufficient cohesiveness with SRA.
In addition, a close look at the metal coating revealed that the metal coating with Zn had a more compact cross-sectional geometry than that with Cu/Sn. In particular, voids of various sizes are observed in the red dotted circle depicted in Figure 15b. This indicates that voids were generated between the metal particles because adhesion between the metal particles and adhesion between the SRA and metal was not sufficient owing to contraction, as mentioned above.
4. Conclusions
The surface temperature varied depending on the type of metal used. Zn showed the lowest surface temperature, while Cu/Sn exhibited the highest. The surface temperature immediately after metal spraying increased with the metal’s melting point.
The strength of the bond between the concrete and metal coatings also differed depending on the type of metal used. Zn exhibited the highest bonding strength (1.84 MPa), while Cu/Sn showed the lowest (1.38 MPa). Upon examining the failure modes, non-interfacial failure occurred mostly with Zn, whereas interfacial failure occurred mostly with Cu/Sn.
Because the bonding strength exhibited a close relationship (R2 = 0.9946) with the difference between the melting point of the metal and surface temperature immediately after metal spraying compared to its relationship (R2 = 0.9589) with the surface temperature immediately after metal spraying, the difference between the melting point and surface temperature immediately after metal spraying was assessed to have a greater impact on the bonding strength between the sprayed metal coating and concrete.
The non-interfacial failure area was quantitatively evaluated using image analysis, and the results exhibited a tendency similar to the bonding strength. Zn exhibited the highest ratio of the non-interfacial failure area to total area (RN), whereas Cu/Sn exhibited the lowest RN value.
The metal coating was found to be closely attached to the concrete surface with Zn; however, there was a gap between the metal coating and the concrete surface with Cu/Sn. This gap induces interfacial failure and ultimately has a negative impact on the bonding strength.
The metal type (namely, the melting point of the metal) was found to have a significant influence on the bonding strength. For the application of metals with a high melting point to the concrete surface, further research on surface treatment methods is required to ensure adequate bonding strength.
Author Contributions
Conceptualization, J.-H.P. and S.-Y.K.; methodology, J.-H.P., S.-Y.K. and H.-S.L.; software, K.W.; validation, J.-H.P., H.-S.L. and K.W.; data curation, J.-H.P.; writing—original draft preparation, J.-H.P.; writing—review and editing, K.W.; visualization, S.-Y.K.; supervision, H.-S.L. and K.W.; funding acquisition, H.-S.L. All authors have read and agreed to the published version of the manuscript.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
Not applicable.
Conflicts of Interest
The authors declare no conflict of interest.
Funding Statement
This research was supported by a grant (2022R1A2C1093253) from the National Research Foundation of Korea. This research was also supported by a National Research Foundation of Korea grant funded by the Korean government (MSIT) (No. NRF-2018R1A5A1025137).
Disclaimer/Publisher’s Note: The statements, opinions, and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of the MDPI and/or editor(s). The MDPI and/or editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions, or products referred to in the content.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.
References
- 1.Nam G. Ph.D. Thesis. Pukyong National University; Busan, Republic of Korea: 2012. The Develop Mentand Application of In-Situ Water-Repellent Painting Method; pp. 1–2. [Google Scholar]
- 2.Sung-Ho J. Experimental study on the Adhesion Property between Spraying Metal and Concrete Surface according to the Treatment Method of Concrete Surface. J. Archit. Inst. Korea. 2003;19:83–90. [Google Scholar]
- 3.Park J.-H., Kim S.-Y., Lee H.-S. An Experimental Study on the Effect of Concrete Surface Treatment Methods on the Bond Strength of Metal Spray Coating. J. Archit. Inst. Korea Struct. Constr. 2020;36:147–154. [Google Scholar]
- 4.Lim J.-T., Jung H.-R. Study on the Development of Finishing Design Methods for Building Structures Using the Metal Films. J. Korea Inst. Struct. Maint. Insp. 2018;22:183–189. [Google Scholar]
- 5.Park J.-H. Ph.D. Thesis. Hanyang University; Seoul, Republic of Korea: 2018. A Study on the Ozone-Resistive and Corrosion Protecting Method for Concrete Structure of Water Treatment Facilities by Applying Anti-Corrosive Arc Thermal Spraying Coatings. [Google Scholar]
- 6.Lee H.-S., Park J.-H., Singh J.K., Choi H.-J., Mandal S., Jang J.-M., Yang H.-M. Electromagnetic shielding performance of carbon black mixed concrete with Zn–Al metal thermal spray coating. Materials. 2020;13:895. doi: 10.3390/ma13040895. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 7.Kondo T., Hamaki H., Masuyama T., Kamigaki N., Takeuchi N. Metal-spraying finishing onto concrete surface; Proceedings of the 1992 Annual Meeting, Japan Society of Finishing Technology; Tokyo, Japan. 9 October 1992; pp. 167–170. [Google Scholar]
- 8.Lee H.-S., Park J.-H., Singh J.K., Ismail M.A. Protection of reinforced concrete structures of waste water treatment reservoirs with stainless steel coating using arc thermal spraying technique in acidified water. Materials. 2016;9:753. doi: 10.3390/ma9090753. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 9.Legoux J.-G., Dallaire S. Adhesion mechanisms of arc-sprayed zinc on concrete. J. Therm. Spray Technol. 1995;4:395–400. doi: 10.1007/BF02648641. [DOI] [Google Scholar]
- 10.Park J.-H., Singh J.K., Lee H.-S. Ozone resistance, water permeability, and concrete adhesion of metallic films sprayed on a concrete structure for advanced water purification. Coatings. 2017;7:41. doi: 10.3390/coatings7030041. [DOI] [Google Scholar]
- 11.Jang J., Wi K., Lee H.-S., Singh J.K., Lee H.-H. Effects of surface treatment conditions on the bonding strength and electromagnetic pulse shielding of concrete using the 85Zn-15Al arc thermal metal spraying method. Materials. 2023;16:1372. doi: 10.3390/ma16041372. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 12.Jeong H.-R. A Study on the Evaluation of Corrosion Characteristics of Al-Mg Coating Deposited by Arc Thermal Spray Process. Hanyang University; Seoul, Republic of Korea: 2022. [Google Scholar]
- 13.Lee H.-S., Park J.-H., Singh J.K., Ismail M.A. Deposition of coating to protect waste water reservoir in acidic solution by arc thermal spray process. Adv. Mater. Sci. Eng. 2018;2018:4050175. doi: 10.1155/2018/4050175. [DOI] [Google Scholar]
- 14.Lee H.-S., Kwon S.-J., Singh J.K., Ismail M.A. Influence of Zn and Mg alloying on the corrosion resistance properties of Al coating applied by arc thermal spray process in simulated weather solution. Acta Metall. Sin. (Engl. Lett.) 2018;31:591–603. doi: 10.1007/s40195-018-0704-x. [DOI] [Google Scholar]
- 15.Lee H.-S., Singh J.K., Ismail M.A. An effective and novel pore sealing agent to enhance the corrosion resistance performance of Al coating in artificial ocean water. Sci. Rep. 2017;7:41935. doi: 10.1038/srep41935. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 16.Jang J.-M., Lee H.-S., Singh J.K. Electromagnetic shielding performance of different metallic coatings deposited by arc thermal spray process. Materials. 2020;13:5776. doi: 10.3390/ma13245776. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 17.Portland Cement. Korean Industrial Standards; Eumseong-gun, Republic of Korea: 2016. [Google Scholar]
- 18.Standard Test Method for Compressive Strength of Concrete. Korean Industrial Standards; Eumseong-gun, Republic of Korea: 2010. [Google Scholar]
- 19.Standard Test Method for Concrete Slump. Korean Industrial Standards; Eumseong-gun, Republic of Korea: 2012. [Google Scholar]
- 20.Standard Test Method for Unit Volume Mass and Air Volume Test Method of Unhardened Concrete (Mass Method) Korean Industrial Standards; Eumseong-gun, Republic of Korea: 2000. [Google Scholar]
- 21.Cinca N., Lima C.R.C., Guilemany J.M. An overview of intermetallics research and application: Status of thermal spray coatings. J. Mater. Res. Technol. 2013;2:75–86. doi: 10.1016/j.jmrt.2013.03.013. [DOI] [Google Scholar]
- 22.Bettridge D., Ubank R. Quality control of high-temperature protective coatings. Mater. Sci. Technol. 1986;2:232–242. doi: 10.1179/mst.1986.2.3.232. [DOI] [Google Scholar]
- 23.Jandin G., Liao H., Feng Z., Coddet C. Correlations between operating conditions, microstructure and mechanical properties of twin wire arc sprayed steel coatings. Mater. Sci. Eng. A. 2003;349:298–305. doi: 10.1016/S0921-5093(02)00767-0. [DOI] [Google Scholar]
- 24.Chaliampalias D., Vourlias G., Pavlidou E., Stergioudis G., Skolianos S., Chrissafis K. High temperature oxidation and corrosion in marine environments of thermal spray deposited coatings. Appl. Surf. Sci. 2008;255:3104–3111. doi: 10.1016/j.apsusc.2008.08.101. [DOI] [Google Scholar]
- 25.Park J.-H., Lee H.-S., Shin J.-H. An Experimental Study on Evaluation of Bond Strength of Arc Thermal Metal Spaying According to Treatment Method of Water Facilities Concrete Surface. J. Korea Inst. Build. Constr. 2016;16:107–115. doi: 10.5345/JKIBC.2016.16.2.107. [DOI] [Google Scholar]
- 26.Cement Filling Compound for Surface Preparation. Korean Industrial Standards; Eumseong-gun, Republic of Korea: 2022. [Google Scholar]
- 27.Standard Test Method for Pull-Off Strength of Coatings Using Portable Adhesion Testers. ASTM; West Conshohocken, PA, USA: 2022. [Google Scholar]
- 28.Schneider C.A., Rasband W.S., Eliceiri K.W. NIH Image to ImageJ: 25 years of image analysis. Nat. Methods. 2012;9:671–675. doi: 10.1038/nmeth.2089. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 29.Paredes R.S., Amico S., d’Oliveira A. The effect of roughness and pre-heating of the substrate on the morphology of aluminium coatings deposited by thermal spraying. Surf. Coat. Technol. 2006;200:3049–3055. doi: 10.1016/j.surfcoat.2005.02.200. [DOI] [Google Scholar]
Associated Data
This section collects any data citations, data availability statements, or supplementary materials included in this article.
Data Availability Statement
Not applicable.