. 2022 Sep 1;105(3):00368504221122287. doi: 10.1177/00368504221122287

Optimization insulation thickness and reduction of CO2 emissions for pipes in all generation district heating networks

Meryem Terhan 1,
PMCID: PMC10358625  PMID: 36047006

Abstract

District heating systems are provided solutions for the increasing energy problems in high-population cities. Energy costs go up depending on increasing heat loss in DHS's distribution network. Heat loss from the network consists of 5–20% of transferred energy, and this loss is higher than the other losses in the heating system. In the study, heat losses from the pipes such as supply-return pipes, hot water and circulation pipes into heat canals are investigated based on energy, exergy, economic and environmental. Optimum insulation thicknesses, energy savings, reduction of CO2 emissions, the first investment costs and payback periods of the pipes in the network of all-generation district heating systems are investigated by using Life Cycle Cost Analysis (LCCA) method for fuel types like natural gas, fuel oil and coal. Optimum insulation thicknesses are calculated for different nominal sizes of pipes and various insulation materials such as glass wool, and rock wool for the different climatic zones. According to the results of the study, the heat losses from pipes in the 4th generation DHS network are decreased between 38.19% and 33.33% from the warmest climate zone to the coldest climate zone according to the 3rd generation. Energy savings, reduction of CO2 emissions, payback periods and optimum insulation thickness values of supply and return pipes in the network are respectively changed between 7.80–98.86 $/m, 39.61–322.32 kg CO2/year, 0.028–0.38 years and 0.025–0.0105 m depending on various fuel types, insulation materials, nominal size pipes, climatic zones and all generation types.

Keywords: District heating network, LTDH network, reduction of CO2 emisisons, life-cycle cost analysis (LCCA), optimum insulation thickness

Introduction

Used to cover space heating and domestic hot water needs, district heating systems (DHS) transfer the heat produced in a plant to the buildings in a campus or region. 1 Components determined DHS are summarized as heat transfer fluid, heat transfer energy and energy sources used. In the systems low pressured vapour, hot water and superheated water are preferred as heat transfer fluids. Energy sources for the systems are arranged fossil fuels, nuclear power, waste heat, cogeneration heat, solar thermal energy, soil source heat pumps and biomass. 2 District heating systems, a century historical background, are separated into four generations depending on supply temperatures, fluid types and energy efficiency as shown Fig.1. 1 The systems are provided solutions for the increasing energy problems in high-population cities such as remediation of air quality because of reducing CO2 emissions, increasing renewable energy sources share, and reducing energy export owing to control of energy demands. 3 The advantages of DHS can be sorted as high efficiency in heat production; fuel used diversity and low interaction with the environment. 4

Figure 1.

Figure 1.

Classification of district heating system.

Shortly, the fall in energy consumption and heat demand in buildings is expected because of increasing energy efficiency precautions. The first investment cost, operation cost and total energy cost go up depending on increasing heat loss in DHS's distribution network. Thus there is a need decreasing of heat losses from pipes in the network. Heat loss from the network consists of 5–20% of transfer energy, and the loss is higher than the other losses in the heating system. Heat losses from the network depend on many factors such as outdoor conditions, insulation of pipes and length of the distribution network.16 The installation of district heating (DH) systems constitutes an advantage in terms of total emission, and pollutant concentration (NOx, CO, PM). The authors presented that air quality is also improved and health externalities are reduced with the installation of a DH system compared to autonomous residential boilers in previous studies. 7 Because of the low operating temperatures, 4th generation district heating systems (low-temperature district heating systems), LTDH has an important potential in decreasing the heat losses from the networks. The decrease in the network's temperatures is caused positive effects in terms of energy efficiency. When the temperatures of the heat networks are decreased, the heat losses from the pipes in networks are reduced. This can create energy savings at a crucial amount. For example, in case the supply and return temperatures are reduced to 60°C/30°C from 80°C/40°C, the decrease in heat losses from the network is estimated at 30%. As heat sources such as geothermal energy, heat pumps and solar heating can be used in these systems, heat generation efficiency is increased. 8 Moreover, low heat losses are caused to lower temperature fluctuations and lower flow velocity is necessitated. For it causes a decrease in the pressure drop, pump energy demand falls. 6 But, though lower supply temperatures are enough to reach convenient room temperatures, these are the biggest problem in providing domestic hot water. Supply water temperature should be ensured that it does not fall under 60°C to prevent the reproduction and proliferation of legionella bacteria in the central domestic hot water systems. 9 This situation is caused to bigger energy consumption and higher heat losses from pipes in the distribution network in the demand the domestic hot water. 10

Exergy is the maximum amount of work that can be done by the system depending on the ambient temperature. Exergy analysis is a method that can be used to increase energy production and conversion. Energy analysis allows for calculating the heat losses, but it does not provide the knowledge on how to convert energy. Because thermodynamics's second law determines that the part that can not be converted into useful work of all system's energy input, exergy analysis must be used with together energy analysis. 11 Exergy analysis is determined the losses and irreversibilities from the network and all system components in the district heating systems. The analysis presents the solutions to decrease irreversibility or exergy loss and to optimise the components and all system's performance depending on the type, location and size of the decrease in the work potential. In other words, the determination of where possible improvements in the system can be made is facilitated thanks to the exergy method as the locations and sizes of exergy losses are identified.1213

Energy consumption for space heating can be decreased significantly by using suitable insulation material because of decreasing fossil fuel consumption and pollution effect on the environment. Even in well-insulated buildings energy consumption and emissions can be rather decreased by insulating heating pipes. Especially, district heating systems, industry and chemical proses plants have confused and expensive pipe configurations. Un-insulation supply and return pipes of the heating system are important sources of waste energy. Insulation application of pipe systems for energy savings not only decreases heat losses from the pipes but also reduces environmental pollution due to fuel savings. Thermal insulation material used is an effective method for thermal impact protection in the buildings and pipes. For this reason, the selection of suitable insulation material and determination of optimum insulation thickness is quite essential.1415 Suitable insulation usage on pipes network in the district heating system is one of the effective ways for energy savings. The insulation decreases fuel consumption and undesirable carbon emissions from fossil fuel combustion in the system. 16 The insulation material thickness must be preferred considering the thermal conductivity and cost of the insulation material with the average outdoor temperature of the region. The insulation thickness not only increases energy savings but also contributes to the decrease of environmental pollution. However, the insulation thickness supplied with no heat losses is neither practical nor economical. Thus, a balance point should be determined between the insulation material cost with energy savings obtained, and this point is shown as the optimum insulation thickness.1520

Literature review

There are many studies related to distribution networks in the district heating system. Flores et al. 6 conducted a techno-economic comparison between networks with conventional DH and LTDH (100-40°C/43-60°). As the results of this study, decreasing the return water temperature is increased energy efficiency in LTDH systems, and pump power is decreased with lower energy demand and lower return water temperature. Furthermore, when the return water temperature falls by 10°C, heat losses of the distribution network are decreased by 6.7% and fell 23% of total pump energy. Gong and Werner 21 mapped flow diagrams of energy and exergy throughout the 2014 year of the district heating system in Sweden. Besides, they visualized the most efficient networks and investigated the use of renewable energy sources in district heating systems in Sweden. Li and Svendsen 13 analysed the energy and exergy of a hypothetical LTDH system's network (55/25°C) consisting of 30 buildings and compared the system's performance with MTDH systems (80/40°C). The total length of the network and annual heat demand are respectively calculated as 1.1 km and 187 kWh/m. Torio and Schmidt 22 investigated as a case study a small district heating system (95°C) in Kassel city in Germany. They presented the results of the energy and exergy analyses of the system. In the study, the strategies were derived for increasing the performance of the district heating systems based on the waste heat. According to the results of the study, in case the supply temperature of the system falls from 95°C to 57.7°C, the exergy efficiency of the system is raised from %32% to %39.3. Yang and Svendsen 23 analysed to determine the performance of an ultra low-temperature district heating system (ULTDH) in Denmark in terms of energy, exergy and economics based on data taken from the system in the study. The performance of the system was compared with medium and low-temperature district heating systems. According to the results of the analysis, low-temperature district heating systems (LTDH) have the highest energy and exergy efficiency. Ultra low-temperature district heating system (ULTDH) shows better performance in terms of energy, exergy and economics because of lower heat loss from the networks according to medium low-temperature district heating systems (MTDH). Baldvinsson and Nakata 24 investigated the energy and exergy performance of the low-temperature district heating system (60/30°C) located in Tohoku in North Japan. They concluded the low-temperature district heating system was not suitable for non-residential buildings in high places in North Japan. Comakli et al. 25 investigated the energy and exergy losses of heat distribution networks consisting of 11988 m length and 65–250 mm nominal size pipes of Ataturk University. The heat loss of the district heating network pipes was found as 8.62%. As a result of the study, the insulation material thickness is the most effective factor because of decreasing heat losses from the pipes. In case the insulation thickness of 20 cm uses instead of 8 cm on the pipes, the heat losses from the pipes are decreased by 25%. Keçebaş et al. 17 calculated the optimum insulation thickness, energy savings and payback periods of pipes used district heating network existed Afyonkarahisar Province in Turkey for five different nominal sizes of pipes and four fuel types during 10 years of economic life. In the study, an optimum model was developed based on Life Cycle Cost Analysis by (P1-P2) method. Rockwool was considered an insulation material and the network consisted of a network of 50–200 mm nominal size pipes. According to the results of the study, the optimum insulation thickness, energy savings and payback period were shown a change respectively between 0.085–0.228 m, 10.041 $/m-175.171 $/m and 0.442–0.808 years depending on different fuel types and pipe diameters. Rosti et al. 26 developed a methodology related to the determination of optimum insulation thickness by first investment cost of insulation and payback period for all climatic zones in Iran because of its economic and ecological importance. In the study, the optimization was carried out by using the Life Cycle Cost Analysis method with a numeric solution. Kayfeci 16 determined that significant energy savings can be obtained by insulating pipe networks and the great number of heat losses stem from the network of heat losses in the district heating system. In the study, the optimum insulation thickness, energy savings, annual operation cost and payback period were calculated by using the Life Cycle Cost Analysis method for different nominal pipe sizes, various insulation materials and heating degree days (HDD). The five different insulation materials were selected as XPS, EPS, foamboard, fibreglass and rock wool and natural gas was used as fuel. In the result of the study, the optimum insulation thickness was shown a change between 0.048–0.134 m; while energy-saving and payback periods were found respectively between 10.84 $/m-49.78 $/m and 0.74–1.29 years, and the best selection of insulation material was concluded to be fibreglass. Zhang et al. 20 calculated the optimum insulation thickness, energy savings and payback period of direct-buried pipes using a district heating network for various pipe diameters, fuel types and different soil deepness for Xion Province in China by using the Life Cycle Cost Analysis method in this study. According to the results of the study, the optimum insulation thickness, energy savings and payback period were respectively changed between 0.060–0.121 m, 36.395 $/m-194.682 $/m and 0.445–1.691 years.

In this study, energy and exergy are analysed the networks of all generations of district heating systems. The pipes such as supply-return pipes, hot water and circulation pipes into the network such as supply-return pipes, hot water and circulation pipes are investigated based on energy, exergy, economic and environmental. Energy and exergy losses from the pipes in the networks are modelled depending on the soil's deepness. The LTDH system is analysed compared to the other generations in terms of energy and exergy efficiency as a case study. Furthermore, the optimum analysis is included for the pipes in networks to obtain fuel savings and decrease energy and exergy losses. Optimum insulation thicknesses, energy savings, reduction of CO2 emissions, first investment costs and payback periods of the pipes in the network of all generation district heating systems are investigated by using the Life Cycle Cost Analysis method for fuel types like natural gas, fuel oil and coal. Optimum insulation thicknesses are calculated for different nominal sizes of pipes (Ø20mm-Ø150 mm) and various insulation materials such as glass wool, and rock wool for the different climatic zones.

The novelty of this study mainly includes the following points:

  • All generation district heating networks have been investigated based on energy, exergy and economics.

  • Energy and exergy losses from the pipes in the networks are modelled depending on the soil's deepness. In the literature, many studies related to the optimum insulation thickness developed a methodology for heat losses from a pipe surrounded by outside air. Besides, optimum insulation thickness has been examined in all climatic zones big range of the heating degrees days.

  • An LTDH system has been analysed as a case study and compared to the other generations.

Methodology

Heat losses from the pipes in the network

In the district heating system, the heat generated in the boilers is transferred by using hot fluid through a closed-loop network to the buildings on the campus. Space heating and domestic hot water demands of the buildings are covered with the heat transferred. In such a system, hot fluid is pumped inside the pipes at a constant low velocity under steady-state flow through networks to the buildings. Therefore, the pipes should be first handled as the major source of heat losses. Temperature changes in pipes from hot fluid to the surrounding environment (soil for buried pipes) are primarily effective in the assessment of insulation material and heat losses from pipes. Pressure drops and molecular diffusion are neglected in the study. To calculate heat losses from the pipes in the canals under soil per unit length, a resistance model is used shown in Fig.2.

Figure 2.

Figure 2.

A sectional view of the canal and the resistance model.

Insulation material resistance;

Ri=12×π×ki×In(r2r1) (1)

Canal resistance;

rc=xcp2×π (2)
Rc=12×π×kc×In(rc+tctc) (3)

The convection resistance of the air in the canal;

Ras=12×π×ha×ri (4)

The air convection coefficient can be found by the following formula. 27

ha=kaD×NuD (5)

To calculate the local Nusselt number at constant temperature and around a cylinder was proposed by Churchill the following formula. 28

NuD=[0.6+0.387×RaD1/6[(1+(0.559/Pr9/16))]8/27]2 (6)

Soil resistance;

Rs=12×π×ks×In[xcrc×(1+1(Dt/xc)2)] (7)

Heat losses from the pipes in the canals per unit length can be calculated in the following formula. 27

Q˙PIPES=[TwTaRi+Ras+Rc+Rs] (8)

Heating Degree Day (HDD) is a unit for measuring how much of a 24-h period is cold and explain the severity of the cold at a given time (day, month, year) taking into account the outside environment and room temperature. If the average daily temperature is above 15° C, heating is unnecessary. The heating cost is directly proportional to the annual HDD.

Annual heat loss from the pipes using HDD term is also can be calculated as follows 29 :

Q˙PIPES=86400×[HDDRi+Ras+Rc+Rs] (9)

Exergy analysis of the network

The exergy balance equation of the district heating system's all components is given with the following formula. The flow diagram related to the system is shown in Fig. 2.

E˙fuel+E˙air+E˙electric=(EsupplyE˙return)water+(E˙fg+E˙surface+E˙pumps+E˙buildings+E˙pipes)loss+IT (10)

Exergy loss from pipes in the canals and pumps can be calculated in the following formulas 27 ( Figure 3).

E˙pipes=Q˙pipes×(1TaTw) (11)
E˙pumps=W˙pumps×(TaTw) (12)

Figure 3.

Figure 3.

The schematic presentation of the flows in the district heating system.

Electric exergy input to the system is equal to the electric energy used to work the pumps.

E˙electric=W˙pumps (13)

Optimization of pipes in the network

There are many methods of economic analysis to assess whether an investment is economical. In this study, the Life Cycle Cost Analysis and P1-P2 method, which is one of the economic analysis methods, was preferred for calculating the optimum insulation thickness. The life cycle cost analysis, which is used to estimate the total cost of the project, includes the initial investment cost of the project, operating expenses, maintenance-repair cost and recycling costs. In other words, it covers a long period from the beginning of the project to the end of the usage period. In addition, the periodic maintenance costs of the investment are calculated. In P1-P2 method, economic analysis is carried out by taking into account the economic parameters such as interest and inflation rates, and fuel and insulation material prices. P1 is the present value factor, which considers the impact of interest rates and inflation rates on the cost of heat loss in the future life cycle. P2 considers the additional investment costs during the life cycle, including pipeline maintenance and resale at the end of the life cycle. 30

Annual fuel consumption corresponding to heat losses from the pipes,

V˙pl=V˙f×Q˙PIPESQ˙f×ηs (14)

annual total fuel energy consumed by the heating system,

Q˙f=Vfx˙xHu (15)

and annual fuel consumption cost corresponding to heat losses from the pipes can be calculated with these formulas.

Cfl=Vplx˙xCf (16)

The volume and cost of insulation material,

Vi=π×(r22r12)×L (17)
Cins=VixCi (18)

energy savings can be calculated as follows:

Q˙es=Q˙uninsQ˙ins=[(1Ra+Rc+Rs)(1Ri+Ra+Rc+Rs)]×(TwTa) (19)

To determine the optimum insulation thickness, a lifetime cost analysis is required. While calculating the total cost, the lifetime (N) and the current value factor (P1) are evaluated together. The current value factor varies depending on the interest rate (i), inflation rate (d) and the lifetime of the insulation (N). The net energy saving amount with insulation is obtained by using the P1-P2 method. The present value factor is calculated from the following equations, depending on whether the interest and inflation rates are equal.1417

P1=1(di)×[1(1+i1+d)N]ifid (20)
P1=N(1+i)ifi=d (21)
P2=1+P1×Cmrv(1+d)N (22)

P2 can be taken as 1 if the maintenance and operation cost is zero. The total cost and annual net energy savings can be calculated by using the following formulas.2630

Ctot=P1×Cfl+P2xCins (23)
Es=P1×C˙fP2×Cins (24)

where Cfˈis the difference between the energy cost for the uninsulated and insulated pipes. The payback period can be evaluated as the self-compensation process of the effect of insulation thickness cost on energy savings. The payback period of the insulation material varies depending on the properties such as the insulation material, the type of fuel and the annual interest rate. The payback period can be calculated for the situations i  =  d or i≠d and P2  =  1 inserted to Eq.24 and by set equal to zero the equation.16,17,29

Annual emission savings,

ESCO2=(V˙pluninsV˙plins)×Hu×EF (25)

where EF is the emission factor of CO2 and takes different values depending on the fuel types of the heating system. 31

System description

Space heating and hot water need of buildings in the 18. The Regional Directorate of Highways's campus, located in Kars city of Turkey is satisfied by the 4th generation low-temperature heating system (LTDH). Kars is the coldest city, situated in the fourth climatic zone of Turkey. The annual fuel consumption of the district heating system is an average of 809,793.50 Nm3. Supply and return water temperatures of the district heating network are varied between 60°C and 50°C. The heat distribution network's length is 1470 m, and the sizes of the nominal pipes in the canals are varied from Ø20 mm to Ø150 mm. The layout plan of the district heating network is given in Fig. 4. As seen in the figure, the heat provided by burning fuel in boilers in Heat Plant is transferred to the buildings on the campus by the network.

Figure 4.

Figure 4.

The location plan of the district heating network.

While the space heating demand of the buildings is covered by supply and return water pipes in the canals, domestic hot water demand is covered by hot water and circulation pipes in the canals or network. This LTDH system analysed is compared to the other generations in terms of energy and exergy efficiency as a case study.

To investigate of optimum insulation thicknesses of the pipes in the canals are based on Life Cycle Cost Analysis and the P1-P2 method. The optimum insulation thicknesses, payback periods and energy savings, and reduction of CO2 emissions are calculated for the different nominal size pipes (Ø20mm-Ø150 mm), different climatic zones and fuel types like natural gas, fuel oil and coal, all generations of the district heating system's network, insulation materials such as glass wool and rock wool. In the optimum analysis calculations, MATLAB Optimization Toolbox is used.

Results

Energy and exergy analysis of the LTDH network as a case study

In the district heating system's network, there are different diameters of heating pipes (supply and return pipes) between Ø25-Ø150 mm and the total length of 1760 m in the network consists of the canals. Besides while a total 1500 m length of hot water pipes has existed the different diameters of Ø25-Ø110 mm, there is a total 1498 m length of the circulation pipes (Ø20-Ø76 mm nominal size). Nominal sizes, insulation thicknesses and length of the pipes in the canals are shown in Table 1 at the current situation. The total length of the pipes in the canals is 4758 m, and the supply and return water temperatures of the network are varied between 60° and 50°C. At the under soil the deepness of the canal is average 1.2 m. In the system's network in four different sizes, the canals exist, and the values of the canal resistance are changed to 0.4403 from 0.3763.

Table 1.

Annual heat and exergy losses of the pipes in the network.

Pipe diameter mm Insulation thickness mm DT mm Pipes length m Heat loss kJ/year Exergy loss kJ/year
Supply and return pipes 150 60 270 240 1.74  ×  108 1.59  ×  108
125 50 204 204 1.47  ×  108 1.33  ×  108
100 50 140 140 9.11  ×  107 8.30  ×  107
80 40 147 147 9.45  ×  107 8.61  ×  107
65 40 249 249 1.46  ×  108 1.33  ×  108
50 30 244 244 1.42  ×  108 1.30  ×  108
40 30 86 86 4.55  ×  107 4.15  ×  107
32 30 268 268 1.29  ×  108 1.17  ×  108
25 30 119 119 5.17  ×  107 4.71  ×  107
20 25 63 63 2.66  ×  107 2.42  ×  107
Total 1760  ×  2 1.05  ×  109 9.54  ×  108
Hot water pipes 110 50 210 380 7.75  ×  107 6.67  ×  107
90 50 190 541 1.01  ×  108 8.69  ×  107
76 40 156 60 1.13  ×  107 9.75  ×  106
63 40 143 230 4.0  ×  107 3.44  ×  107
50 30 110 48 8.41  ×  106 7.23  ×  106
40 30 100 50 7.30 x106 6.84  ×  106
32 30 92 18 2.38 x106 2.24  ×  106
25 30 85 173 2.06 x107 1.94  ×  107
Total 1500  ×  1 2.50 x108 2.33  ×  108
Circulation pipes 76 40 156 452 8.54  ×  107 7.34  ×  107
63 40 143 467 8.12  ×  107 6.98  ×  107
50 30 110 60 1.05  ×  107 9.04  ×  106
40 30 100 41 6.52  ×  106 5.60  ×  106
32 30 92 237 3.43  ×  107 2.94  ×  107
25 30 85 165 2.15  ×  107 1.85  ×  107
20 25 70 76 9.64  ×  106 8.28  ×  106
Total 1498  ×  1 2.49  ×  108 2.14  ×  108

Supply and return heating pipes, hot water pipes and circulation pipes in heat canals are insulated with glass wool to decrease heat losses. The thermal conductivity coefficient of insulation material is taken as k  =  0.035 W/m.K, and soil resistance values are found between 1.3781–1.4130. Parameters and values used in resistance calculations are shown in Table 2.

Table 2.

Results of the resistant model.

Parameter Value
Canal material Concrete
 kc 2.1 W/m.K
 Rc 0.376–0.441 W/m2.K
 tc 20 cm
Insulation material Glass wool
 ki 0.040 W/m.K
 Ri 2.3387–4.985 W/m2.K
Deepness of soil xc 1.2 m
 ks 2 W/m.K
 Rs 1.378–1.413 W/m.K
 ha 6.902–7.897 W/m2.K
 RaD 1.25  ×  106-7.18  ×  107
 NuD 20.48–69.05

Heat losses from all pipes in the district heating network are calculated as 50.41 kW, 33.68 kW of this loss stems from supply and return pipes and 16.72 kW of this loss from hot water and circulation pipes.

Considering all district heating systems annual heat loss value and heat loss ratio from all pipes in the network are found respectively as 1.57  ×  109 kJ and 5.97%. Similarly, exergy loss from all pipes in the district heating network is calculated as 45.07 kW, and 30.68 kW of this loss stems from supply and return pipes and 7.50 kW of this loss from hot water and 6.88 of this loss from circulation pipes.

Considering all-district heating systems annual exergy loss value and exergy loss ratio from all pipes in the network are found respectively as 1.40  ×  109 kJ and 4.90%. While 18 of the pumps with different sizes and capacities in the Heat Plant are used for space heating lines; 6 numbers of the pumps are used for hot water and circulation lines. The total power of the pumps is 3.37 kW and exergy loss from the pumps is 2.53 kW. Input exergy to the system is lost 0.27% from the pumps.

The supply and return water temperatures of the system were measured between 60°C and 50°C. Energy and exergy transferred to supply water from boilers are respectively figured out at 4292 kW and 157 kW. The exergy ratio transferred to supply water from the boilers is found as 17.07%.

Optimization of the pipes in the networks

To minimize the heat losses and fuel savings, the pipes should be investigated in terms of optimum insulation thickness. To calculate optimum insulation thicknesses, energy savings and payback periods of the pipes are used Life Cycle Cost Analysis and P1-P2 method.

Optimum insulation thicknesses are examined for different nominal sizes of pipes (Ø20mm-Ø150 mm) and various insulation materials such as glass wool, and rock wool for the different climatic zones and fuel types like natural gas, fuel oil and coal. Parameters and values used in the economic analysis are shown in Table 3.

Table 3.

Parameters used in the economic and environmental analysis.1318,28

Parameters Values
Heating degree-days (HDD) 1250–4250 °C days
Insulation material Glass wool Rock wool
Price, Ci 75 $/m3 95 $/m3
ki 0.040 W/m2.K 0.035 W/m2.K
Fuel Natural gas Coal Fuel-oil
Price, Cf 0.5022 $/m3 0.3929 $/m3 1.3202 $/m3
Hu 8250 kcal/m3 7007 kcal/kg 9875 kcal/kg
Emission factor of CO2 0.234 kg CO2/kWh 0.433 kg CO2/kWh 0.330 kg CO2/kWh
Efficiency of heating system 93% 65% 80%
Generations of DHS 1st generation 2nd generation 3rd generation 4th generation
Mean temperature of supply and return waters 125°C 110°C 80°C 55°C
Interest rate, i 10%
Inflation rate, d 11%
Lifetime, N 10 years

Change of insulation, fuel and total annual costs according to insulation thickness is shown in Fig. 5 for 3rd generation, natural gas, Ø125 mm nominal size pipe and rock wool material. As seen in the figure while the insulation cost increases depending on the increase of the insulation thickness, the fuel cost decreases due to the reduction of heat losses thanks to the insulation. The total cost curve decreases up to one point depending on the insulation thickness and then starts to increase. The insulation thickness corresponding to this point indicates the optimum insulation thickness.

Figure 5.

Figure 5.

Change of annual costs with different insulation thicknesses (3rd generation, natural gas, Ø125 mm nominal size pipe, rock wool material).

By the insulation application, heat losses from the pipes are reduced and fuel savings is provided. However, increasing the thickness of the insulation after the optimum insulation thickness not only increases the energy savings but also increases the cost of the insulation material.

In Fig. 6, the change in insulation thickness and annual energy savings are shown depending on the insulation material for the 4th generation, HDD  =  4250 ° C days, Ø80 mm nominal size pipe, natural gas. As seen in the figure, while the energy savings changes increase at the first values of the insulation thickness, the energy savings changes decrease in the further values.

Figure 6.

Figure 6.

Change of energy savings with different insulation thicknesses for insulation materials (4th generation, HDD  =  4250 °C days, Ø80 mm nominal size pipe, natural gas).

Rock wool insulation material provides higher energy savings compared to glass wool due to its low thermal conductivity coefficient. In the energy savings and insulation thickness figure, the insulation thickness corresponding to the highest energy savings value gives the optimum insulation thickness. In Fig. 7, annual energy savings is given with increasing insulation thickness depending on fuel types for 2nd generation, HDD  =  3750 °C days, Ø125 mm nominal size pipe, rock wool material.

Figure 7.

Figure 7.

Change of energy savings with different insulation thickness for fuel types (2nd generation, HDD  =  3750 °C days, Ø125 mm nominal size pipe, rock wool material).

The highest energy saving is achieved in the fuel-oil fuel type and the lowest energy savings values are in the natural gas fuel type. Thermal insulation becomes more important in inefficient fuels such as fuel oil and coal than natural gas.

Annual energy savings values for supply and return pipes, hot water and circulation pipes are respectively changed between 7.80–98.86 $/m, 2.05–12.20 $/m depending on fuel types, generations of the district heating systems, insulation materials and climatic zones.

In Table 4, energy and emission savings and payback periods change ranges of the supply and return pipes are shown for the 4th generation according to the insulation materials and fuel types. The payback period that shows the value of energy savings achieved by applying insulation to the pipes in the heat network is equal to the initial investment cost and varies according to many variables such as fuel type, climate zone, generation of district heating system and insulation material. Emission reduction of CO2 has twice the value for the coal-fired heating systems compared to the other fuels because of maximum fuel savings. In Fig. 8, the payback period is shown depending on the insulation thickness and fuel types for the 3rd generation, HDD  =  2250°C days, Ø100 mm nominal size pipe, glass wool material. While the highest payback period is found in natural gas heating systems, the lowest payback period is obtained from coal-fired heating systems.

Table 4.

Optimum insulation thickness, energy and emission savings, payback periods change ranges of the supply and return pipes depending on the insulation materials and fuel types.

Supply and return pipes
4th generation, HDD  =  2750 °C days
Optimum thickness m Energy savings $/m.year Emission reduction kg CO2/year Payback period years
Nominal size RW-GW RW-GW RW-GW RW-GW
Ø125 Natural gas 0.035-0.040 12.55-12.64 63.73-64.16 0.28-0.31
Fuel oil 0.061-0.069 34.98-34.60 114.07-110.47 0.21-0.20
Coal 0.037-0.041 17.40-17.39 177.53-177.43 0.27-0.28
Ø100 Natural gas 0.034-0.040 12.48-11.88 63.35-60.32 0.25-0.24
Fuel oil 0.061-0.068 34.61-33.16 112.85-108.27 0.17-0.18
Coal 0.036-0.040 16.48-16.47 168.06-167.92 0.22-0.23
Ø80 Natural gas 0.034-0.039 12.14-11.52 61.66-58.48 0.22-0.19
Fuel oil 0.060-0.066 33.96-32.42 110.70-108.12 0.15-0.14
Coal 0.035-0.039 16.04-16.12 163.58-164.42 0.17-0.19
Ø65 Natural gas 0.033-0.037 11.49-11.42 58.37-58.02 0.20-0.17
Fuel oil 0.060-0.063 33.96-32.56 110.70-106.16 0.13-0.12
Coal 0.034-0.036 15.85-15.09 161.73-155.85 0.15-0.17
Ø50 Natural gas 0.030-0.035 10.46-10.82 53.11-54.96 0.18-0.17
Fuel oil 0.056-0.061 32.55-33.22 106.12-105.93 0.13-0.11
Coal 0.033-0.035 15.15-15.28 154.47-153.92 0.15-0.16
Natural gas 0.028-0.033 9.92-10.34 50.37-52.48 0.15-0.14
Ø40 Fuel oil 0.053-0.056 31.77-30.09 103.58-98.10 0.10-0.09
Coal 0.030-0.032 14.53-14.72 148.17-150.07 0.13-0.12
Natural gas 0.025-0.030 9.38-9.84 47.68-49.98 0.12-0.10
Ø32 Fuel oil 0.050-0.053 30.75-29.03 100.29-94.65 0.08-0.07
Coal 0.028-0.030 13.88-12.99 141.61-132.58 0.10-0.11

Figure 8.

Figure 8.

Effect of insulation thickness on the payback period for fuel types (3rd generation, HDD  =  2250 °C days, Ø100 mm nominal size pipe, glass wool material).

In Fig. 9, the payback period is given depending on the insulation thickness and the type of insulation material for the 4th generation, HDD  =  4250°C days, Ø80 mm of nominal size pipe, natural gas. Although glass wool insulation material provides lower energy savings than rock wool, it is lower than rock wool in terms of payback period due to its lower cost As can be seen from the figure, the payback period is increased by increasing the insulation thickness. Payback period values for supply and return pipes, hot water and circulation pipes are respectively changed between 0.028–0.38 years, 0.063–0.47 years depending on fuel types, generations of the district heating systems, insulation materials and climatic zones.

Figure 9.

Figure 9.

Effect of insulation thickness on the payback period for insulation material (4th generation, HDD  =  4250°C days, Ø80 mm nominal size pipe, natural gas).

Optimum insulation thicknesses, annual energy saving values, payback periods, annual fuel consumption values of the heating system pipes, hot water and circulation pipes of different diameters have been investigated depending on fuel type, climatic zones, insulation material and generation type of the district heating system.

In Fig. 10, optimum insulation thickness values of pipes of different diameters in the heating system are given for different insulation materials and different types of fuel for 3rd generation and HDD  =  2750°C days. While optimum insulation thicknesses are the lowest in natural gas, it is the highest in fuel oil. Also, optimum insulation thicknesses are lower for rock wool insulation material than glass wool material.

Figure 10.

Figure 10.

Optimum insulation thickness of the insulation material and fuel types for nominal size pipes (for 3rd generation and HDD  =  2750°C days).

Optimum insulation thickness values for supply and return pipes, hot water and circulation pipes are respectively changed between 0.025–0.105 m, 0.020–0.050 m depending on fuel types, generations of the district heating systems, different insulation materials and climatic zones.

Comparison of all generation networks

District heating systems, a century historical background, have been separated into four groups (generations) depending on supply temperatures, fluid types and energy efficiency. In this study, energy and exergy losses from the pipes in the district heating network and optimum thickness, energy savings and payback periods of the pipes are examined in terms of these four generations.

According to the results of the study energy and exergy losses from pipes in the district heating network rise with an increase in heating degree days (HDD) value. Depending on the supply and return water temperatures in the network, energy and exergy losses from pipes decrease to 4th generation from 1st generation district heating system. The heat losses from pipes in the 4th generation DHS network decreased between 38.19% and 33.33% from the warmest climate zone to the coldest climate zone according to the 3rd generation. In addition, the heat losses from pipes in the 4th generation DHS network decreased between 64.01% and 58.40% from the warmest climate zone to the coldest climate zone according to 1st generation.

In Fig. 11, the change of the exergy factor is shown for 150 mm of nominal size pipe depending on the different climatic zones and generations. The exergy factor means the ratio of heat losses and exergy losses. As can be seen from the figure, the biggest change in the exergy factor is observed in the 4th generation DHS network. The highest exergy factor values for the constant HDD value are reached in the 1st generation.

Figure 11.

Figure 11.

Exergy factor of the generation types for various HDD (for Ø150 mm pipe and glass wool material).

Optimum insulation thickness values of supply and return pipes, hot water and circulation pipes in the network are investigated for all DHS generations, fuel types, different climatic zones and different diameters of pipes.

In Fig. 12, optimum insulation thicknesses of supply and return pipes by different nominal sizes in the network are shown depending on fuel and generation types for rock wool insulation material and HDD  =  2750°C days. As seen in the figure, while the optimum insulation thickness value reaches the highest value in fuel oil, it is the lowest value in natural gas because of being the most efficient fuel type. For this reason, natural gas-fired district heating systems are cheaper than the other fuel types in terms of initial investment cost The new generation, 4th generation district heating systems, also have the lowest optimum insulation thickness values due to low network pipe temperatures. In Fig. 13, changes in energy savings are given related to insulation thickness and generation types for Ø80 mm pipe, glass wool material and HDD  =  1250°C days. The highest energy savings values are found in fuel oil-fired systems and 1st generation. This result shows how important to insulate the pipes in the network of the existing traditional district heating systems at suitable insulation thicknesses. While annual energy savings, emission reduction of CO2, payback periods and optimum insulation thickness values are respectively changed between 27.65–98.86 $/m, 140.41–322.32 kg CO2/year, 0.028-0.21 years and 0.040 −0.105 m for supply and return pipes in the 1st generation network from the warmest zone to the coldest climate zone; changes of these values are respectively changed for supply and return pipes in the 4th generation network are respectively observed between 7.80-34.80 $/m, 39.61–113.44 kg CO2/year, 0.066–0.38 years and 0.025–0.080 m depending on various fuel types, insulation materials, nominal size pipes and climatic zones. Annual energy savings, emission reduction of CO2, payback periods and optimum insulation thickness values of hot water and circulation pipes in the network are respectively calculated between 2.05–12.20 $/m, 10.43–39.79 kg CO2/year, 0.063–0.47 years and 0.020–0.050 m. These values vary depending on the type of fuel, insulation material and various nominal size pipes, but not depending on the type of generation network. Optimum insulation thickness, energy savings and payback periods change ranges of the supply and return pipes (nominal size of Ø150 mm) for all generations are given in the Appendix tables.

Figure 12.

Figure 12.

Optimum insulation thickness of the generation types for all fuel types (for rock wool material and HDD  =  2750°C days).

Figure 13.

Figure 13.

Change of energy savings related to insulation thickness (HDD  =  1250°C days for Ø80 mm pipe and glass wool material).

Conclusions

In this study, energy and exergy losses from the pipes in the networks are modelled depending on the soil's deepness. The LTDH system is analysed compared to the other generations in terms of energy and exergy efficiency as a case study. Optimum insulation thicknesses, energy savings, reduction of CO2 emissions, first investment costs and payback periods of the pipes in the network of all generation district heating systems are investigated by using the Life Cycle Cost Analysis method for fuel types like natural gas, fuel oil and coal various insulation materials such as glass wool, rock wool for the different climatic zones. Besides the results were obtained compatible and confirmed with the scientific studies presented in the reference part. Based on the analysis results the major conclusions can be drawn:

  1. The highest energy saving is achieved in the fuel-oil fuel type and the lowest energy savings values are in the natural gas fuel type. Thermal insulation becomes more important in inefficient fuels such as fuel oil and coal than natural gas. While the highest payback period is found in natural gas heating systems, the lowest payback period is obtained from coal-fired heating systems. Although glass wool insulation material provides lower energy savings than rock wool, it is lower than rock wool in terms of payback period due to its lower cost While optimum insulation thicknesses are the lowest in natural gas fuel, it is the highest in fuel oil fuel type. Also, optimum insulation thicknesses are lower for rock wool insulation material than glass wool material.

  2. Depending on the supply and return water temperatures in the network, energy and exergy losses from pipes decrease to 4th generation from 1st generation district heating system. The heat losses from pipes in the 4th generation DHS network decreased between 38.19% and 33.33% from the warmest climate zone to the coldest climate zone according to the 3rd generation. Besides the heat losses from pipes in the 4th generation DHS network decreased between 64.01% and 58.40% from the warmest climate zone to the coldest climate zone according to 1st generation. The biggest change in exergy factor is observed in the 4th generation DHS network. The highest exergy factor values for the constant HDD value are reached in the 1st generation.

  3. Optimum insulation thickness values for supply and return pipes, hot water and circulation pipes are respectively changed between 0.025–0.105 m, 0.020–0.050 m depending on fuel types, generations of the district heating systems, different insulation materials and climatic zones. While optimum insulation thickness value reaches the highest value in fuel oil, it is the lowest value in natural gas because of being the most efficient fuel type. For this reason, natural gas-fired district heating systems are cheaper than the other fuel types in terms of initial investment cost The new generation, 4th generation district heating systems, also have the lowest optimum insulation thickness values due to low network pipe temperatures.

  4. Annual energy savings, payback periods and optimum insulation thickness values of supply and return pipes in the network are respectively changed between 7.80–98.86 $ / m, 0.028–0.38 and 0.025–0.0105 m depending on various fuel types, insulation materials, nominal size pipes, climatic zone. The highest energy savings values are found in fuel oil-fired systems and 1st generation. This result shows how important to insulate the pipes in the network of the existing traditional district heating systems at suitable insulation thickness and all generation types.

  5. Finally, emission reduction of CO2 has twice the value for the coal-fired heating systems compared to the other fuels because of maximum fuel savings.

Glossary

Nomenclature

Cf

Fuel cost, $/m3

Cfl

Annual fuel consumption cost occurred heat losses from pipes, $/year

Ci

Cost of Insulation material per unit volume, $/m3

Cins

Insulation cost, $

Cm

Maintenance and operation cost, $

Ctot

Total cost, $

d

Inflation rate,%

Dt

Diameter of insulation pipe, m

Es

Energy savings, $/m

ESCO2

Emission savins of CO2, kg CO2/year

EF

Emission factor of CO2, kg CO2/kWh

h

Heat convection coefficient, W/m2.K

Hu

Lower heating value of the fuel, kJ/m3

i

Interest rate,%

IT

Total irreversibility

k

Thermal conductivity coefficient, W/m.K

L

Length, m

N

Lifetime, years

Nu

Nusselt number

Pr

Prandtl number

rv

Ratio of resale value to first cost

R

Thermal resistance, m2.K/W

Ra

Rayleigh number

Q

Heat transfer rate, kJ/s

Qf

Annual fuel energy consumed from the heating system, kJ/year

tc

Canal thickness, m

T

Temperature, °C

Tb

Base temperature, °C

Tsa

Solar-air temperature, °C

ύ

Volumetric flow rate, m3/s

V

Volume, m3

Vf

Annual fuel consumption of heating system, m3/year

Vpl

Annual fuel consumption occurred heat losses from pipes, m3/year

xcp

Perimeter of canal, m

xc

Dept of canal,m

Greek symbols

ηs

Efficiency of heating system, %

Subscripts

a

Air

i, ins

Insulation

un-ins

Uninsulation

c

Canal

C

Cost

D

Diameter

f

Fuel

fg

Flue gas

HDD

Heating degree-days

LCCA

Life cycle cost analysis

p

Pipe

pl

Loss from pipe

r1

Inner radius

r2

Outer radius

s

Soil

Tsa

Solar-air temperature

w

Water

Appendix

Table A1.

Optimum insulation thickness, energy savings and payback periods change ranges of the supply and return pipes (Ø150 mm) for 1st generation.

Supply and return pipes (Ø150 mm)
 1st generation
Optimum thickness m Energy savings $/m.year Emission reduction kg CO2/year Payback period years
RW-GW RW-GW RW-GW RW-GW
HDD  =  1250 °C days Natural gas 0.052-0.054 29.29-27.65 148.73-410.41 0.26-0.21
Fuel oil 0.092-0.095 85.34-81.35 278.22-265.23 0.17-0.14
Coal 0.055-0.072 38.68-39.74 393.48-405.32 0.19-0.22
HDD  =  2250 °C days Natural gas 0.054-0.058 29.93-28.25 151.96-143.45 0.25-0.21
Fuel oil 0.094-0.098 87.19-83.12 284.29-271.02 0.17-0.14
Coal 0.055-0.074 39.52-40.60 403.13-414.13 0.19-0.21
HDD  =  2750 °C days Natural gas 0.056-0.060 30.59-28.88 155.34-146.62 0.25-0.21
Fuel oil 0.96-0.100 89.12-84.96 290.55-277.01 0.17-0.14
Coal 0.057-0.075 40.39-41.50 412.09-423.31 0.19-0.21
HDD  =  3750 °C days Natural gas 0.057-0.061 31.26-29.50 158.70-149.80 0.24-0.20
Fuel oil 0.98-0.102 91.05-86.81 296.85-283.03 0.16-0.14
Coal 0.059-0.078 41.27-42.40 421.02-432.45 0.18-0.20
HDD  =  4250 °C days Natural gas 0.060-0.063 31.81-30.03 161.53-152.46 0.24-0.20
Fuel oil 0.100-0.105 92.68-98.86 302.13-322.32 0.16-0.13
Coal 0.060-0.080 42.01-43.15 428.49-440.18 0.18-0.20

RW(Rock wool), GW(Glass wool).

Table A2.

Optimum insulation thickness, energy savings and payback periods change ranges of the supply and return pipes (Ø150 mm) for 2nd generation.

Supply and return pipes (Ø150 mm)
 2nd generation
Optimum thickness m Energy savings $/m.year Emission reduction kg CO2/year Payback period years
RW-GW RW-GW RW-GW RW-GW
HDD  =  1250 °C days Natural gas 0.046-0.054 23.91-23.89 121.40-121.33 0.25-0.24
Fuel oil 0.080-0.094 70.01-70.31 228.25-229.23 0.16-0.16
Coal 0.050-0.071 33.43-34.34 341.01-350.30 0.22-0.25
HDD  =  2250 °C days Natural gas 0.048-0.057 24.51-24.49 124.46-124.39 0.24-0.24
Fuel oil 0.080-0.095 71.76-72.08 233.97-234.98 0.15-0.16
Coal 0.051-0.074 34.27-35.21 349.57-359.08 0.22-0.25
HDD  =  2750 °C days Natural gas 0.050-0.060 25.14-25.12 127.61-127.57 0.24-0.24
Fuel oil 0.085-0.097 73.60-73.92 239.95-241.01 0.15-0.16
Coal 0.053-0.075 35.15-36.11 358.50-368.26 0.21-0.24
HDD  =  3750 °C days Natural gas 0.054-0.060 25.76-25.75 130.81-130.74 0.23-0.23
Fuel oil 0.096-0.099 79.47-75.76 259.09-247.04 0.14-0.15
Coal 0.055-0.077 36.02-37.00 367.43-377.44 0.21-0.23
HDD  =  4250 °C days Natural gas 0.055-0.060 26.28-26.27 133.48-133.41 0.23-0.22
Fuel oil 0.098-0.100 81.09-77.31 264.37-252.04 0.18-0.15
Coal 0.057-0.078 36.75-37.76 374.93-385.17 0.20-0.23

Table A3.

Optimum insulation thickness, energy savings and payback periods change ranges of the supply and return pipes (Ø150 mm) for 3rd generation.

Supply and return pipes (Ø150 mm)
 3rd generation
Optimum thickness m Energy savings $/m.year Emission reduction kg CO2/year Payback period years
RW-GW RW-GW RW-GW RW-GW
HDD  =  1250 °C days Natural gas 0.042-0.051 15.17-15.42 77.01-78.31 0.30-0.31
Fuel oil 0.079-0.080 48.02-45.58 156.56-148.62 0.23-0.19
Coal 0.045-0.053 21.65-21.64 220.89-220.75 0.27-0.27
HDD  =  2250 °C days Natural gas 0.041-0.050 15.73-15.52 79.84-81.18 0.29-0.30
Fuel oil 0.080-0.080 49.78-47.26 162.28-154.84 0.22-0.18
Coal 0.045-0.055 22.45-22.44 228.98-228.83 0.27-0.26
HDD  =  2750 °C days Natural gas 0.042-0.053 16.30-16.58 82.78-84.17 0.28-0.28
Fuel oil 0.081-0.083 51.61-48.99 168.26-159.73 0.21-0.18
Coal 0.048-0.056 23.28-23.26 237.40-237.29 0.26-0.26
HDD  =  3750 °C days Natural gas 0.043-0.054 16.88-17.16 85.73-87.14 0.27-0.27
Fuel oil 0.082-0.086 53.44-50.73 174.25-165.41 0.21-0.17
Coal 0.050-0.057 24.10-24.09 245.85-245.70 0.25-0.25
HDD  =  4250 °C days Natural gas 0.046-0.054 17.37-17.66 88.20-89.67 0.26-0.27
Fuel oil 0.085-0.087 54.98-52.20 179.26-170.18 0.20-0.17
Coal 0.050-0.060 24.80-24.78 252.92-252.77 0.24-0.24

Table A4.

Optimum insulation thickness, energy savings and payback periods change ranges of the supply and return pipes (Ø150 mm) for 4th generation.

Supply and return pipes (Ø150 mm)
 4th generation
Optimum thickness m Energy savings $/m.year Emission reduction kg CO2/year Payback period years
RW-GW RW-GW RW-GW RW-GW
HDD  =  1250 °C days Natural gas 0.030-0.035 11.65-11.68 42.51-39.59 0.38-0.36
Fuel oil 0.055-0.062 32.05-31.68 84.48-84.44 0.23-0.23
Coal 0.037-0.039 16.04-15.43 126.35-118.26 0.36-0.31
HDD  =  2250 °C days Natural gas 0.033-0.037 12.34-12.38 45.04-47.22 0.36-0.38
Fuel oil 0.060-0.067 33.95-33.56 94.77-89.45 0.26-0.22
Coal 0.037-0.040 16.99-16.94 133.82-125.29 0.34-0.29
HDD  =  2750 °C days Natural gas 0.035-0.040 13.06-13.10 47.68-49.98 0.34-0.36
Fuel oil 0.063-0.072 35.93-35.52 100.29-94.65 0.24-0.20
Coal 0.038-0.042 17.98-17.93 141.61-132.58 0.33-0.28
HDD  =  3750 °C days Natural gas 0.036-0.043 13.78-13.82 50.28-52.74 0.35-0.34
Fuel oil 0.065-0.076 37.91-37.46 105.81-99.86 0.23-0.19
Coal 0.039-0.045 18.97-18.92 149.41-151.88 0.31-0.32
HDD  =  4250 °C days Natural gas 0.038-0.048 14.38-14.43 52.50-55.03 0.31-0.33
Fuel oil 0.068-0.080 40.43-39.12 110.42-113.44 0.22-0.25
Coal 0.040-0.050 19.80-19.74 155.97-158.56 0.29-0.30

Footnotes

The author(s) declared no potential conflicts of interest with respect to the research, authorship, and/or publication of this article.

Funding: The author(s) received no financial support for the research, authorship, and/or publication of this article.

References

  • 1.Mazhar AR, Liu S, Shukla A. A state of art review on the district heating systems. Renewable Sustainable Energy Rev 2018; 96: 420–439. [Google Scholar]
  • 2.Lake A, Rezaie B, Beyerlein S. Review of district heating and cooling systems for a sustainable future. Renewable Sustainable Energy Rev 2017; 67: 417–425. [Google Scholar]
  • 3.Sayegh MA, Danielewicz J, Nannou Tet al. et al. Trends of European research and development in district heating technologies. Renewable Sustainable Energy Rev 2017; 68: 1183–1192. [Google Scholar]
  • 4.Jie P, Tian Z, Yuan Set al. et al. Modeling the dynamic characteristics of a district heating network. Energy 2012; 39: 126–134. [Google Scholar]
  • 5.del Hoyo Arce I, Lopez SH, Perez SLet al. et al. Models for fast modelling of district heating and cooling networks. Renewable Sustainable Energy Rev 2018; 82: 1863–1873. [Google Scholar]
  • 6.Castro Flores JF, Lacarriere B, Chiu JNWet al. et al. Assessing the techno-economic impact of low-temperature subnets in conventional district heating networks. Energy Procedia 2017; 116: 260–272. [Google Scholar]
  • 7.Ravina M, Panepinto D, Zanetti M. District heating networks: an inter-comparison of environmental indicators. Environmental Science and Pollution Research 2021; 28: 33809–33827. [DOI] [PubMed] [Google Scholar]
  • 8.Østergaard D, Svendsen S. Space heating with ultra-low-temperature district heating-a case study of four single-family houses from the 1980s. Energy Procedia 2017; 116: 226–235. [Google Scholar]
  • 9.Köfinger M, Basciotti D, Schmidt RRet al. et al. Low temperature district heating in Austria: energetic, ecologic and economic comparison of four case studies. Energy 2016; 110: 95–104. [Google Scholar]
  • 10.Yang X, Li H, Svendsen S. Energy, economy and exergy evaluations of the solutions for supplying domestic hot water from low-temperature district heating in Denmark. Energy Convers Manage 2016; 122: 142–152. [Google Scholar]
  • 11.Terehovics E, Veidenbergs I, Blumberga D. Exergy analysis for district heating network. Energy Procedia 2017; 113: 189–193. [Google Scholar]
  • 12.Gong M, Werner S. Exergy analysis of network temperature levels in Swedish and Danish district heating systems. Renewable Energy 2015; 84: 106–113. [Google Scholar]
  • 13.Li H, Svendsen S. Energy and exergy analysis of low temperature district heating network. Energy 2012; 45: 237–246. [Google Scholar]
  • 14.Başoğul Y, Demircan C, Keçebaş A. Determination of optimum insulation thickness for environmental impact reduction of pipe insulation. Appl Therm Eng 2016; 101: 121–130. [Google Scholar]
  • 15.Keçebaş A. Determination of insulation thickness by means of exergy analysis in pipe insulation. Energy Convers Manage 2012; 58: 76–83. [Google Scholar]
  • 16.Kayfeci M. Determination of energy saving and optimum insulation thicknesses of the heating piping systems for different insulation materials. Energy Build 2014; 69: 278–284. [Google Scholar]
  • 17.Keçebaş A, Alkan MA, Bayhan M. Thermo-economic analysis of pipe insulation for district heating piping systems. Appl Therm Eng 2011; 31: 3929–3937. [Google Scholar]
  • 18.Keçebaş A. Determination of optimum insulation thickness in pipe for exergetic life cycle assessment. Energy Convers Manage 2015; 105: 826–835. [Google Scholar]
  • 19.Ilhan U. Optimum insulation thickness for pipes in district heating systems. Journal of Mechanical and Energy Engineering 2018; 42: 225–232. [Google Scholar]
  • 20.Zhang L, Wang Z, Yang Xet al. et al. Thermo-economic analysis for directly-buried pipes insulation of district heating piping systems. Energy Procedia 2017; 105: 3369–3376. [Google Scholar]
  • 21.Gong M, Werner S. Mapping energy and exergy flows of district heating in Sweden. Energy Procedia 2017; 116: 119–127. [Google Scholar]
  • 22.Torio H, Schmidt D. Development of system concepts for improving the performance of a waste heat district heating network with exergy analysis. Energy Build 2010; 42: 1601–1609. [Google Scholar]
  • 23.Yang X, Svendsen S. Ultra-low temperature district heating system with central heat pump and local boosters for low-heat-density area: analyses on a real case in Denmark. Energy 2018; 159: 243–251. [Google Scholar]
  • 24.Baldvinsson I, Nakata T. A feasibility and performance assessment of a low temperature district heating system-A North Japanese case study. Energy 2016; 95: 155–174. [Google Scholar]
  • 25.Comakli K, Yuksel B, Comakli O. Evaluation of energy and exergy losses in district heating network. Appl Therm Eng 2004; 24: 1009–1017. [Google Scholar]
  • 26.Rosti B, Omidvar A, Monghasemi N. Optimal insulation thickness of common classic and modern exterior walls in different climate zones of Iran. Journal of Building Engineering 2020; 27: 100954. [Google Scholar]
  • 27.Comakli K. Energy and exergy analysis of district heating plant of Ataturk University, Ph. D. Thesis, Ataturk University, Erzurum, Turkey, 2003.
  • 28.Cengel YA. Heat and mass transfer. third ed. New York, USA: McGraw-Hill, 2006. [Google Scholar]
  • 29.Ertürk M. Optimum insulation thicknesses of pipes with respect to different insulation materials, fuels and climate zones in Turkey. Energy 2016; 113: 991–1003. [Google Scholar]
  • 30.Zhang T, Li A, Hari Qet al. et al. Economic thickness and life cycle cost analysis of insulating layer for the urban district steam heating pipe. Case Studies in Thermal Engineering 2022; 34: 102058. [Google Scholar]
  • 31.Energy Performance Regulations in Buildings, Ankara, Turkey, 2011.

Articles from Science Progress are provided here courtesy of SAGE Publications