Abstract
This paper introduces a novel and improved double-resistor damped double-tuned passive power filter (DR-DDTF), designed using multi-objective optimization algorithms to mitigate harmonics and increase the hosting capacity of distribution systems with distributed energy resources. Although four different topologies of single-resistor damped double-tuned filters (DDTFs) have been studied before in the literature, the effectiveness of two different DR-DDTF configurations has not been examined. This work redresses this gap by demonstrating that via comprehensive simulations on two power systems, DR-DDTF provides better harmonic suppression and resonance mitigation than single-resistor alternatives. When it comes to optimizing the DR-DDTF for maximum hosting capacity and minimum system active power losses, the multi-objective artificial hummingbird outperformed six other algorithms in the benchmark. To allow for higher penetration of distributed generation without requiring grid upgrades, this newly developed harmonic mitigation filter provides a good alternative.
1. Introduction
The integration of renewable energy sources into electric grids has gained significant attention in the past few years because of their environmental benefits and the potential to decrease dependence on fossil fuels [1]. However, the integration of these sources presents various challenges, including the hosting capacity (HC) limitations of the distribution systems. HC refers to the maximum limit of renewable energy that can be safely and reliably accommodated within the existing grid infrastructure. As the penetration of renewable energy sources increases, it becomes crucial to enhance the HC to fully utilize the potential of these clean energy resources [2].
Several factors inherently limit the HC of a distribution system. For instance, the power system’s voltage stability, thermal limits, and protection schemes impose constraints on the maximum limit of renewable energy that can be integrated. Additionally, the presence of harmonics, originating from various sources such as the grid, nonlinear loads, and inverter-based renewable distributed generation, further complicates the HC enhancement process. Harmonics introduce voltage and current distortions, leading to increased losses, reduced equipment lifespan, and decreased system reliability [3].
One promising approach to enhance the HC of harmonically distorted distribution systems is through harmonic mitigation techniques. Harmonic mitigation aims to minimize the adverse effects of harmonics, thereby increasing the system’s capacity to accommodate renewable energy sources. Various mitigation techniques have been proposed, including active power filters, passive filters, and hybrid filter configurations. Among these approaches, passive power filters have gained attention due to their simplicity, low cost, and ease of implementation [4]. According to [5], the cost of passive filters is significantly less than active and hybrid filters for the same rating, especially in high power applications. Shunt-passive and series-passive filters are used to mitigate AC and DC drives harmonics rather than active or hybrid filters due to their performance and cost effectiveness in [6].
Passive power filters employ passive components, such as inductors and capacitors, to attenuate harmonics and improve power quality. These filters can suppress a wide range of harmonic frequencies, making them suitable for HC enhancement. Passive power filter design and optimization for harmonic mitigation within the context of HC enhancement is an ongoing research field in line with the literature [7,8].
The aim of this paper is to propose a novel approach for HC enhancement in harmonically distorted distribution systems using a double-resistor damped double-tuned passive power filter (DR-DDTF). The primary novelty lies in the design of this type of passive power filter, as the damped double-tuned passive power filters (DDTF) have six different schemes presented before in the literature. The four single-resistor schemes of this filter have been investigated before in literature, but the two double-resistors have not been designed, analyzed, or investigated. One more contribution of this paper is the utilization of different multi-objective optimization techniques in the design process to maximize HC and minimize system active power losses simultaneously. By employing six multi-objective optimization algorithms–multi-objective particle swarm optimization (MOPSO), multi-objective slime mould optimization (MOSMA), multi-objective thermal exchange optimization (MOTEO), non-dominated sorting whale optimization (NSWO), non-dominated sorting Harris Hawks optimization (NSHHO), and multi-objective artificial hummingbird algorithm (MOAHA), the performance of the proposed filter is thoroughly evaluated.
To assess the effectiveness of the proposed method, two power systems are considered, each characterized by a different set of harmonic signatures. The first system comprises 30 harmonic signatures, while the second system includes 49 harmonic signatures. The harmonic sources in these systems include the grid, nonlinear loads, and inverter-based renewable distributed generation. Comparative analysis is conducted to evaluate the performance of the proposed filter design using the different optimization algorithms.
The paper is organized as follows: The literature review is presented in Section 2. The system formulation including: the system components, the filter design equations, different power quality indices, the problem formulation, and the used optimization algorithms are presented in Section 3. are presented in Section 4. The results and discussions are presented in Section 4. The conclusions and future work are presented in Section 5.
2. Literature review
Mirbagheri S. et al. [9] and Ismael S. et al. [2,10] provided an in-depth definition and explanation of HC, emphasizing its role in accommodating high levels of distributed generation while maintaining grid stability and power quality. The authors also stressed the importance of HC as a critical parameter for integrating renewable energy into the grid and enhancing energy sustainability. The authors in [9] stated that the goal of many researchers was -for so long- the determination of the optimal DG sizing and sitting while neglecting an important practical factor that can make these studies hard to implement. This factor is the highest amount of generation that the distribution grid can accommodate while adhering to grid constraints. It is a crucial performance indicator that must be taken into account when planning and operating the grid. The authors in [2,10] stated that the HC concept was presented to solve the conflict between the DGs owners/investors and the power system operators, as the owners tend to install more and more DGs to maximize their profits, while the system operators are disturbed by the issues and the adverse effects of the excessive DG penetration in the networks.
Researchers like Yuan J. et al. [11] and Qamar N. et al. [12] have investigated the factors that influence HC in power systems. Their study highlighted the impact of voltage limits, thermal limits, and power flow constraints on the HC of distribution networks. Understanding these determinants is crucial for devising effective strategies to improve HC. The authors in [11] determined the maximum HC of photovoltaic (PV) systems in electric grids considering some performance and operating power network indices like the optimal power flow, the network standard voltage limits, the network thermal and ampacity limits, and the power factor limits. The authors in [12] stated the aforementioned performance and operating constraints as in [11] and extended the limiting factors of the HC to voltage imbalance, voltage flicker and harmonics.
HC determination can be achieved using different techniques. According to [2], The assessment of HC is subject to uncertainty, primarily due to the unknown locations of DGs, their various unit ratings, their intermittent nature due to the changing weather conditions, and load profile variations. According to [12], there are various HC determination approaches such as the deterministic approach, the stochastic approach, the time series approach, the worst-case hour approach, and the stochastic time series approach. The main difference between these approaches is the consideration of uncertainty factors, the intermittent operation of DGs, and other practical uncertainty and limiting factors.
To mitigate these risks, it is essential to carefully design and manage the penetration of RES or distributed generation (DG) into the electrical power system, or in other words, increase the system HC. In the literature, many solutions have been recommended to achieve this goal. These solutions can include implementing advanced control and monitoring systems to manage the power flow dynamically and utilizing energy storage solutions to even out fluctuations in renewable energy output. In addition, using effective harmonic mitigation strategies can help address the issue of harmonic distortion and ensure that the system remains stable and efficient. DG active power reduction, the system reactive power control, and the use of an on-load tap changer (OLTC) are also some of the suggested solutions. Several solutions can be used together to increase HC while maintaining system indices within their standard limits in more complex systems [2,4,10,13–18]. The HC issues, some of the suggested HC enhancement techniques, and the main paper focus are depicted in Fig 1.
Fig 1. HC issues and their suggested solutions from the literature.
Recently, there has been a significant amount of research dedicated to enhancing the HC of distribution networks as an alternative to costly upgrades. This section delves into various methodologies and approaches discussed across a range of literature, all aimed at increasing the HC of electrical networks. The authors in [13] introduced a technique for optimally selecting conductors utilizing the salp swarm optimization (SSO) algorithm. The primary aim was to simultaneously lower the combined annual investment expenses and energy costs, all while adhering to system voltage limits and the thermal/mechanical capacities of the conductors. Despite the outlined strategy having some practical challenges, the same article introduced an alternative method for reinforcing feeders, ultimately resulting in improved HC values.
Fig 2 illustrates harmonic-constrained HC (HCHC) enhancement using a general system performance index, where the objective is to increase the HC while maintaining the index within its acceptable operating range.
Fig 2. HC enhancement illustration using a general system performance.
In the context of [12], the primary aim was to effectively manage the dynamic fluctuations in voltage within DG-integrated systems. To enhance voltage regulation in both stable and changing conditions, an adaptable controller is suggested for STATCOMs used within low-voltage (LV) grids. This controller contributes to the enhancement of hosting capacity, encompassing both static and dynamic scenarios. In [19], a method involving risk assessment was employed to evaluate the hosting capacity of active distribution networks (ADNs), considering various uncertainties of DGs. A probabilistic approach is utilized to account for system uncertainty. Additionally, a range of techniques has been devised to augment network hosting capacity, including demand response in smart grids, as highlighted in [19,20]. The authors in [21] presented an optimal placement of PV systems, while the authors in [22] introduced two reactive power control techniques, namely cos(φ) and Q(V), along with prediction-based active power control involving DGs. These control strategies are tested on an existing distribution grid featuring a single medium voltage (MV) feeder and numerous LV grids. The results indicated that employing the Q(V) strategy can boost the hosting capacity of an area by up to 15% compared to the cos(φ) strategy. The authors in [23] contributed by a voltage control strategy for active transformers, which, according to existing literature, shifts the concern from overvoltage in the network to the ratings of grid components when installing PV systems. However, it was important to note that these techniques are not widely applicable but are dependent on grid topology and specifications and possess certain limitations.
According to [12], the HC enhancement techniques in the literature can be categorized into the following different categories: OLTC transformer employment, curtailment of dispersed generation resources, optimized PV deployment, active power control, reactive power control, network reconfiguration, the use of battery energy storage system, and harmonic mitigation.
Focusing on harmonic mitigation as an HC enhancement technique, harmonics give rise to issues of diminished power quality and energy wastage within the system. Hence, it becomes essential to implement appropriate protective measures against harmonic disturbances prior to embarking on the grid design process. The authors in [4] employed a C-type passive power filter to mitigate harmonics in a distribution system increasing its HC while achieving satisfactory values of different harmonic indices according to the IEEE 519 standards. In [24], the HC evaluation of a two-bus industrial distribution system was carried out, taking harmonic restrictions into account. The research revealed a steep reduction in HC as nonlinearity of the load side increases. To alleviate these harmonics, a passive C-type filter was suggested. This solution not only maximizes HC but also delivers enhanced voltage regulation, improved power factors, and harmonics limitation, leading to an impressive 55.34% increase in HC. In [25], the authors introduced a comprehensive formula capable of determining HC at specific points in distribution and transmission systems affected by harmonic distortions. Applying this equation to an actual power system yielded a HC range of 37 MW for the worst-case scenario and 160 MW for the best-case scenario. Using an alternating current-based optimal power flow method, the authors of [26] addressed harmonics by focusing on voltage and thermal restrictions, which were the main factors limiting HC. In order to determine allowable limitations for DG integration, the authors of [27] carefully aligned the method with acceptable harmonic analysis assumptions for different scenarios and created precise equations. Traditional radial distribution systems can benefit from this method, which is both technically and economically sound.
Among the previous solutions suggested in the literature, harmonic mitigation using power filters increases the HCHC of the system, improves its power factor (both displacement and distortion components), decreases the system active power losses, and improves other system indices such as: increasing the load voltage, and decreasing the source current. Passive power filters are cheaper and more suitable for high-voltage and high-power applications than active power filters [28]. Damped passive power filters are used to avoid harmonic resonance problems while improving the system power quality, as in [7,8].
Harmonic pollution and overloading of different system components are considered as power loss and power quality concerns in this study. They occur because of unplanned addition and sizing of DGs, the use of electronic-based loads, and the rapidly increasing installation of harmonic-injecting RES in electric systems.
Further, the MOAHA is used for maximizing the HCHC and minimizing system active power losses (PLOSS) of a harmonic-polluted electric distribution system. Utility-side voltage harmonics are included, as are current harmonics created by the nonlinear load and generated by the DGs.
A shunt-connected capacitor bank is used to investigate HC enhancement under sinusoidal conditions. A damped double-tuned filter (DDTF) is designed and connected parallel to the load to improve the system’s power quality. There are six schemes for this filter in the literature, four of them are single-resistor schemes, and two of them are double-resistor. Only the single-resistor schemes were designed, analyzed, and compared in the literature; however, one scheme (scheme B) was proven to be superior compared to the others [8]. This filter provides harmonic mitigation of the system, which improves power quality indices such as: voltage total harmonic distortion (THDV), current total demand distortion (TDDI), and individual harmonic voltage and current distortions (IHDV and IHDI) and corrects the true power factor (PF) of a combination of linear and nonlinear loads. The allowable levels of harmonic distortion are determined by following the IEEE 519 guidelines [29]. Limits on encouraged power factor, thermal capacity of transmission lines, and system voltage are all factors in Egypt’s electrical distribution code [30] that are met in the study.
3. System formulation
3.1. System description and parameters
The system consists of a utility grid (reduced to its Thevenin’s equivalent), a PV generator which is an inverter-based harmonic-generating DG source, a combination of linear and non-linear load, and the proposed passive power filter. All the system components are connected to the point of common coupling (PCC). The system is depicted in Fig 3.
Fig 3. The studied system.
Two test system parameters are used in this paper. The values of nonlinear load and PV generator IHDI, Grid-side IHDV are obtained from the literature to compare the results with those achieved in [4,29]. The first test system (TS1) contains 30 harmonic orders, while the second (TS2) contains 49 harmonic orders. For both systems, the non-linearity ratio (NLL), which is the ratio of the nonlinear load power to the total load power equals 25%. The parameters of TS1 are shown in Table 1.
Table 1. TS1 parameters.
| Parameter | Value |
|---|---|
| Base voltage (kV) | 13.8 |
| Base current (A) | 314 |
| Base Power (kVA) | 7500 |
| Frequency (Hz) | 50 |
| Rated load active power (p.u.) | 0.92 |
| Rated load reactive power (p.u.) | 0.39 |
| Thevenin’s resistance (Ω) | 0.0115 |
| Thevenin’s reactance (Ω) | 0.1154 |
The values of IHDI for the non-linear load (IHDINLL) and IHDV for the grid-side harmonics (IHDVS), also referred to as background voltage distortion for TS1, as well as their maximum limits (IHDI,MAX, IHDV,MAX) implied by IEEE 519 based on the system voltage and short-circuit capacity with the corresponding harmonic orders (h) are shown in Table 2. Also, the values of IHDI for the PV generator (IHDIPV) used in TS1 are shown in Table 3. The parameters of TS2 are shown in Table 4. The values of IHDINLL for TS2 and IHDI,MAX implied by IEEE 519 based on the system voltage and short-circuit capacity with the corresponding h are shown in Table 5. The values of IHDVS for TS2 and IHDVS,MAX implied by IEEE 519 based on the system voltage and short-circuit capacity with the corresponding h are shown in Table 6. The values of IHDIPV used in TS2 are shown in Table 7.
Table 2. Non-linear load’s individual harmonic currents and grid’s individual harmonic voltages as percentages of their fundamental values for TS1 and their maximum limits implied by IEEE 519.
| h | Non-linear load | Grid-side harmonics | ||
|---|---|---|---|---|
| IHDINLL (%) | IHDI,MAX (%) | IHDVS (%) | IHDV,MAX (%) | |
| 5 | 20.00 | 7.00 | 3.00 | 3.00 |
| 7 | 14.30 | 7.00 | 2.00 | 3.00 |
| 11 | 9.10 | 3.50 | 2.00 | 3.00 |
| 13 | 7.70 | 3.50 | 1.00 | 3.00 |
| 17 | 5.90 | 2.50 | 1.00 | 3.00 |
| 19 | 5.30 | 2.50 | 1.00 | 3.00 |
| 23 | 4.30 | 1.00 | 1.00 | 3.00 |
| 25 | 4.00 | 1.00 | 0.50 | 3.00 |
| 29 | 3.40 | 1.00 | 0.50 | 3.00 |
Table 3. The individual harmonic currents of the PV generator used in TS1 as a percentage of its fundamental current.
| h | IHDIPV (%) | h | IHDIPV (%) | h | IHDIPV (%) |
|---|---|---|---|---|---|
| 1 | 100 | 11 | 0.67 | 21 | 0.50 |
| 2 | 1.13 | 12 | 0.80 | 22 | 0.40 |
| 3 | 3.27 | 13 | 0.46 | 23 | 0.20 |
| 4 | 0.26 | 14 | 1.06 | 24 | 0.35 |
| 5 | 3.48 | 15 | 0.30 | 25 | 1.33 |
| 6 | 0.12 | 16 | 0.50 | 26 | 0.19 |
| 7 | 1.12 | 17 | 1.48 | 27 | 0.61 |
| 8 | 0.82 | 18 | 0.59 | 28 | 1.20 |
| 9 | 0.49 | 19 | 1.14 | 29 | 0.90 |
| 10 | 0.84 | 20 | 0.71 | 30 | 0.67 |
Table 4. TS2 parameters.
| Parameter | Value |
|---|---|
| Base voltage (kV) | 11 |
| Base current (A) | 525 |
| Base Power (kVA) | 10000 |
| Frequency (Hz) | 50 |
| Rated load active power (p.u.) | 0.72 |
| Rated load reactive power (p.u.) | 0.38 |
| Thevenin’s resistance (Ω) | 0.455 |
| Thevenin’s reactance (Ω) | 1.165 |
Table 5. Non-linear load’s individual harmonic currents as a percentage of its fundamental values for TS2.
| h | IHDINLL (%) | h | IHDINLL (%) | h | IHDINLL (%) |
|---|---|---|---|---|---|
| 3 | 15.00 | 19 | 5.30 | 35 | 2.43 |
| 5 | 12.00 | 21 | 4.74 | 37 | 2.21 |
| 7 | 11.00 | 23 | 4.32 | 39 | 2.06 |
| 9 | 8.05 | 25 | 4.01 | 41 | 1.88 |
| 11 | 7.15 | 27 | 3.79 | 43 | 1.64 |
| 13 | 6.42 | 29 | 3.40 | 45 | 1.47 |
| 15 | 5.87 | 31 | 2.86 | 47 | 1.35 |
| 17 | 5.44 | 33 | 2.62 | 49 | 1.26 |
Table 6. The grid’s harmonic voltages as percentages of their fundamental values for TS2 and their maximum limits implied by IEEE 519.
| h | IHDVS (%) | IHDV,MAX (%) | h | IHDVS (%) | IHDV,MAX (%) |
|---|---|---|---|---|---|
| h<7 | 2.00 | 3.00 | 25 ≤ h ≤ 35 | 0.50 | 3.00 |
| 7 ≤ h < 13 | 1.25 | 3.00 | 35 ≤ h < 45 | 0.25 | 3.00 |
| 13 ≤ h <25 | 0.80 | 3.00 | 45 ≤ h < 49 | 0.15 | 3.00 |
Table 7. The individual harmonic currents of the PV generator used in TS2 as a percentage of its fundamental current.
| h | IHDIPV (%) | h | IHDIPV (%) | h | IHDIPV (%) |
|---|---|---|---|---|---|
| 2 | 0.3281 | 18 | 0.4344 | 34 | 0.0642 |
| 3 | 3.9664 | 19 | 1.3261 | 35 | 0.2945 |
| 4 | 0.5835 | 20 | 0.4288 | 36 | 0.0884 |
| 5 | 3.7461 | 21 | 1.1262 | 37 | 0.2760 |
| 6 | 0.8764 | 22 | 0.4066 | 38 | 0.0670 |
| 7 | 2.7612 | 23 | 0.5980 | 39 | 0.2480 |
| 8 | 0.9513 | 24 | 0.2670 | 40 | 0.0360 |
| 9 | 2.4682 | 25 | 0.5322 | 41 | 0.2360 |
| 10 | 0.9814 | 26 | 0.2150 | 42 | 0.0240 |
| 11 | 1.9091 | 27 | 0.5030 | 43 | 0.2040 |
| 12 | 0.7603 | 28 | 0.1970 | 44 | 0.0170 |
| 13 | 1.8321 | 29 | 0.4850 | 45 | 0.1940 |
| 14 | 0.6713 | 30 | 0.1690 | 46 | 0.0090 |
| 15 | 1.6222 | 31 | 0.4240 | 47 | 0.1470 |
| 16 | 0.5524 | 32 | 0.1120 | 48 | 0.0351 |
| 17 | 1.4140 | 33 | 0.3970 | 49 | 0.1220 |
3.2. Filter design
The different DDTF schemes are shown in Fig 4. As mentioned earlier, there are six different DDTF schemes; four of them are single-resistor DDTF (SR-DDTF), and two are DR-DDTF. The DR-DDTFs have not been designed nor investigated in literature before. Hence, in this paper, DR-DDTFs are utilized as well as Scheme B as the best SR-DDTF according to [8]. The direct design equations of the undamped double-tuned filter (DTF) design equations were introduced in [29]. A comparison between the different design methodologies of this filter was conducted in [25].
Fig 4. DDTF schemes featuring Scheme (B) as the best SR-DDTF scheme.
According to [5], DDTFs should be designed using bi-level optimization, where the filter is designed as an undamped DTF first. Then, the lower-level objective function (OFL) minimizes the difference between the tuning frequencies of the DTF (ω1, ω2) and the frequencies at which the DDTF has the lowest impedance value (ωz1, ωz2). The higher-level objective function (OFH) is the system indices that need to be improved; in this case, the maximization of HCHC and the minimization of PLOSS simultaneously. Therefore, this problem is tackled using bi-level multi-objective optimization. The flowchart of this optimization problem is shown in Fig 5.
Fig 5. Bi-level multi-objective optimization problem flowchart.
The DTF parameters (L1,L2,C1,C2) can be obtained by the following equations:
| (1) |
| (2) |
| (3) |
| (4) |
| (5) |
| (6) |
where ωf is the fundamental angular frequency, ω1, and ω2 are the two tuning angular frequencies of the DTF, ωs is the tuning angular frequency of the series part of the DTF, ωp is the tuning angular frequency of the parallel part of the DTF, Qf is the reactive power of the filter in VARs, and V is the voltage of the PCC.
3.3. System performance indices
The distribution line’s current at h (ISh) can be given as follows:
| (7) |
where VSh is the hth source (slack-bus) voltage, VLh is the hth PCC voltage, and ZLh is the hth distribution line’s impedance which can be given as follows:
| (8) |
where RLh and XL are the real and imaginary parts of the line’s equivalent impedance at h and at the fundamental frequency, respectively.
The source current IS, the load or PCC voltage VL and the filter current If are obtained by the following equations:
| (9) |
| (10) |
| (11) |
where Ifh is the filter current at h and is expressed as:
| (12) |
The harmonic derating factor (HDF), which quantifies the overloading of transmission lines in harmonically distorted systems, can be expressed as:
| (13) |
PLOSS can be expressed as:
| (14) |
where Pline is the distribution line’s active power losses, and Pfilter is the filter’s active power losses that can be determined as follows:
| (15) |
The true load power factor (PF) and the displacement power factor (DPF) at PCC are formulated as:
| (16) |
| (17) |
where ϕh is the angle between and at h, VL1 is the fundamental-frequency load voltage, IS1 represents the fundamental-frequency source current, and ϕ1 is the angle between and .
The total harmonic distortion for the PCC voltage (THDV) and the total demand distortion for the source current (TDDI) are expressed, respectively, as follows:
| (18) |
| (19) |
where ILM represents the fundamental-frequency maximum load ampacity. The individual PCC voltage IHDVL and line current IHDIL harmonics can be obtained by:
| (20) |
| (21) |
Finally, HCHC can be calculated as follows:
| (22) |
where SPV is the apparent power rating of the PV generator, and SL rated is the apparent power rating of the load.
3.4. Problem formulation
3.4.1. Objective functions
For DDTF Scheme B, the OFL can be expressed as:
| (23) |
where ΔωZ1 = ωZ1−ω1, and ΔωZ2 = ωZ2−ω2. For both Schemes E and F, the OFL can be expressed as:
| (24) |
The OFH can be expressed as follows:
| (25) |
where ϕPV is the power angle of the PV generator. So, determining the optimal values of the SPV and ϕPV gives PPV and QPV, respectively, the PV generator’s active and reactive powers.
3.4.2. Constraints
The previous objective functions are subjected to the following constraints (Con):
| (26) |
where and are set to 95% and 105%, respectively.
| (27) |
where is the maximum distribution line ampacity.
| (28) |
where DPFmin and PFmin are set to 0.92, and DPFmax and PFmax are set to 1.
| (29) |
| (30) |
where the maximum limits of the individual and total voltage, and current harmonic distortion are implied by IEEE 519. THDVmax equals 5%, and TDDImax equals 8%.
| (31) |
3.5. Optimization algorithms
The recently developed multi-objective artificial hummingbird algorithm (MOAHA) is a bio-intelligence-based multi-objective optimization technique introduced in 2022 [31]. According to its designer, MOAHA has demonstrated superior performance over commonly used algorithms in the literature for multi-objective problems.
MOAHA takes inspiration from the foraging behaviors of hummingbirds in nature. During the optimization process, MOAHA mimics three key hummingbird foraging tactics: directed foraging towards known flower locations, territorial foraging in productive areas, and migration between habitats. Additionally, these foraging behaviors are designed to simulate three flight capabilities of hummingbirds: axial flight, diagonal flight, and omnidirectional maneuvering. MOAHA also employs a memory-based visitation table, modeling a hummingbird’s ability to remember productive flower locations using experience.
Its developers have validated MOAHA on various multi-objective benchmark functions and real-world engineering optimization problems, demonstrating its effectiveness [31,32]. The specific equations, flowchart, and implementation details are available in these references. Initially, MOAHA requires the pre-definition of four key parameters before optimizing an objective function: the maximum number of iterations/generations, number of populations, number of decision variables/problem dimensions, and archive size for storing non-dominated solutions.
After obtaining a Pareto-optimal front (POF) of solutions using MOAHA, a final selection step is incorporated by using a multi-criteria decision-making method called Technique for Order of Preference by Similarity to Ideal Solution (TOPSIS) [33]. This allows for the identification of a single best solution among the POF based on preference criteria. The incorporation of this intelligent selection method enhances MOAHA’s capabilities to provide both multi-objective exploration and focused recommendation abilities.
In summary, MOAHA provides a powerful swarm intelligence-based multi-objective optimizer that takes inspiration from hummingbirds evolved foraging behaviors and flight dynamics. Its performance and expandability by integrating intelligent solution recommendation methods highlights the promise of bio-inspired algorithms [34].
The obtained results from MOAHA are compared to those from five different multi-objective optimization algorithms, namely: the multi-objective particle swarm optimization algorithm (MOPSO) [35], the multi-objective slime mould algorithm (MOSMA) [36], the non-dominated sorting whale optimization algorithm (NSWOA) [37], the non-dominated sorting Harris hawks optimization algorithm (NSHHO) [38], and the multi-objective thermal exchange optimization algorithm (MOTEO) [39] in order to verify the effectiveness and superiority of this technique. The aforementioned methodology is better described by the flowchart in Fig 6.
Fig 6. The paper methodology flowchart.
As shown in Fig 6, Iter is the current iteration/generation number, hmax equals 30 for TS1 and 49 for TS2. The fundamental-frequency optimal power flow for the studied systems is performed using the Newton-Raphson technique to obtain system voltages and currents. Also, a harmonic power flow is carried out at each to get the corresponding harmonic system voltages and currents, and other power quality indices.
4. Results and discussions
This section is divided into two sub-sections: one for the results and discussions of TS1 and the other for TS2. For both systems, the optimization algorithms parameters are shown in Table 8.
Table 8. Optimization algorithms parameters.
| Optimization Algorithm Parameter | Value |
|---|---|
| Maximum number of iterations/ generations (Itermax) | 500 |
| Number of populations (Npop) | 500 |
| Total number of calculations | 250,000 |
4.1. TS1 results
The fundamental-frequency power flow was used to examine the power quality of the system’s base case and determine the amount of reactive power needed to increase the DPF to its highest value (close to unity). All harmonic signatures from the sources are ignored in this case, only non-linear harmonics are considered. A capacitor bank is connected at the PCC to improve the load PF. The capacitor bank is sized so that it supplies all the load reactive power. The simulation results of these cases are shown in Table 9.
Table 9. Simulation results of the base and the capacitor bank cases in the absence of sources harmonics for TS1.
| Parameter | Base Case | Capacitor Bank |
|---|---|---|
| Reactive Power (MVAR) | -- | 2.9250 |
| VL (p.u.) | 0.9484 | 0.8882 |
| PF (%) | 91.7991 | 91.9524 |
| DPF (%) | 92.0691 | 92.0691 |
| HDF (%) | 99.3240 | 99.2590 |
| PLOSS (p.u.) | 0.0376 | 0.1710 |
| TDDI (%) | 7.0627 | 7.4204 |
| THDV (%) | 3.2076 | 3.5362 |
| PPV (MW) | -- | 6.9000 |
| QPV (MVAR) | -- | 0.0000 |
| HC (%) | -- | -- |
In the study undertaken, a capacitor bank was employed to enhance the PF of the system, resulting in a near-unity PF without the addition of the inverter-based PV generator. However, when the PV generator was introduced into the system, its performance deteriorated, and several key performance metrics exhibited inferior results compared to the base case. The PV generator was added to the system solely for the purpose of supplying active power to the grid, without consuming or supplying reactive power. It should be noted that the analysis focused exclusively on the non-linear load harmonics, disregarding the harmonics from the grid and PV generator.
In the base case scenario, the power factor was found to be below 92%, falling short of the minimum threshold value specified for the PCC voltage (0.95 p.u.). Although the HC theoretically demonstrated a significant improvement, the power factor of the load did not meet the minimum system specifications (below 92%), and the PCC voltage dropped below both the 0.95 p.u. threshold and the corresponding value observed in the base case. Moreover, the presence of the capacitor bank resulted in increased PLOSS compared to the base case. Additionally, the THDV and the TDDI values worsened, albeit still within an acceptable range. Consequently, achieving this desired HC value proved unattainable. The findings of this study highlight the substantial influence that harmonics and power factor values can exert in limiting the penetration levels of DGs, particularly in systems where non-linear load harmonics are prevalent.
When shunt-connected capacitors are employed in distorted systems with harmonics, there is a potential risk of electrical harmonic resonance occurring between the capacitors and the system’s inductive components. This phenomenon can exacerbate the overall operating conditions, leading to adverse effects such as amplified harmonic levels, increased voltage distortion, and even equipment damage. Therefore, the need for effective harmonic mitigation strategies becomes paramount.
To address this challenge, the problem is revisited under conditions of harmonic pollution, considering all three sources of harmonics: the grid, the PV generator, and the non-linear load. By incorporating the harmonic content from all these sources, a comprehensive analysis can be conducted to evaluate the impact on the system performance. This approach enables a more accurate assessment of the harmonic distortion levels, power factor degradation, and voltage quality.
The inclusion of all three harmonics sources allows for a thorough understanding of the system’s behavior and aids in the development of appropriate mitigation techniques. By identifying the dominant harmonic frequencies and their interactions with the shunt-connected capacitors, effective measures can be implemented to suppress resonance and minimize the adverse effects of harmonic distortion. These measures may include the use of harmonic filters, passive or active damping techniques, or the adjustment of capacitor parameters to avoid resonance conditions. The simulation results of the base case, the capacitor bank, and the three DDTF schemes designed using MOAHA are shown in Table 10.
Table 10. Simulation results of the base case, the capacitor bank, and the three MOAHA-designed DDTF schemes for TS1 with the presence of all system harmonic signatures.
| Parameter | Base Case | Compensated System | |||
|---|---|---|---|---|---|
| Capacitor Bank | DDTF Scheme B | DDTF Scheme E | DDTF Scheme F | ||
| Reactive Power (MVAR) | -- | 2.9250 | 5.8616 | 5.6355 | 5.4156 |
| VL (p.u.) | 0.9484 | 0.8890 | 0.9957 | 0.9941 | 0.9933 |
| PF (%) | 91.7991 | 91.9501 | 92.0011 | 92.0030 | 92.8689 |
| HDF (%) | 99.3240 | 99.4560 | 99. 4718 | 99.4561 | 99.2076 |
| Pline (kW) | 282 | 1282 | 5.9915 | 10.5202 | 12.1086 |
| Pfilter (kW) | -- | -- | 14.3007 | 0.0005 | 0.0045 |
| PLOSS (kW) | 282 | 1282 | 20.2922 | 10.5207 | 12.1131 |
| TDDI (%) | 7.0627 | 6.3769 | 6.1757 | 7.6865 | 7.8223 |
| THDV (%) | 3.2076 | 5.4327 | 3.6600 | 3.4595 | 3.4106 |
| PPV (MW) | -- | 6.9000 | 5.1478 | 5.7919 | 5.6787 |
| QPV (MVAR) | -- | 0.0000 | 1.6871 | 1.8504 | 1.6644 |
| HCHC (%) | -- | -- | 72.2289 | 81.0709 | 78.9011 |
DDTF Scheme E is the best scheme that maximizes HC and minimizes PLOSS simultaneously for TS1. The results of Scheme B are better than what is reported in the literature. According to [4], the best HCHC for this system achieved using C-type passive power filter was found to be 69.86%. SR-DDTF scheme B achieves HCHC 72.23%, and the two DR-DDTF schemes achieve better values where the best value achieved by Scheme E is about 81.07%. The designed filters parameters for TS1 are shown in Table 11.
Table 11. The MOAHA-designed DDTFs parameters for TS1.
| Parameter | DDTF Scheme B | DDTF Scheme E | DDTF Scheme F |
|---|---|---|---|
| h 1 | 5.0339 | 2.9935 | 3.0034 |
| h 2 | 7.3309 | 5.8834 | 21.3034 |
| m p | 6.8710 | 4.7633 | 11.3722 |
| Rf (Ω) | 1.7171 | -- | -- |
| R1 (kΩ) | -- | 31.2107 | 51.1886 |
| R2 (kΩ) | -- | 75.3758 | 5.9393 |
| C1 (μF) | 754.949 | 746.1905 | 689.2059 |
| L1 (μH) | 465.2674 | 993.1815 | 123.5466 |
| C2 (μF) | 7197.5 | 1413.8379 | 55.9159 |
| L2 (μH) | 29.8181 | 315.8559 | 1401.1185 |
4.2. TS2 results
The base and the capacitor bank cases in the absence of source harmonics for TS2 are given in Table 12.
Table 12. Simulation results of the base and the capacitor bank cases in the absence of sources harmonics for TS2.
| Parameter | Base Case | Capacitor Bank |
|---|---|---|
| Reactive Power (MVAR) | -- | 3.8000 |
| VL (p.u.) | 0.95651 | 0.90744 |
| PF (%) | 88.1849 | 88.3415 |
| DPF (%) | 88.4385 | 88.4385 |
| HDF (%) | 99.5320 | 99.4920 |
| PLOSS (p.u.) | 0.024547 | 0.10872 |
| TDDI (%) | 5.8385 | 6.096 |
| THDV (%) | 2.7071 | 2.9479 |
| PPV (MW) | -- | 7.4888 |
| QPV (MVAR) | -- | 0.0000 |
| HC (%) | -- | -- |
For the base case, the PF is less than 92%. Trying to improve the system performance using capacitor bank, the PF value is still under 92%, and TDDI value increased compared to the base case due to the existence of the PV generator harmonics.
The simulation results of the base case, capacitor bank case, and the three different DDTF schemes (B, F, and E) designed using MOAHA are shown in Table 13. It can be noticed that in the base, and the capacitor bank cases, the VL, PF, and HDF values are less (worse) due to the existence of all system harmonics (grid and non-linear load harmonics are added here). The values of PLOSS, TDDI, and THDV are greater (worse) than the previous case. DDTF Scheme E gives the highest HC and the lowest PLOSS for TS2. The value in the capacitor case is greater than 5% which is the maximum limit implied by IEEE 519–2014. For the same system parameters, the highest HCHC value in the literature was 83.29% achieved by utilizing a hybrid active filtering technique in [40] compared to 76.0796% achieved by DR-DDTF scheme E.
Table 13. Simulation results of the base case, the capacitor bank, and the three MOAHA-designed DDTF schemes for TS2 with the presence of all system harmonic signatures.
| Parameter | Base Case | Compensated System | |||
|---|---|---|---|---|---|
| Capacitor Bank | DDTF Scheme B | DDTF Scheme E | DDTF Scheme F | ||
| Reactive Power (MVAR) | -- | 3.8000 | 5.5033 | 5.6939 | 5.5789 |
| VL (p.u.) | 0.9469 | 0.8835 | 0.9939 | 0.9967 | 0.9937 |
| PF (%) | 88.1362 | 88.4385 | 92.0322 | 93.7036 | 92.0226 |
| HDF (%) | 99.3630 | 99.5170 | 99.4584 | 99.4689 | 99.4427 |
| Pline (kW) | 378.61 | 1733.6 | 10.6533 | 3.2667 | 11.8420 |
| Pfilter (kW) | -- | -- | 10.6508 | 4.2636 | 4.4745 |
| PLOSS (kW) | 378.61 | 1733.6 | 21.3041 | 7.5303 | 16.3164 |
| TDDI (%) | 6.6486 | 6.081 | 7.6072 | 7.9998 | 7.9453 |
| THDV (%) | 5.4902 | 5.3683 | 3.4917 | 3.1787 | 3.4089 |
| PPV (MW) | -- | 7.4888 | 5.7334 | 5.8954 | 5.6496 |
| QPV (MVAR) | -- | 0.0000 | 1.8009 | 1.8964 | 1.8488 |
| HCHC (%) | -- | -- | 73.8272 | 76.0796 | 73.0277 |
MOAHA was utilized in [41] to design SR-DDTF (scheme B) using TS1 data and an HCHC value of 72.2% was achieved. The designed filters parameters for TS2 are shown in Table 14.
Table 14. The MOAHA-designed DDTFs parameters for TS2.
| Parameter | DDTF Scheme B | DDTF Scheme E | DDTF Scheme F |
|---|---|---|---|
| h 1 | 4.0106 | 3.5784 | 2.9803 |
| h 2 | 28.1139 | 48.6777 | 20.7403 |
| m p | 12.5613 | 15.5402 | 15.0016 |
| Rf (Ω) | 1.8273 | -- | -- |
| R1 (kΩ) | -- | 33.2724 | 3.6917 |
| R2 (kΩ) | -- | 5.5037 | 90.9565 |
| C1 (μF) | 758.6649 | 719.5288 | 767.9090 |
| L1 (μH) | 165.7546 | 112.0770 | 777.1757 |
| C2 (μF) | 107.5961 | 44.8610 | 66.1718 |
| L2 (μH) | 596.8126 | 935.2326 | 680.3839 |
The IHDIL for TS2 is depicted in Fig 7.
Fig 7. IHDIL values and the corresponding maximum limits for TS2.
The IHDVL for TS2 is depicted in Fig 8.
Fig 8. IHDVL values and the corresponding maximum limits for TS2.
The values of IHDIL and IHDVL are clearly within limits. A comparison between different DDTFs (Scheme E) designed using MOAHA, MOPSO, MOSMA, NSWOA, NSHHO, and MOTEO for TS2 is shown in Table 15. These results prove the superiority and effectiveness of MOAHA-designed DDTF Scheme E compared to the results obtained using the other algorithms.
Table 15. Comparison between system parameters with different DDTFs Scheme E designed using: MOAHA, MOPSO, MOSMA, NSWOA, NSHHO, MOTEO for TS2.
| Parameter | MOAHA | MOPSO | MOSMA | NSWOA | NSHHO | MOTEO |
|---|---|---|---|---|---|---|
| Reactive Power (MVAR) | 5.6939 | 5.5810 | 4.7134 | 5.0083 | 3.9510 | 4.5340 |
| VL (p.u.) | 0.9967 | 0.9936 | 0.9870 | 0.9929 | 0.9833 | 0.9951 |
| PF (%) | 93.7036 | 92.1612 | 97.7019 | 93.7037 | 98.3801 | 90.3298 |
| HDF (%) | 99.4689 | 99.1746 | 99.2319 | 99.1576 | 99.2208 | 99.1114 |
| Pline (kW) | 3.2667 | 12.2166 | 41.5231 | 15.4011 | 65.0720 | 10.3213 |
| Pfilter (kW) | 4.2636 | 2.5941 | 0.2727 | 0.1837 | 1.3849 | 0.3329 |
| PLOSS (kW) | 7.5303 | 14.8107 | 41.7958 | 15.5849 | 66.4570 | 10.6543 |
| TDDI (%) | 7.9998 | 7.9802 | 7.6466 | 7.9998 | 7.5773 | 8.1245 |
| THDV (%) | 3.1787 | 3.3818 | 3.9298 | 3.7826 | 4.6566 | 4.8165 |
| PPV (MW) | 5.8954 | 5.6221 | 4.1404 | 5.3991 | 3.3613 | 4.7749 |
| QPV (MVAR) | 1.8964 | 1.8441 | 1.0472 | 1.2475 | 0.3960 | 0.3461 |
| HCHC (%) | 76.0796 | 72.6880 | 52.4669 | 68.0752 | 41.5788 | 58.8140 |
The POF of the solutions obtained by MOAHA-designed DR-DDTF Scheme E for TS2 is shown in Fig 9.
Fig 9. The POF of the solutions for MOAHA-designed DR-DDTF Scheme E for TS2.
The best solution is to be chosen using TOPSIS, in which the two objectives are given equal weights in this study.
It is clear that MOTEO fails to satisfy the TDDI and PF constraints. The highest HCHC as well as the lowest PLOSS values are obtained by MOAHA.
5. Conclusions and future work
To sum up, the paper conclusions are discussed in the following bullets:
In this study, a novel design for the double-resistor damped double-tuned passive power filter (DR-DDTF) was proposed to enhance the hosting capacity while minimizing active power losses in two test systems (TS1 and TS2).
The performance of two DR-DDTF schemes (Schemes E and F) was compared with Scheme B, which was previously identified as the best single-resistor DDTF (SR-DDTF) in literature.
The results obtained from the simulations demonstrated that Scheme E outperformed the other schemes and proved to be the most efficient DR-DDTF for both TS1 and TS2. This scheme achieved a significant improvement in the hosting capacity while effectively reducing the active power losses while satisfying other system constraints for VL, PF, THDV, TDDI, HDF, IHDV, and IHDI.
These findings highlight the superiority of the proposed DR-DDTF design in comparison to the existing SR-DDTF schemes.
Furthermore, the filters were designed using a bi-level MOAHA. The optimization algorithm was compared to five other optimization techniques, including MOPSO, MOSMA, NSWOA, NSHHO, and MOTEO. The results indicated that MOAHA exhibited superior performance in terms of optimizing the objective functions and achieving the desired filter design.
Finally, this study presents a significant advancement in the design of passive power filters for enhancing hosting capacity and minimizing active power losses. The use of DR-DDTFs, particularly Scheme E, offers improved performance compared to the existing SR-DDTF scheme. Moreover, the successful application of the bi-level multi-objective artificial hummingbird optimization algorithm demonstrates its effectiveness in designing optimal damped double-tuned filter configurations.
Future work may include further investigations of DR-DDTF Schemes: Although Scheme E has shown superior performance in the tested scenarios, it is essential to explore the potential of other DR-DDTF schemes and evaluate their effectiveness in different system configurations and operating conditions. Comparative studies can shed light on the strengths and limitations of various DR-DDTF designs.
Further techno-economic analysis and assessment may be conducted to evaluate the performance of the proposed DR-DDTFs under uncertainties and variations in system parameters, load profiles, and renewable energy generation which may provide a more comprehensive understanding of their applicability and effectiveness in real-world scenarios.
Supporting information
(PDF)
Data Availability
All relevant data is within the manuscript and its supporting information files.
Funding Statement
Prince Sattam bin Abdulaziz University for funding this research work through the project number (PSAU/2023/01/25559) The funders had no role in study design, data collection and analysis, decision to publish, or preparation of the manuscript.
References
- 1.Ellithy H.H.; Hasanien H.M.; Alharbi M.; Sobhy M.A.; Taha A.M.; Attia M.A. Marine Predator Algorithm-Based Optimal PI Controllers for LVRT Capability Enhancement of Grid-Connected PV Systems. Biomimetics 2024, 9, 66, doi: 10.3390/biomimetics9020066 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 2.Ismael S.M.; Abdel Aleem S.H.E.; Abdelaziz A.Y.; Zobaa A.F. State-of-the-Art of Hosting Capacity in Modern Power Systems with Distributed Generation. Renew Energy 2019, 130, 1002–1020, doi: 10.1016/j.renene.2018.07.008 [DOI] [Google Scholar]
- 3.Xi Z.; Xiang Y.; Huang Y.; Yu B.; Weng L.; Tang C.; et al. Hosting Capability Assessment and Enhancement of Electric Vehicles in Electricity Distribution Networks. J Clean Prod 2023, 398, 136638, doi: 10.1016/j.jclepro.2023.136638 [DOI] [Google Scholar]
- 4.Ellamsy H.T.; Ibrahim A.M.; Ali Z.M.; Shady H. E., A.A. Multi-Objective Particle Swarm Optimization for Harmonic-Constrained Hosting Capacity Maximization and Power Loss Minimization in Distorted Distribution Systems. In Proceedings of the 2021 IEEE International Conference on Environment and Electrical Engineering and 2021 IEEE Industrial and Commercial Power Systems Europe (EEEIC / I&CPS Europe); IEEE, September 7 2021; pp. 1–6. [Google Scholar]
- 5.Dekka A.R.; Beig A.R.; Poshtan M. Comparison of Passive and Active Power Filters in Oil Drilling Rigs. In Proceedings of the 11th International Conference on Electrical Power Quality and Utilisation; IEEE, October 2011; pp. 1–6. [Google Scholar]
- 6.Aleem S.H. E.A. Design and Comparative Analysis of Shunt-Passive and Series-Passive for AC Drives-Based Loads Using Sequential Quadratic Programming. In Proceedings of the 2024 28th International Conference on Information Technology (IT); IEEE, February 21 2024; pp. 1–6. [Google Scholar]
- 7.Hidayah Abdul Kahar N.; Zobaa A.F.; Turky R.A.; Zobaa A.M.; Abdel Aleem S.H.E.; Ismail B. Comparative Analysis of Optimal Damped and Undamped Passive Filters Using MIDACO-Solver. Ain Shams Engineering Journal 2023, 14, 102056, doi: 10.1016/j.asej.2022.102056 [DOI] [Google Scholar]
- 8.Zobaa A.M.; Abdel Aleem S.H.E.; Youssef H.K.M. Bi-Level Damped Double-Tuned Harmonic Passive Filters Design: Multi-Criteria Decision-Making Analysis. Ain Shams Engineering Journal 2023, 14, 102082, doi: 10.1016/j.asej.2022.102082 [DOI] [Google Scholar]
- 9.Mirbagheri S.M.; Falabretti D.; Ilea V.; Merlo M. Hosting Capacity Analysis: A Review and a New Evaluation Method in Case of Parameters Uncertainty and Multi-Generator. In Proceedings of the 2018 IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial and Commercial Power Systems Europe (EEEIC / I&CPS Europe); IEEE, June 2018; pp. 1–6. [Google Scholar]
- 10.Ismael S.; Abdel Aleem S.; Abdelaziz A.; Zobaa A. Probabilistic Hosting Capacity Enhancement in Non-Sinusoidal Power Distribution Systems Using a Hybrid PSOGSA Optimization Algorithm. Energies (Basel) 2019, 12, 1018, doi: 10.3390/en12061018 [DOI] [Google Scholar]
- 11.Yuan J.; Weng Y.; Tan C.-W. Determining Maximum Hosting Capacity for PV Systems in Distribution Grids. International Journal of Electrical Power & Energy Systems 2022, 135, 107342, doi: 10.1016/j.ijepes.2021.107342 [DOI] [Google Scholar]
- 12.Qamar N.; Arshad A.; Mahmoud K.; Lehtonen M. Hosting Capacity in Distribution Grids: A Review of Definitions, Performance Indices, Determination Methodologies, and Enhancement Techniques. Energy Sci Eng 2023, 11, 1536–1559, doi: 10.1002/ese3.1389 [DOI] [Google Scholar]
- 13.Ismael S.M.; Abdel Aleem S.H.E.; Abdelaziz A.Y.; Zobaa A.F. Practical Considerations for Optimal Conductor Reinforcement and Hosting Capacity Enhancement in Radial Distribution Systems. IEEE Access 2018, 6, 27268–27277, doi: 10.1109/ACCESS.2018.2835165 [DOI] [Google Scholar]
- 14.Lamedica R.; Geri A.; Gatta F.M.; Sangiovanni S.; Maccioni M.; Ruvio A. Integrating Electric Vehicles in Microgrids: Overview on Hosting Capacity and New Controls. IEEE Trans Ind Appl 2019, 55, 7338–7346, doi: 10.1109/TIA.2019.2933800 [DOI] [Google Scholar]
- 15.Talkington S.; Grijalva S.; Reno M.J.; Azzolini J.A.; Pinney D. A Measurement-Based Approach to Voltage-Constrained Hosting Capacity Analysis with Controllable Reactive Power behind-the-Meter. Electric Power Systems Research 2023, 221, 109395, doi: 10.1016/j.epsr.2023.109395 [DOI] [Google Scholar]
- 16.Nakhodchi, N.; Bollen, M.H.J. ESTIMATION OF SAFE HARMONIC HOSTING CAPACITY. In Proceedings of the CIRED 2021—The 26th International Conference and Exhibition on Electricity Distribution; Institution of Engineering and Technology, 2021; pp. 693–697.
- 17.De Cillo Moro V.; Bonadia S., Trindade R.; C. L, F. A Review of Methods for Assessing DER Hosting Capacity of Power Distribution Systems. IEEE Latin America Transactions 2022, 20, 2275–2287, doi: 10.1109/TLA.2022.9885165 [DOI] [Google Scholar]
- 18.Diaaeldin I.M.; Abdel Aleem S.H.E.; El-Rafei A.; Abdelaziz A.Y.; Zobaa A.F. Enhancement of Hosting Capacity with Soft Open Points and Distribution System Reconfiguration: Multi-Objective Bilevel Stochastic Optimization. Energies (Basel) 2020, 13, 5446, doi: 10.3390/en13205446 [DOI] [Google Scholar]
- 19.Al-Saadi H.; Zivanovic R.; Al-Sarawi S.F. Probabilistic Hosting Capacity for Active Distribution Networks. IEEE Trans Industr Inform 2017, 13, 2519–2532, doi: 10.1109/TII.2017.2698505 [DOI] [Google Scholar]
- 20.Karimi M.; Mokhlis H.; Naidu K.; Uddin S.; Bakar A.H. A. Photovoltaic Penetration Issues and Impacts in Distribution Network–A Review. Renewable and Sustainable Energy Reviews 2016, 53, 594–605, doi: 10.1016/j.rser.2015.08.042 [DOI] [Google Scholar]
- 21.Athari M.H.; Wang Z.; Eylas S.H. Time-Series Analysis of Photovoltaic Distributed Generation Impacts on a Local Distributed Network. In Proceedings of the 2017 IEEE Manchester PowerTech; IEEE, June 2017; pp. 1–6. [Google Scholar]
- 22.Rascon O.C.; Schachler B.; Buhler J.; Resch M.; Sumper A. Increasing the Hosting Capacity of Distribution Grids by Implementing Residential PV Storage Systems and Reactive Power Control. In Proceedings of the 2016 13th International Conference on the European Energy Market (EEM); IEEE, June 2016; pp. 1–5. [Google Scholar]
- 23.Hashemi S.; Ostergaard J. Efficient Control of Energy Storage for Increasing the PV Hosting Capacity of LV Grids. IEEE Trans Smart Grid 2016, 1–1, doi: 10.1109/TSG.2016.2609892 [DOI] [Google Scholar]
- 24.Sakar S.; Balci M.E.; Aleem S.H.E.A.; Zobaa A.F. Hosting Capacity Assessment and Improvement for Photovoltaic-Based Distributed Generation in Distorted Distribution Networks. In Proceedings of the 2016 IEEE 16th International Conference on Environment and Electrical Engineering (EEEIC); IEEE, June 2016; pp. 1–6. [Google Scholar]
- 25.Santos I.N.; Ćuk V.; Almeida P.M.; Bollen M.H.J.; Ribeiro P.F. Considerations on Hosting Capacity for Harmonic Distortions on Transmission and Distribution Systems. Electric Power Systems Research 2015, 119, 199–206, doi: 10.1016/j.epsr.2014.09.020 [DOI] [Google Scholar]
- 26.Wei Sun; Harrison G.P.; Djokic S.Z. Distribution Network Capacity Assessment: Incorporating Harmonic Distortion Limits. In Proceedings of the 2012 IEEE Power and Energy Society General Meeting; IEEE, July 2012; pp. 1–7. [Google Scholar]
- 27.Bhowmik A.; Maitra A.; Halpin S.M.; Schatz J.E. Determination of Allowable Penetration Levels of Distributed Generation Resources Based on Harmonic Limit Considerations. IEEE Transactions on Power Delivery 2003, 18, 619–624, doi: 10.1109/TPWRD.2003.810494 [DOI] [Google Scholar]
- 28.Zobaa A.M.; Abdel Aleem S.H.E.; Youssef H.K.M. Comparative Analysis of Double-Tuned Harmonic Passive Filter Design Methodologies Using Slime Mould Optimization Algorithm. In Proceedings of the 2021 IEEE Texas Power and Energy Conference (TPEC); IEEE, February 2 2021; pp. 1–6. [Google Scholar]
- 29.IEEE IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems. IEEE Std 519–2014 (Revision of IEEE Std 519–1992) 2014, 1–29. [Google Scholar]
- 30.Abdel Aleem H.E., Elmathana S.; T, Zobaa M.; F, A. Different Design Approaches of Shunt Passive Harmonic Filters Based on IEEE Std. 519–1992 and IEEE Std. 18–2002. Recent Patents on Electrical & Electronic Engineering 2013, 6, 68–75, doi: 10.2174/2213111611306010009 [DOI] [Google Scholar]
- 31.Zhao W.; Zhang Z.; Mirjalili S.; Wang L.; Khodadadi N.; Mirjalili S.M. An Effective Multi-Objective Artificial Hummingbird Algorithm with Dynamic Elimination-Based Crowding Distance for Solving Engineering Design Problems. Comput Methods Appl Mech Eng 2022, 398, 115223, doi: 10.1016/j.cma.2022.115223 [DOI] [Google Scholar]
- 32.Khodadadi N.; Mirjalili S.M.; Zhao W.; Zhang Z.; Wang L.; Mirjalili S. Multi-Objective Artificial Hummingbird Algorithm. In; 2023; pp. 407–419. [Google Scholar]
- 33.Hwang C.-L.; Lai Y.-J.; Liu T.-Y. A New Approach for Multiple Objective Decision Making. Comput Oper Res 1993, 20, 889–899, doi: 10.1016/0305-0548(93)90109-V [DOI] [Google Scholar]
- 34.Al-Baik O.; Alomari S.; Alssayed O.; Gochhait S.; Leonova I.; Dutta U.; et al M. Pufferfish Optimization Algorithm: A New Bio-Inspired Metaheuristic Algorithm for Solving Optimization Problems. Biomimetics 2024, 9, 65, doi: 10.3390/biomimetics9020065 [DOI] [PMC free article] [PubMed] [Google Scholar]
- 35.Coello Coello, C.A.; Lechuga, M.S. MOPSO: A Proposal for Multiple Objective Particle Swarm Optimization. In Proceedings of the Proceedings of the 2002 Congress on Evolutionary Computation. CEC’02 (Cat. No.02TH8600); IEEE; pp. 1051–1056.
- 36.Premkumar M.; Jangir P.; Sowmya R.; Alhelou H.H.; Heidari A.A.; Chen H. MOSMA: Multi-Objective Slime Mould Algorithm Based on Elitist Non-Dominated Sorting. IEEE Access 2021, 9, 3229–3248, doi: 10.1109/ACCESS.2020.3047936 [DOI] [Google Scholar]
- 37.Jangir Dr. Pradeep Narottam Jangir Non-Dominated Sorting Whale Optimization Algorithm (NSWOA): A Multi-Objective Optimization Algorithm for Solving Engineering Design Problems. Global Journals of Research in Engineering 2017, 17, 15–42. [Google Scholar]
- 38.Jangir P.; Heidari A.A.; Chen H. Elitist Non-Dominated Sorting Harris Hawks Optimization: Framework and Developments for Multi-Objective Problems. Expert Syst Appl 2021, 186, 115747, doi: 10.1016/j.eswa.2021.115747 [DOI] [Google Scholar]
- 39.Khodadadi N.; Talatahari S.; Dadras Eslamlou A. MOTEO: A Novel Multi-Objective Thermal Exchange Optimization Algorithm for Engineering Problems. Soft comput 2022, 26, 6659–6684, doi: 10.1007/s00500-022-07050-7 [DOI] [Google Scholar]
- 40.Bajaj M.; Singh A.K. Performance Assessment of Hybrid Active Filtering Technique to Enhance the Hosting Capacity of Distorted Grids for Renewable Energy Systems. Int J Energy Res 2022, 46, 2783–2809, doi: 10.1002/er.7345 [DOI] [Google Scholar]
- 41.Zobaa, A.M.; Shady Abdel Aleem, H.E.; Hosam Youssef, K.M. Hosting Capacity Enhancement of Harmonically Distorted Distribution Systems Using Multi-Objective Artificial Hummingbird Algorithm. In Proceedings of the 2023 24th International Middle East Power System Conference (MEPCON); IEEE, December 19 2023; pp. 1–8.
Associated Data
This section collects any data citations, data availability statements, or supplementary materials included in this article.
Supplementary Materials
(PDF)
Data Availability Statement
All relevant data is within the manuscript and its supporting information files.