Enhancing Coordination Efficiency with Fuzzy Monte Carlo Uncertainty Analysis for Dual-Setting Directional Overcurrent Relays Amid Distributed Generation

Faraj Al-Bhadely 1,*, Aslan İnan 1
Editors: Seyed Morteza Alizadeh1, Akhtar Kalam1
PMCID: PMC11243921  PMID: 39000894

Abstract

In the contemporary context of power network protection, acknowledging uncertainties in safeguarding recent power networks integrated with distributed generation (DG) is imperative to uphold the dependability, security, and efficiency of the grid amid the escalating integration of renewable energy sources and evolving operational conditions. This study delves into the optimization of relay settings within distribution networks, presenting a novel approach aimed at augmenting coordination while accounting for the dynamic presence of DG resources and the uncertainties inherent in their generation outputs and load consumption—factors previously overlooked in existing research. Departing from conventional methodologies, the study proposes a dual-setting characteristic for directional overcurrent relays (DOCRs). Initially, a meticulous modeling of a power network featuring distributed generation is undertaken, integrating Weibull probability functions for each resource to capture their probabilistic behavior. Subsequently, the second stage employs the fuzzy Monte Carlo method to address generation and consumption uncertainties. The optimization conundrum is addressed using the ant lion optimizer (ALO) algorithm in the MATLAB environment. This thorough analysis was conducted on IEEE 14-bus and IEEE 30-bus power distribution systems, showcasing a notable reduction in the total DOCR operating time compared to conventional characteristics. The proposed characteristic not only achieves resilient coordination across a spectrum of uncertainties in both distributed generation outputs and load consumption, but also strengthens the resilience of distribution networks overall.

Keywords: overcurrent relay coordination, uncertainty, distributed generation, fuzzy Monte Carlo simulation, ALO

1. Introduction

1.1. Importance

In the dynamic realm of power distribution systems, the integration of distributed generation resources presents a distinctive array of hurdles in ensuring the dependable and effective protection of power networks. Coordinating directional overcurrent relays (DOCRs) become increasingly intricate when faced with uncertainties arising from both distributed generation (DG) outputs and load consumption patterns. Conventionally, relay configurations have been established without considering the dynamic presence of DG sources or fluctuations in their performance, thereby constraining the adaptability of the distribution networks. Traditional DOCRs are typically set to trigger at a fixed current level and direction, predicated on predetermined settings that are primarily suited to standard operating conditions. Nevertheless, the increasing incorporation of DG into power systems has introduced new challenges for protection and coordination. DG sources such as solar and wind power, exhibit variability in their output due to factors such as weather conditions and fluctuations in demand. This variability can result in shifts in fault currents and locations within the power system, complicating the maintenance of effective coordination using conventional single-setting DOCRs. To address these challenges, recent research has concentrated on the development of dual-setting DOCRs, which provide greater flexibility and adaptability in coordinating protection schemes in the presence of DG. Dual-setting relays enable a single relay to function in both the forward/primary and reverse/backup directions, simultaneously. This innovative programming approach augments relay operation efficiency by reducing the total relay tripping time. In light of these advancements, the following section presents a literature review encompassing recent modern research in this area.

1.2. Literature Review

Traditional directional overcurrent relays (DOCRs) have long been the cornerstone of power system protection strategies, offering fixed parameters for pickup currents, time delays, and directional features. However, as power systems undergo transformations with the integration of distributed generation (DG) and encounter heightened uncertainties, the shortcomings of single-setting relays have become apparent. Early investigations into traditional DOCRs primarily focused on optimizing relay configurations for coordination and fault detection under stable operational conditions. Pioneering research [1,2,3,4,5] underscored the significance of precisely configuring relay parameters to ensure efficient coordination and mitigate the risk of erroneous operations. Similarly, other studies [6,7] shed light on the complexities of coordinating protection schemes in systems with extensive DG penetration, proposing heuristic-driven methodologies to bolster coordination reliability. However, these endeavors have yet to present a comprehensive framework for modeling uncertainties in distribution power networks. As power systems transition towards more decentralized and dynamic architectures, the necessity for adaptive protection schemes becomes paramount [8]. Dual-setting DOCRs have emerged as a promising solution for addressing the limitations of single-setting relays and enhancing protection coordination in modern power systems [9]. These dual-setting relays offer flexibility to independently adjust the pickup currents and time delays for each directional setting, thereby enabling improved fault detection and discrimination across various operating scenarios [10]. Recent advancements in dual-setting DOCRs have been spurred by the incorporation of advanced optimization techniques and uncertainty analysis. Several studies [11,12,13] introduced optimization algorithms tailored for dual-setting relays, leveraging methodologies such as genetic algorithms and particle swarm optimization to identify optimal relay settings while considering system constraints and coordination requisites. These methodologies demonstrate enhanced coordination capabilities. In addition, a scheme based on the overcurrent theory using a supervisory system with communication capabilities was developed to re-evaluate the coordination for every topological change in the power system [14]. Furthermore, the behavior of overcurrent relays was studied, concentrating on operating speed and relay selectivity to ensure proper coordination of the protection system [15]. Alternatively, the manta ray foraging optimization approach was utilized to enhance overcurrent relay (OCR) configurations and maintain coordination tolerances within relay pairs [16], while simulated annealing–linear programming was used to obtain optimal OCR coordination [1]. Moreover, a comprehensive analysis of the selectivity challenges in OCR design based on statistical data was carried out [17]. Furthermore, the tripping characteristics of OCR relays, both standard and non-standard, were investigated using the tug-of-war optimization algorithm and the charged system search algorithm [18]. Consequently, to address the increased short-circuit currents arising from DG integration, an online communication system with multi-setting relays developed from offline experiments was incorporated [19]. In addition, a protective system based on communication linkages between OCRs with ideal standard features placed on both sides of the distribution lines and protection zones was suggested [20]. Furthermore, modern numerical relays with multifunctional data storage, communication, and signal processing functions were used to optimize relay settings while considering the various operational scenarios related to DG resources. An advanced two-level algorithm intended to optimize protective relay parameters by integrating various operating scenarios within communication systems was also introduced [21]. In another study, relay working times were determined using only the local voltage magnitude [22]. In a further study, a novel OCR-based area protection scheme designed especially for distribution networks with significant DG source penetration was proposed [23]. Additionally, wind speed and direction predictions were employed to facilitate online relay settings, initially determined offline using optimization techniques [24]. Furthermore, a unique non-communication-based time–current–voltage dual-setting directional overcurrent prevention strategy designed specifically for distribution systems with DG integration was also introduced [25]. The sine–cosine technique was used to overcome optimal coordination issues associated with directional OCRs [26]. In a further work, network topology groups and ideal relay settings were discussed concurrently [27]. Furthermore, support vector machines were used as a classifier to establish predefined trip times for OCRs [28]. Moreover, a multi-agent system-based hierarchical protection approach was used to provide a comprehensive protection strategy, with higher levels of updated relay settings and lower ones concentrating on fault clearance and protection coordination [29]. Ultimately, to increase the versatility of protection methods, user-defined dual-setting OCRs with hybrid time current-voltage characteristics were designed [30]. Numerous studies have investigated the protection of optimized microgrids (MGs) and smart grids (SGs), such as those referenced in [31,32]. However, their focus was primarily on the foundational network configuration and selectivity constraints. This myopic approach risks selectivity constraints that breach alternate topologies. Moreover, the absence of a comprehensive modeling strategy for uncertainties poses significant challenges in real-world applications. In light of these limitations, some scholars, as exemplified in [33,34], have explored protection coordination across diverse grid configurations, while protecting MGs/SGs with a singular setting group sans additional communication infrastructure for various configurations. However, while this is convenient and practical, it may impede protection speed due to multifarious constraints and a restricted search space for DOCRs. Entering the concept of adaptive protection is a pragmatic avenue to address concerns in MG/SG protection across varying operating conditions and topologies. Nonetheless, the implementation of adaptive protection systems necessitates extensive telecommunication links and introduces uncertainty into their operations [34]. However, dependable communication-aided adaptive schemes have significant advantages. Numerous research endeavors have scrutinized adaptive protective schemes for SGs/MGs. For instance, the authors of [35] introduced an adaptive and robust protection mechanism that accounts for the power quality characteristics and voltage indicators. Similarly, the authors of [36] reported adaptive protection considering the stability constraints of distributed generations (DGs), whereas [37] focused on reducing coordination optimization constraints. However, it is crucial to optimize the current and time settings of OCRs while overlooking optimization of the characteristic curves. This oversight, coupled with the absence of a comprehensive method to address uncertainties, renders these methods practical, yet potentially less efficient in real-world scenarios. In active distribution networks (ADNs), SGs, and MGs, uncertainties stemming from load and generation units can lead to protection miscoordination. To address this challenge, a study [38] proposed clustering different network topologies into a limited set, facilitating the determination of optimal relay settings for each cluster. This approach, simultaneously tackles setting groups and optimal network topology clusters, while also investigating the impact of relay characteristics on reducing operating times. Despite these advancements, the number of available setting groups remains significantly lower than the number of potential configurations, limiting multiple-setting group-based protective schemes to a handful of topologies and operation modes. In [39], a pioneering setting-group-based scheme for protecting networked MGs employing DOCRs was introduced. This scheme ensures adequate protection across all MGs under various interconnections with the utility grid. However, while [39] offers a model for categorizing MG interconnections into distinct groups and determining optimal relay settings, it falls short in accommodating diverse states of uncertainties in the protection scheme. However, these studies have yet to present a practical and comprehensive scheme for modeling uncertainties in protection settings, which could potentially impact the performance and reliability compared to traditional methods. Reference [40] introduced a methodology aimed at addressing uncertainty in demands and DGs within distribution systems through Monte Carlo simulation, a statistical technique that generates multiple random samples of uncertain parameters to analyze system behavior and understand the impacts of uncertainties on system performance. However, the neglect of the fuzzification of relay inputs in this research raises concerns about the efficiency and accuracy of the proposed scheme. The incorporation of uncertainty analysis using fuzzy Monte Carlo techniques has further bolstered the capabilities of dual-setting DOCRs to mitigate uncertainties stemming from DG integration and load variations, aspects overlooked in previous state-of-the-art research. Although significant strides have been made in the development and application of dual-setting DOCRs, challenges persist, including the lack of standardized methodologies for relay parameter optimization and coordination algorithms. Future research endeavors should prioritize addressing these challenges to propel power system protection toward meet the evolving requirements of modern power systems.

1.3. Contribution

The integration of dual-Setting directional overcurrent relays (DOCRs) with uncertainty analysis introduces a pioneering methodology that seamlessly merges DOCRs with uncertainty modeling utilizing fuzzy Monte Carlo methods, which incorporates fuzzy Monte Carlo simulation to effectively model and address uncertainties stemming from factors such as load variations, intermittent renewable energy generation, and equipment failures. By doing so, it enhances the adaptability of relay coordination to fluctuating operating conditions, consequently bolstering the system reliability and performance. Moreover, the proposed fuzzy Monte Carlo simulation possesses several distinctive capabilities that have been overlooked in previous state-of-the-art studies. The primary contributions of our study can be succinctly outlined as follows:

  • Capturing Imprecise Information: Unlike conventional probabilistic methods that rely on precise probability distributions, fuzzy logic enables the representation of imprecise or vague information inherent in real-world systems. This feature proves invaluable in scenarios where obtaining precise data is challenging.

  • Flexibility in Modeling: Fuzzy Monte Carlo offers unparalleled flexibility in modeling uncertainties by accommodating expert knowledge or subjective assessments. This adaptability allows for the inclusion of qualitative factors, thereby enhancing the realism and accuracy of the uncertainty model. Fuzzy logic excels in handling the nonlinear and complex relationships often encountered in engineering and decision-making contexts.

  • Robustness to Data Limitations: In situations where data availability is limited or uncertain, fuzzy Monte Carlo remains robust by incorporating expert knowledge or heuristic information. This resilience to data limitations renders fuzzy Monte Carlo indispensable in scenarios where empirical data may be scarce or unreliable.

  • Integration with Monte Carlo Simulation: By integrating fuzzy logic with Monte Carlo simulation, fuzzy Monte Carlo harnesses the strengths of both approaches. This integration ensures the efficient generation of probabilistic outcomes while capturing qualitative aspects of uncertainty.

Additionally, this study contributes to the practical application of uncertainty modeling by employing a Weibull distribution to accurately depict the variability and unpredictability of DG power generation and demand in real-world scenarios. Furthermore, a Monte Carlo simulation approach with a fixed number of iterations was utilized to address uncertainties in the input variables, such as DG output and load demand. This simulation technique guarantees the accurate and efficient sampling of uncertain variables, leading to enhanced convergence and a comprehensive understanding of the potential outcomes and behaviors of the power system under varying conditions. Finally, the proposed methodology enhances the efficiency and resilience of protection schemes by offering insights into the impact of uncertainties on protection coordination and presenting practical solutions for their mitigation. Conventional relay coordination typically involves fixed relay settings based on predetermined system parameters. It is proposed that dual-setting relay coordination allows for the dynamic adjustment of relay settings in response to changing system conditions or events. This dynamic adaptation enhances the flexibility and robustness of the coordination scheme, enabling better fault detection and isolation, particularly in systems with a high DG penetration and variable generation patterns.

1.4. Organization

The rest of the paper is organized as follows. Section 2 discusses the conceptual framework and the probabilistic model underpinning the fuzzy Monte Carlo method. In Section 3, we detail the mathematical formulation of our proposed technique. Section 4 presents the simulation results and a thorough discussion of these findings. Lastly, Section 5 summarizes the key conclusions drawn from the study.

2. Probabilistic Model of Fuzzy Monte Carlo

The probabilistic model of fuzzy Monte Carlo (PFMC) is a pivotal approach in the realm of power system protection that directly handles the dual challenges posed by randomness and vagueness. In essence, probabilistic modeling takes the center stage, offering a method to encapsulate uncertainties stemming from randomness. Here, probability distributions, including Weibull, exponential, and log-normal distributions, serve as robust tools to depict the uncertainties linked to equipment failure rates and fault occurrence probabilities, as elucidated subsequently. In this vein, this study amalgamates both probabilistic and fuzzy logic methodologies, crafting a holistic framework tailored to model uncertainties in power system protection. Furthermore, the use of Monte Carlo simulations serves as a cornerstone, facilitating the dissemination of uncertainties throughout the protection system, thereby evaluating its efficacy across diverse operational scenarios. Random samples are drawn from the probability distributions of the input parameters, whereas fuzzy inference systems process fuzzy inputs adeptly, yielding fuzzy outputs. Through the simulation of myriad scenarios, the Monte Carlo methodology provides a thorough assessment of the protection system’s reliability, resilience, and effectiveness in navigating risks under uncertain conditions. Illustrating the conceptual underpinning of the proposed protection scheme, Figure 1 offers a visual depiction outlining the framework’s key components and their interrelationships.

Figure 1.

Figure 1

Conceptual Model of Proposed Protection scheme Using Fuzzy Monte Carlo Probabilistic Model.

2.1. Calculation of Weibull Distribution Parameters

Robust modeling techniques are employed to address the variability and unpredictability inherent in power system parameters such as load demands and DG output. This section outlines the approach for modeling uncertain variables and provides insights into the methodologies utilized. The DG output pattern follows a Weibull probability density function (PDF) [41], as shown in Equation (1).

f(x)=βαβxβ1expxαβ (1)

The uncertainty associated with the load can be represented using a normal PDF, as shown in Equation (2).

f(x)=1σ2πe(xμ)22σ2 (2)

In this method, y = f(x) is regarded as a multivariate function, where x=x1,x2,x3,,xn represents a vector of uncertain random input variables. It is assumed that the PDFs of the input variables are known. The objective was to derive the PDF of y, the output variable.

2.2. Monte Carlo Simulation with PDFs

In addition to calculating the Weibull distribution parameters, the probabilistic modeling method incorporates uncertainty modeling using the fuzzy Monte Carlo method. A straightforward approach with a fixed number of iterations was adopted to perform the Monte Carlo simulation. This technique facilitates the accurate and efficient sampling of uncertain variables, resulting in improved convergence and reliability of the analysis. In each iteration of the Monte Carlo simulation, the values for the uncertain input variables were sampled from their respective probability distributions or fuzzy sets. Generating a large number of samples allows a comprehensive understanding of the potential outcomes and behaviors of the system under varying conditions. Over the past decade, the increasing penetration of DG has fundamentally changed the operation and protection of distribution networks. In this study, the previous research on single-setting DOCRs was extended by developing a methodology for optimal coordination using dual-setting DOCRs. This methodology involves the integration of advanced optimization techniques with uncertainty analysis to ensure robust and reliable protection coordination in the presence of a DG source. Incorporating uncertainty modeling using fuzzy Monte Carlo methods allows accounting for the variability and unpredictability associated with DG output and system conditions. This allows the identification of optimal relay settings that are adaptive to changing operating conditions and can mitigate the effects of uncertainties on protection coordination. Overall, this work builds upon the foundation of previous research on single-setting DOCRs and advances the state-of-the-art in power system protection by introducing dual-setting DOCRs with enhanced flexibility, adaptability, and robustness in coordinating protection schemes in the presence of distributed generation and uncertainty. The contribution of DG sources to faults depends on factors such as the generating capacity of the DG source (size of the DG source), the distance from the DG source to the fault location and the type of DG source. To represent the variability and uncertainty of (DG) power generation and demand in real world scenarios, we used a Weibull distribution. In addition, a simple Monte Carlo simulation approach with a fixed number of iterations was employed. This technique provides an accurate and efficient sampling of uncertain variables, leading to better convergence. A Monte Carlo simulation was performed to account for the uncertainty in the input variables. In each simulation iteration, the sample values for the uncertain input variables are obtained from their respective probability distributions or fuzzy sets.

3. Problem Formulation

The operating time of a DOCR typically inversely correlates with the short-circuit current it experiences, a relationship that has been thoroughly explored in numerous studies on protection systems. The time–current characteristic of the relay is generally described as in Equation (3) [42].

Tik=TMSi×AIF,ikPSiB1 (3)

where i denotes the relay identifier, and k signifies the fault location identifier. The constants A and B, which are often adjusted to 0.14 and 0.02, respectively, depend on the kind of OCR. The relay fault current is denoted by IF,ik, while PSi represents the relay pickup current.

3.1. Modeling Dual-Setting DOCR Characteristics

Dual-setting directional overcurrent relays (DS-DOCRs) represent a significant leap forward in protective relay technology. These relays, designed to operate in both the forward and reverse directions, offer primary and backup protection functionalities. In contrast to conventional DOCRs restricted to one direction, DS-DOCRs provide bidirectional fault detection capabilities. Leveraging advanced mechanisms, DS-DOCRs are adept at detecting faults in both directions and triggering responses based on pre-defined time and pickup settings.

Primary Protection: This denotes the principal function of the relay, triggered when the fault current flows in the forward direction. The settings for primary protection are designated as TMSfw and PSfw, where TMSfw represents the time multiplier setting, and PSfw represents the pickup setting.

Backup Protection: This serves as a secondary protection function of the relay and is activated when the fault current flows in the reverse direction. The settings for backup protection are indicated as TMSrv and PSrv, where TMSrv represents the time multiplier setting and PSrv represents the pickup setting.

Time–Current Characteristic: This refers to a graphical representation illustrating how the relay responds to various fault currents over time. Figure 2 illustrates the time–current characteristic curve of the relay, depicting its response for both primary and backup protection operations.

Figure 2.

Figure 2

Time–current characteristics for the dual-setting DOCR.

Figure 3 illustrates an example of a dual-setting directional overcurrent relay equipped with the relay characteristics depicted in the same figure. Each relay is represented by two arrows, indicating the two directions of the fault current flow for which the relay can operate. The red-colored parts of the DOCRs represents the forward-directed protection section, while the green-colored parts indicates the reverse-directed protection section. In the event of a fault occurring at point F, the relay configurations are as follows: R3 serves as the backup relay for R1, and R4, R5, and R6 function as backup relays for R2. In such scenarios, R3 utilizes settings associated with reverse operation (TMSrv3 and PSrv3), whereas R1 employs settings linked with forward operation (TMSfw1 and PSfw1), and similarly for other relays. This configuration ensures comprehensive protection coverage for fault occurrences in both forward and reverse directions.

Figure 3.

Figure 3

Protection with dual-setting directional relays.

Previous research, e.g., [43], has highlighted the challenges in ensuring proper coordination between relays with dual settings. Therefore, the proposed scheme emphasizes the importance of efficient communication even in low-bandwidth scenarios to ensure effective coordination for backup operations, as discussed in [44]. Figure 4 illustrates a section of the test system, emphasizing the communication strategy employed between the dual-setting relays. The essence of this strategy lies in establishing communication between the relays operating in the reverse and forward directions along the same lines. This communication ensures that the reverse direction characteristic of each relay communicates with the forward direction characteristic of the adjacent relay, effectively blocking its operation when necessary. By implementing this communication strategy across all relays in the system, we aim to prevent scenarios such as the unintended operation of a relay (e.g., R13 in the forward direction) for a fault at a specific location (e.g., F8). This proactive approach not only maintains the achieved reduction in fault isolation time but also ensures proper protection coordination among the relays. It is important to note that the communication mechanism primarily applies to the backup relay operations. Therefore, in the event of a communication failure or delay, the primary relays remain unaffected, and the protection scheme can still isolate faults in a timely manner. For instance, in the case of a fault at F8, the R15’s forward characteristic will operate and isolate the fault regardless of the communication link’s status. Even if R15 fails to operate because of a malfunction and the communication link is lost, R13 will still operate before relay R14, guaranteeing fault isolation, albeit with temporary coordination discrepancies.

Figure 4.

Figure 4

Illustration of a segment from the test system, emphasizing the communication approach employed.

3.2. Objective Function

Due to the presence of fault currents flowing in both the forward and reverse directions, certain manufacturers have proposed dual-setting DOCRs to respond differently in each direction. In [34], the following objective function is present in Equation (4):

OBJ=mink=1Mi=1NfwTi,kfw+j=1NrvTj,krv(i,j)ω (4)

In this context, ω represents the set of relay P/B pairs and N denotes the total number of relays, while M indicates the total number of fault locations along all lines. The terms Ti,kfw, and Tj,krv correspond to the tripping times of relays i, and j for a fault at location k during forward and reverse operations, respectively, as described by Equations (5) and (6):

Ti,kfw=TMSifw×AIF,ifwPSifwB1 (5)
Tj,krv=TMSjrv×AIF,jrvPSjrvB1 (6)

In this context, TMSifw and TMSjrv are the time multiplier settings for relays i and j in the forward and reverse directions, respectively. Similarly, PSifw and PSjrv denote the plug settings of relays i and j for forward and reverse operations, respectively. The fault current at location k, passing through relay i in the forward direction, is represented as IF,ifw. Likewise, IF,jrv indicates the fault current passing through relay j in the reverse direction due to a fault at location k. The coordination constraints, which must be met to solve the protection coordination problem, can be expressed by Equation (7).

Tj,krvTi,kfwCTIi,j,k (7)

The coordination time interval CTI represents the minimum time difference between the operation of primary and backup relays. Typically, the CTI ranges from 0.2 to 0.5 s; in this study, it was set to 0.2 s. Furthermore, there are upper and lower bounds on the relay settings, defined by Equations (8) and (9), respectively.

PSmin(PSifw,PSjrv)PSmax (8)
TMSmin(TMSifw,TMSjrv)TMSmax (9)

In this context, PSmin and PSmax denote the lower and upper bounds, respectively, for relay i’s plug setting. Similarly, TMSmin and TMSmax represent the lower and upper bounds for the time multiplier setting for relay i.

3.3. ALO Optimization Approach for Addressing Coordination Issues

This study introduces an optimization algorithm referred to as the ant lion optimizer (ALO), which is meticulously crafted to effectively address coordination challenges. In particular, the ALO method is employed to determine the optimal values for both the pickup current and Time Multiplier Setting (TMS) of dual-setting DOCRs deployed within distribution systems integrated with DG sources [45]. The ALO used in this study employs an initial population of 250 antlions. As a population-based metaheuristic algorithm, ALO operates on a matrix of multiple antlion and ant individuals. The number of antlions in the initial population was set to 250, which is within the common range of 20–500 individuals used for population-based optimization algorithms. This population size of antlions, along with the population of ants, forms the basis for the cooperative hunting mechanism at the core of the ALO optimization approach. The operational steps of the proposed ALO algorithm, designed to minimize the operating time of the dual-setting DOCRs, are outlined as follows:

  • Step 1: Input Acquisition and System Data Analysis:
    • Acquire input parameters, encompassing distribution system data and relay specifications.
    • Establish primary/backup relay pairs based on gathered data.
    • Calculate both the full load and short circuit currents for each relay to ascertain their operational conditions.
  • Step 2: Initializing Population:
    • Generate initial populations of both antlions and ants, distributing them randomly while adhering to the defined upper and lower parameter constraints.
  • Step 3: Evaluating Fitness Function:
    • Evaluate the fitness function, representing the total relay operating time, for all ants and antlions by employing the objective function index for assessment.
  • Step 4: Identifying Elite Antlions:
    • Identify elite antlion solutions by discerning the top-performing candidates.
  • Step 5: Updating Positions:
    • Adjust parameters to steer ants toward the central point of attraction, represented by antlion.
  • Step 6: Generating Random Walk:
    • Devise a random-walk mechanism to normalize the movement patterns of both ants and antlions.
  • Step 7: Adjusting Positions for Antlions:
    • Update the positions of antlions utilizing a predefined formula to refine their spatial locations.
  • Step 8: Evaluating Solutions:
    • Assess the best solution and substitute the antlion with the corresponding ant if it outperforms an elite candidate.
  • Step 9: Storage and Termination:
    • If the maximum iterations are attained, store and present the optimal results achieved through the algorithm.

A flowchart detailing the operational steps of the ALO algorithm is presented in Figure 5.

Figure 5.

Figure 5

Flowchart of the ant lion optimization (ALO) algorithm.

4. Case Study and Results

4.1. Case 1: IEEE 14-Bus System

In this case study, the adapted distribution section of the IEEE-14 bus system, representing a 7-bus microgrid setup as illustrated in Figure 6, was utilized to analyze the proposed protection method. This configuration includes three (DG sources with a capacity of 20 MVA each linked to buses B4, B5, and B6. Moreover, the 7-bus microgrid system is connected to the sub-transmission network via buses B1 and B2, each with a generation capacity of 60 MVA. Further specifications of the test system can be found in Ref. [46]. This test setup comprised eight lines, protected by 16 dual-setting DOCRs positioned at both line ends. There are 22 relay pairs (RP1RP22). Specifics of the number of primary and backup relays are outlined in Table 1.

Figure 6.

Figure 6

Modified distribution portion of the IEEE 14-bus system.

Table 1.

The primary/backup protective relays.

Relay Pair Primary
Relay
Backup Relay Relay Pair Primary
Relay
Backup Relay
RP1 R1 R3 RP12 R8 R11
RP2 R1 R5 RP13 R9 R7
RP3 R2 R12 RP14 R10 R16
RP4 R3 R1 RP15 R11 R8
RP5 R3 R5 RP16 R12 R2
RP6 R4 R13 RP17 R13 R4
RP7 R5 R1 RP18 R14 R15
RP8 R5 R3 RP19 R14 R6
RP9 R6 R14 RP20 R15 R6
RP10 R6 R15 RP21 R15 R14
RP11 R7 R9 RP22 R16 R10

Simulation Result, Using ALO Algorithm

In this scenario, the metaheuristic ALO algorithm was applied to attain the optimal coordination of dual-setting DOCRs within the test network. A comprehensive, step-by-step elucidation of the implemented algorithm is as follows.

  • Step 1: Optimal Setting Without Considering Uncertainty:

The fault current values recorded via the primary and backup relays for the distribution part of the IEEE-14-bus system are presented in Table 2. The operating times of the primary and backup relay pairs and their associated CTI values are listed in Table 3. The optimal relay setting values for the dual-setting DOCRs are presented in Table 4.

Table 2.

Fault currents through primary and backup relay pairs.

Primary
Relay
Fault
Current (A)
Backup Relay Fault
Current (A)
Primary
Relay
Fault
Current (A)
Backup Relay Fault
Current (A)
R1 10,653.6 R3 1222.4 R8 4713.5 R11 4704.0
R1 10,653.6 R5 2649.6 R9 8183.2 R7 1255.2
R2 7324.3 R12 2555.1 R10 2892.0 R16 3040.1
R3 8858.6 R1 1480.5 R11 6593.3 R8 6593.2
R3 8858.6 R5 1647.9 R12 7922.3 R2 3363.8
R4 6079.3 R13 2093.6 R13 6530.3 R4 2051.0
R5 13,330.2 R1 2246.6 R14 7981.2 R15 2656.4
R5 13,330.2 R3 974.1 R14 7981.2 R6 940.0
R6 9472.2 R14 1877.4 R15 6729.0 R6 2025.4
R6 9472.2 R15 1413.2 R15 6729.0 R14 933.4
R7 14,970.6 R9 1444.0 R16 3232.1 R10 3074.6
Table 3.

Operational times between P/B relay pairs with CTI.

Relay Pairs ALO Relay Pairs ALO
Primary Backup Tp (s) Tb (s) CTI (s) Primary Backup Tp (s) Tb (s) CTI (s)
R1 R3 0.101 0.302 0.201 R8 R11 0.106 0.309 0.204
R1 R5 0.101 0.302 0.201 R9 R7 0.104 0.314 0.210
R2 R12 0.141 0.347 0.206 R10 R16 0.104 0.309 0.205
R3 R1 0.128 0.342 0.213 R11 R8 0.103 0.307 0.205
R3 R5 0.128 0.354 0.226 R12 R2 0.109 0.310 0.202
R4 R13 0.116 0.328 0.212 R13 R4 0.103 0.319 0.216
R5 R1 0.103 0.304 0.201 R14 R15 0.103 0.358 0.255
R5 R3 0.103 0.329 0.226 R14 R6 0.103 0.304 0.200
R6 R14 0.101 0.302 0.201 R15 R6 0.117 0.325 0.208
R6 R15 0.101 0.301 0.200 R15 R14 0.117 0.370 0.253
R7 R9 0.105 0.313 0.208 R16 R10 0.103 0.307 0.204
Table 4.

Optimal setting for dual-setting DOCRs in distribution part of the IEEE-14 Bus System using ALO.

Relay No. Forward Reverse Relay No. Forward Reverse
TMS (s) PS (pu) TMS (s) PS (pu) TMS (s) PS (pu) TMS (s) PS (pu)
R1 0.074 0.045 0.178 0.025 R9 0.078 0.032 0.162 0.025
R2 0.113 0.021 0.148 0.075 R10 0.041 0.109 0.199 0.023
R3 0.102 0.026 0.125 0.042 R11 0.080 0.021 0.099 0.302
R4 0.082 0.031 0.167 0.034 R12 0.088 0.021 0.157 0.068
R5 0.082 0.038 0.149 0.054 R13 0.070 0.040 0.157 0.047
R6 0.079 0.029 0.193 0.022 R14 0.063 0.077 0.174 0.022
R7 0.094 0.023 0.164 0.021 R15 0.087 0.027 0.116 0.059
R8 0.054 0.085 0.214 0.036 R16 0.040 0.134 0.191 0.028
OF (s) = 1.747 s
  • Step 2: Optimal Relay Setting Considering Uncertainty:

The stochastic nature of DG sources and electrical loads introduces uncertainties that profoundly affect the operation of microgrids and distribution networks. Failure to address these uncertainties can result in unrealistic and inaccurate modeling outcomes. Consequently, in this phase, the uncertainties linked to the DG sources and electrical loads were taken into account to effectively optimize the relay settings. To address the challenges posed by uncertainty, a probabilistic analysis is seamlessly integrated into the relay coordination process. By factoring in the variability in DG output power and load demand, the approach ensures that relay settings exhibit robustness and adaptability to a spectrum of operating conditions. This method not only bolsters the reliability and resilience of the distribution network but also fortifies it against unforeseeable fluctuations in both power generation and consumption. The subsequent sections provide a detailed overview of the input data used in the analysis, with a specific focus on the uncertainties associated with the load demand and output power of DG sources within the IEEE 14-bus test system.

  1. Load Uncertainties

    The uncertainties surrounding the load demand at each bus within the test system are critical for precise modeling and analysis. To visually represent these uncertainties, PDFs for both active and reactive power of load demands at each bus are presented. In Figure 7a, the fluctuation in active power load demand across numerous iterations is showcased, offering insights into its variability over time. Additionally, the 3D plot in Figure 7b illustrates the PDF of the active power load demand for each bus. Each curve in this plot represents the PDF of active power load demand at a specific bus, offering a graphical representation of the uncertainties associated with the active power load demand.

    Likewise, Figure 8a portrays the fluctuation in the reactive power load demand across various iterations, providing insight into its variability over time. The 3D plot in Figure 8b presents the PDF of the reactive power load demand for each bus in the test network. These graphical depictions serve to elucidate the uncertainties inherent in load demand across different buses within the network, thereby facilitating more robust modeling and analysis processes.

  2. Distributed Generation Source Output Power Uncertainties

    In addition to load uncertainties, uncertainties exist in the output power of DG sources. Figure 9 illustrates the variation in DG source output power across multiple iterations, offering insights into the variability of DG source power output. Each subplot in the figure represents the output power of a specific DG source throughout the iterations, effectively showcasing the uncertainties associated with DG source power generation.

  3. Monte Carlo Simulation

    One of the most prevalent and accurate stochastic methods used in this study is Monte Carlo simulation (MCS), where the sample sizes are typically set to Ns=500. The MCS is an iterative process that encompasses the following steps:

    • The behavior of the power system for each sample scenario was simulated by considering the generated samples of uncertain parameters.

    • Short-circuit analysis was conducted to ascertain the fault currents in the system for each sample scenario and store these fault currents in a cell array corresponding to each scenario.

    • An optimization algorithm (such as ALO) is utilized to determine the optimal settings for relay coordination based on the fault currents obtained from short circuit analysis. The objective is to minimize the operating time while ensuring proper relay coordination.

    • After obtaining the optimal settings for relay coordination for each sample scenario, the PDFs for the TMS and PS parameters were obtained for both forward and reverse relays. This facilitates the analysis of the distribution of optimal settings across all sample scenarios.

    • The best optimal settings were identified by locating the peaks of the PDFs for the TMS and PS parameters. These settings represent the most frequently occurring optimal configurations across all the sample scenarios.

Figure 7.

Figure 7

Variation in and PDF of Active Power Load Demand in IEEE-14 Bus system.

Figure 8.

Figure 8

Variation in and PDF of Reactive Power Load Demand in IEEE-14 Bus system.

Figure 9.

Figure 9

Variation in DG Outputs Across MCS Iterations in IEEE-14 Bus system.

The optimal relay settings obtained in this process consider the probabilistic distribution of the fault currents and operating conditions. By integrating uncertainty-aware strategies, the coordination of dual-setting DOCRs is optimized to mitigate the risks associated with potential faults and disturbances in the distribution system. The PDFs of the TMS and PS were analyzed for both forward and reverse relays. Additionally, the combined PDFs of the optimal TMS and PS settings are plotted, highlighting the maximum probability density and their respective optimal settings. These PDFs provide valuable insights into the distribution of the optimal relay settings throughout the network. Through a comprehensive analysis, the optimal TMS and PS values for forward-direction relays were determined, as illustrated in Figure 10. Similarly, Figure 11 presents the optimal TMS and PS values for reverse-direction relays.

Figure 10.

Figure 10

PDF and combined PDF of optimal setting for forward relays in IEEE-14 Bus system.

Figure 11.

Figure 11

PDF and combined PDF of optimal setting for reverse relays in IEEE-14 Bus system.

As depicted in Figure 10 and Figure 11 the optimized values for the TMS and PS with the maximum PDF considering uncertainties are notably lower compared to the TMS and PS values without accounting for uncertainties, as indicated in Table 4. This observation underscores the significance of incorporating uncertainties into relay settings, particularly when there are variations in the input data, such as load and generation uncertainties. This highlights the necessity of accounting for uncertainties to ensure a more accurate and reliable relay coordination in the face of varying system conditions. Figure 12 and Figure 13 depict the boxplot graphical representation of the relay operation times in states where uncertainties are considered and not considered, respectively. In Figure 12, all CTI ranges (boxplots) of relay pairs in the state considering uncertainties meet the threshold of CTImin=0.2 (highlighted by a red line). However, in Figure 13, relay pairs such as RP.3,RP.6,RP.9,RP.10,RP.16,RP.17,RP.19, and RP.20 do not satisfy the minimum value of CTImin=0.2 when uncertainties are not taken into account.

Figure 12.

Figure 12

Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting Under Uncertainty.

Figure 13.

Figure 13

Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting without considering uncertainty.

4.2. Case 2: IEEE-30 Bus System

To validate the effectiveness of the newly proposed protection strategy, its application was extended from the distribution section of the IEEE-14 bus test system to a larger microgrid setup. Specifically, the novel protection technique was deployed within the distribution segment of the IEEE-30 bus test system, which represents a 17-bus microgrid configuration [46]. This system consists of 21 lines, safeguarded by 42 dual-setting DOCRs positioned at both ends of the lines, providing a more thorough validation of the proposed methodology. Within this setup, four DG sources are integrated, each with a capacity of 15 MVA and connected to buses B3, B7, B11, and B16. Additionally, the system is linked to the utility grid through buses B1, B6, and B14, as illustrated in Figure 14. Detailed information regarding the number of primary and backup relays can be found in Table 5.

Figure 14.

Figure 14

Modified distribution portion (17-Bus Network) of the IEEE-30 Bus system.

Table 5.

The primary/backup protective relays.

Relay
Pair
Primary
Relay
Backup
Relay
Relay
Pair
Primary
Relay
Backup
Relay
Relay
Pair
Primary
Relay
Backup
Relay
RP1 R1 R3 RP25 R14 R18 RP49 R31 R38
RP2 R1 R19 RP26 R15 R12 RP50 R31 R41
RP3 R1 R21 RP27 R15 R13 RP51 R32 R27
RP4 R2 R5 RP28 R16 R17 RP52 R33 R29
RP5 R3 R1 RP29 R17 R16 RP53 R33 R35
RP6 R3 R19 RP30 R18 R14 RP54 R34 R31
RP7 R3 R21 RP31 R19 R1 RP55 R34 R38
RP8 R4 R6 RP32 R19 R3 RP56 R34 R41
RP9 R4 R7 RP33 R19 R21 RP57 R35 R29
RP10 R5 R2 RP34 R20 R26 RP58 R35 R33
RP11 R6 R4 RP35 R21 R1 RP59 R36 R37
RP12 R6 R7 RP36 R21 R3 RP60 R37 R36
RP13 R7 R4 RP37 R21 R19 RP61 R38 R31
RP14 R7 R6 RP38 R22 R24 RP62 R38 R34
RP15 R8 R9 RP39 R23 R28 RP63 R38 R41
RP16 R8 R40 RP40 R24 R22 RP64 R39 R42
RP17 R9 R8 RP41 R25 R30 RP65 R40 R8
RP18 R9 R40 RP42 R26 R20 RP66 R40 R9
RP19 R10 R11 RP43 R27 R32 RP67 R41 R31
RP20 R11 R10 RP44 R28 R23 RP68 R41 R34
RP21 R12 R13 RP45 R29 R33 RP69 R41 R38
RP22 R12 R15 RP46 R29 R35 RP70 R42 R39
RP23 R13 R12 RP47 R30 R25
RP24 R13 R15 RP48 R31 R34

In this case study, two scenarios are examined, one in which uncertainties are considered and one in which they are not. The ALO algorithm was utilized to optimize the coordination of dual-setting DOCRs within the test network. Initially, the relay settings were determined without considering the uncertainties. Fault current readings obtained from the P/B relays in the distribution section of the IEEE-30 bus system is shown in Table 6. Furthermore, Table 7 provides information on the operating times of the P/B relay pairs and their corresponding CTI values. The optimal settings for dual-setting DOCRs are presented in Table 8. This analysis aims to evaluate the performance of the proposed protection strategy under different conditions, shedding light on its effectiveness in mitigating faults and enhancing the system reliability.

Table 6.

Fault currents through primary and backup relay pairs.

Primary
Relay
Fault
Current (A)
Backup
Relay
Fault
Current (A)
Primary
Relay
Fault
Current (A)
Backup
Relay
Fault
Current (A)
R1 11,648.9 R3 670.7 R21 8446.1 R3 829.0
R1 11,648.9 R19 1839.0 R21 8446.1 R19 1008.5
R1 11,648.9 R21 1954.9 R22 3676.2 R24 3675.5
R2 5493.0 R5 5475.9 R23 5633.3 R28 2643.6
R3 8454.8 R1 1771.5 R24 4773.9 R22 4772.4
R3 8454.8 R19 1516.9 R25 4048.0 R30 4049.4
R3 8454.8 R21 1613.0 R26 6137.9 R20 6140.3
R4 6141.8 R6 1777.1 R27 3572.0 R32 3567.2
R4 6141.8 R7 1962.6 R28 5828.0 R23 3212.8
R5 7080.3 R2 7059.4 R29 8237.6 R33 1484.9
R6 9107.0 R4 3339.6 R29 8237.6 R35 983.7
R6 9107.0 R7 2640.4 R30 3428.9 R25 3426.2
R7 7561.2 R4 2217.5 R31 6177.5 R34 3560.5
R7 7561.2 R6 3389.4 R31 6177.5 R38 1519.4
R8 3677.8 R9 1865.3 R31 6177.5 R41 1128.8
R8 3677.8 R40 1806.4 R32 3462.9 R27 3464.2
R9 4173.4 R8 2826.2 R33 9327.5 R29 1477.9
R9 4173.4 R40 1348.9 R33 9327.5 R35 499.0
R10 3220.9 R11 3224.8 R34 5175.9 R31 2035.3
R11 2409.6 R10 2407.2 R34 5175.9 R38 1533.1
R12 7288.1 R13 630.8 R34 5175.9 R41 1605.4
R12 7288.1 R15 437.4 R35 6880.3 R29 1154.0
R13 3670.6 R12 602.9 R35 6880.3 R33 347.3
R13 3670.6 R15 457.7 R36 3876.2 R37 1603.8
R14 2386.1 R18 456.5 R37 4450.0 R36 2095.1
R15 4879.3 R12 732.7 R38 5488.5 R31 1509.8
R15 4879.3 R13 81.5 R38 5488.5 R34 2801.4
R16 1467.2 R17 1466.0 R38 5488.5 R41 1196.5
R17 1937.1 R16 1936.4 R39 3238.3 R42 3237.9
R18 2961.1 R14 963.7 R40 4514.0 R8 3056.0
R19 12,808.9 R1 1957.7 R40 4514.0 R9 1464.7
R19 12,808.9 R3 1279.3 R41 6597.0 R31 1478.5
R19 12,808.9 R21 1756.7 R41 6597.0 R34 3613.4
R20 2892.6 R26 2878.5 R41 6597.0 R38 1537.6
R21 8446.1 R1 1266.0 R42 2596.3 R39 2592.7

Table 7.

Operational times between P/B relay pairs with CTI.

Relay Pairs ALO Relay Pairs ALO
Primary Backup Tp (s) Tb (s) CTI (s) Primary Backup Tp (s) Tb (s) CTI (s)
R1 R4 0.130 0.463 0.332 R21 R4 0.168 0.375 0.206
R1 R20 0.130 0.381 0.251 R21 R20 0.168 0.382 0.213
R1 R22 0.130 0.372 0.242 R22 R23 0.113 0.440 0.327
R2 R6 0.188 0.467 0.279 R23 R27 0.116 0.551 0.435
R3 R2 0.119 0.369 0.250 R24 R21 0.104 0.497 0.393
R3 R20 0.119 0.408 0.289 R25 R29 0.316 0.521 0.205
R3 R22 0.119 0.396 0.277 R26 R19 0.134 0.357 0.223
R4 R5 0.177 0.520 0.343 R27 R31 0.101 0.371 0.270
R4 R8 0.177 0.492 0.315 R28 R24 0.284 0.501 0.216
R5 R1 0.180 0.499 0.318 R29 R34 0.108 0.316 0.208
R6 R3 0.153 0.421 0.268 R29 R36 0.108 0.383 0.275
R6 R8 0.153 0.439 0.286 R30 R26 0.116 0.732 0.616
R7 R3 0.158 0.476 0.318 R31 R33 0.112 0.345 0.233
R7 R5 0.158 0.413 0.255 R31 R37 0.112 0.332 0.220
R8 R10 0.149 0.405 0.256 R31 R42 0.112 0.343 0.231
R8 R39 0.149 0.425 0.277 R32 R28 0.138 0.392 0.254
R9 R7 0.174 0.456 0.282 R33 R30 0.116 0.316 0.200
R9 R39 0.174 0.466 0.292 R33 R36 0.116 0.515 0.399
R10 R12 0.194 0.520 0.326 R34 R32 0.100 0.301 0.201
R11 R9 0.178 0.504 0.327 R34 R37 0.100 0.331 0.231
R12 R14 0.147 0.486 0.339 R34 R42 0.100 0.318 0.218
R12 R16 0.147 0.516 0.368 R35 R30 0.131 0.348 0.217
R13 R11 0.173 0.467 0.293 R35 R34 0.131 0.521 0.389
R13 R16 0.173 0.506 0.333 R36 R38 0.212 0.523 0.312
R14 R17 0.199 0.627 0.428 R37 R35 0.120 0.434 0.314
R15 R11 0.163 0.411 0.248 R38 R32 0.123 0.327 0.204
R15 R14 0.163 1.316 1.154 R38 R33 0.123 0.367 0.244
R16 R18 0.175 0.590 0.415 R38 R42 0.123 0.339 0.216
R17 R15 0.191 0.516 0.325 R39 R41 0.151 0.356 0.205
R18 R13 0.182 0.569 0.387 R40 R7 0.218 0.443 0.225
R19 R2 0.126 0.356 0.231 R40 R10 0.218 0.421 0.203
R19 R4 0.126 0.357 0.231 R41 R32 0.119 0.329 0.210
R19 R22 0.126 0.385 0.260 R41 R33 0.119 0.344 0.225
R20 R25 0.186 0.480 0.294 R41 R37 0.119 0.331 0.212
R21 R2 0.156 0.420 0.264 R42 R40 0.113 0.359 0.245

Table 8.

Optimal setting for dual-setting DOCRs in distribution part of the IEEE-30 bus system using ALO.

Relay No. Forward Reverse Relay No. Forward Reverse
TMS (s) PS (pu) TMS (s) PS (pu) TMS (s) PS (pu) TMS (s) PS (pu)
R1 0.076 0.055 0.079 0.209 R22 0.040 0.188 0.343 0.027
R2 0.130 0.038 0.505 0.067 R23 0.038 0.338 0.226 0.086
R3 0.091 0.026 0.162 0.025 R24 0.071 0.029 0.205 0.090
R4 0.050 0.124 0.242 0.041 R25 0.204 0.030 0.445 0.033
R5 0.193 0.071 0.154 0.238 R26 0.095 0.031 0.252 0.041
R6 0.060 0.133 0.170 0.108 R27 0.072 0.018 0.151 0.144
R7 0.120 0.060 0.151 0.064 R28 0.196 0.033 0.229 0.089
R8 0.055 0.105 0.199 0.083 R29 0.056 0.145 0.128 0.054
R9 0.045 0.113 0.144 0.080 R30 0.043 0.159 0.255 0.084
R10 0.129 0.085 0.145 0.129 R31 0.081 0.028 0.176 0.023
R11 0.050 0.154 0.287 0.094 R32 0.094 0.021 0.250 0.022
R12 0.059 0.084 0.099 0.070 R33 0.082 0.047 0.178 0.019
R13 0.103 0.005 0.239 0.003 R34 0.063 0.043 0.218 0.029
R14 0.078 0.030 0.122 0.055 R35 0.090 0.041 0.152 0.037
R15 0.072 0.091 0.238 0.004 R36 0.098 0.096 0.343 0.006
R16 0.047 0.039 0.157 0.055 R37 0.075 0.039 0.316 0.016
R17 0.058 0.026 0.374 0.048 R38 0.093 0.020 0.215 0.011
R18 0.134 0.003 0.181 0.008 R39 0.119 0.010 0.294 0.006
R19 0.078 0.098 0.139 0.048 R40 0.173 0.013 0.203 0.019
R20 0.060 0.030 0.234 0.044 R41 0.087 0.030 0.246 0.005
R21 0.115 0.051 0.158 0.040 R42 0.090 0.008 0.301 0.007
OF (s) = 6.084 s

In the subsequent phase, aimed at assessing and comparing the effectiveness of the proposed protection scheme, particularly in addressing uncertainties about demand load and generation, the fuzzy Monte Carlo technique, as detailed in a previous case study, was employed to analyze the input parameters of the current investigation. To visually depict these uncertainties, PDFs for both active and reactive power of load demands at each bus are presented. Figure 15a illustrates the fluctuation of active power load demand across numerous iterations, offering valuable insights into its temporal variability. Furthermore, the 3D plot in Figure 15b shows the PDF of the active power load demand for each bus. Each curve in this plot represents the PDF of the active power load demand at a specific bus, offering a graphical depiction of the uncertainties associated with the active power load demand. Similarly, Figure 16a illustrates the dynamic fluctuation of reactive power load demand across diverse iterations, offering valuable insights into its temporal variability. Concurrently, the 3D plot in Figure 16b delineates the PDF of the reactive power load demand for each bus within the test network. These visual representations serve to elucidate the inherent uncertainties associated with load demand across various buses within the network, thus enhancing the comprehensiveness and reliability of modeling and analysis.

Figure 15.

Figure 15

Variation in and PDF of Active Power Load Demand in IEEE-30 Bus system.

Figure 16.

Figure 16

Variation in and PDF of Reactive Power Load Demand in IEEE-30 Bus system.

Conversely, uncertainties are also present in the output power of DG sources. Figure 17 depicts the fluctuations in DG source output power across numerous iterations, providing valuable insights into the variability of their power generation. Each subplot in the figure corresponds to the output power of a specific DG source through iterations, effectively highlighting the uncertainties inherent in the DG source power generation. These visual representations offer a comprehensive understanding of the variability in DG source power output, contributing to a more nuanced analysis of the system.

Figure 17.

Figure 17

Variation in DG Outputs Across MCS Iterations in IEEE-30 Bus system.

The optimal relay settings derived through the fuzzy Monte Carlo technique consider the probabilistic distribution of fault currents and operating conditions. Incorporating strategies that acknowledge the uncertainty, the coordination of dual-setting DOCRs is fine-tuned to mitigate the risks associated with potential faults and disturbances in the distribution system. An analysis of PDFs for TMS and PS was conducted for both forward and reverse relays. Moreover, combined PDFs showing the optimal TMS and PS settings were plotted, highlighting the maximum probability density with their corresponding optimal configurations. These PDFs offer valuable insight into the spread of optimal relay settings across networks. Through examination, the optimal TMS and PS values for forward-direction relays were determined, as depicted in Figure 18. Similarly, Figure 19 illustrates the optimal TMS and PS values for reverse-direction relays.

Figure 18.

Figure 18

PDF and combined PDF of optimal setting for forward relays in IEEE-30 Bus system.

Figure 19.

Figure 19

PDF and combined PDF of optimal setting for reverse relays in IEEE-30 Bus system.

As illustrated in Figure 18 and Figure 19, the optimized values for the TMS and PS maximize the PDF while considering uncertainties, are notably lower than the TMS and PS values when uncertainties are not accounted for, as indicated in Table 8. This observation underscores the critical importance of integrating uncertainties into relay settings, particularly in scenarios where there are fluctuations in the input data, such as load and generation uncertainties. This emphasizes the imperative need to address uncertainties to ensure a more precise and dependable relay coordination amid varying the system conditions. Figure 20 and Figure 21 present boxplot graphical representations of relay operation times in states in which uncertainties are considered and not considered, respectively. In Figure 20, all CTI ranges (boxplots) of relay pairs in the state considering uncertainties fulfill the threshold of CTImin=0.2 (highlighted by a red line). However, in Figure 21, relay pairs such as RP.12, RP.13, RP.14, RP.25, RP.26, and RP.59 fail to meet the minimum value of CTImin=0.2 when the uncertainties are not factored in.

Figure 20.

Figure 20

Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting Under Uncertainty.

Figure 21.

Figure 21

Boxplot of CTI Variation Across MCS Iterations for Relay Pairs, with Optimal Setting without considering uncertainty.

5. Conclusions

In today’s evolving power networks, the integration of distributed generation resources introduces a unique set of challenges in ensuring reliable and effective protection. As discussed in this paper, optimizing the coordination of directional overcurrent relays (DOCRs) become increasingly complex when confronted with uncertainties stemming from both distributed generation (DG) outputs and load consumption patterns. Consequently, this study underscores the importance of integrating uncertainties into the optimization process of dual-setting DOCRs. By employing advanced techniques, such as the fuzzy Monte Carlo method, it is demonstrated that considering uncertainties in relay settings significantly impacts the resulting values of the Time Multiplier Setting (TMS) and Pickup Current Setting (PS). The analysis, as evidenced by the simulation results, indicates that optimized relay settings, when accounting for uncertainties, tend to be notably lower than those obtained without considering uncertainties. This observation highlights the necessity of incorporating uncertainties, especially in environments where variations in input data, such as load and generation uncertainties prevail. The fuzzy Monte Carlo method plays a critical role in this study by simulating the various uncertainties associated with DG and load patterns. These simulations generate a range of possible scenarios, reflecting the real-world variability of power networks. To efficiently handle and optimize these scenarios, the ant lion optimization (ALO) Algorithm is employed. The ALO algorithm is particularly suited for this task due to its robustness in finding optimal solutions in complex, multidimensional search spaces. By integrating the results from the fuzzy Monte Carlo simulations with the ALO algorithm, the study ensures that the optimization process accounts for the inherent uncertainties, thereby enhancing the reliability and accuracy of the relay settings. The findings emphasize the pivotal role of uncertainty-aware strategies in enhancing the accuracy and reliability of relay coordination, thereby ensuring robust protection against potential faults and disturbances in distribution systems. Furthermore, graphical representations illustrate the tangible benefits of accounting for uncertainties in relay operation times. The disparities observed between relay pairs when uncertainties are considered and when they are not underscore the potential risks associated with disregarding uncertainties in relay settings. In essence, this study advocates for a paradigm shift towards embracing uncertainty-aware approaches in the design and optimization of relay settings. By doing so, the power system can better adapt to its dynamic nature, ultimately enhancing its resilience and reliability in the face of uncertain operating conditions.

Acknowledgments

The authors would like to acknowledge that this paper is submitted in partial fulfilment of the requirements for the PhD degree at Yildiz Technical University.

Abbreviations

The following abbreviations are used in this manuscript:

ADN Active distribution networks.
ALO Ant lion optimizer algorithm.
CTI Coordination time interval.
DOCRs Directional overcurrent relays.
DG Distributed generation.
DS-DOCRs Dual-setting directional overcurrent relays.
MCS Monte Carlo simulation.
MGs Microgrids.
OLF Overload factor.
OCR Overcurrent relay.
PS pickup (plug) setting.
PFMC Probabilistic model of fuzzy Monte Carlo.
PDF Probability density function.
P/B Primary/backup.
SGs Smart grids.
TMS Time multiplier setting.

Author Contributions

F.A.-B.: Conceptualization, methodology, experimentation, validation, formal analysis, investigation, data curation, writing—original draft, writing—review and editing, and visualization. A.İ.: Conceptualization, methodology, validation, investigation, resources, writing—original draft, writing—review and editing, visualization, supervision, and project administration. All authors have read and agreed to the published version of the manuscript.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Data are contained within the article.

Conflicts of Interest

The authors declare no conflicts of interest.

Funding Statement

This research received no external funding.

Footnotes

Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

References

  • 1.Kida A.A., Rivas A.E.L., Gallego L.A. An improved simulated annealing–linear programming hybrid algorithm applied to the optimal coordination of directional overcurrent relays. Electr. Power Syst. Res. 2020;181:106197. doi: 10.1016/j.epsr.2020.106197. [DOI] [Google Scholar]
  • 2.ElSayed S.K., Elattar E.E. Hybrid Harris hawks optimization with sequential quadratic programming for optimal coordination of directional overcurrent relays incorporating distributed generation. Alex. Eng. J. 2021;60:2421–2433. doi: 10.1016/j.aej.2020.12.028. [DOI] [Google Scholar]
  • 3.Habib K., Lai X., Wadood A., Khan S., Wang Y., Xu S. An improved technique of Hybridization of PSO for the Optimal Coordination of Directional Overcurrent Protection Relays of IEEE bus system. Energies. 2022;15:3076. doi: 10.3390/en15093076. [DOI] [Google Scholar]
  • 4.Wang Y., Habib K., Wadood A., Khan S. The hybridization of PSO for the optimal coordination of directional overcurrent protection relays of the IEEE bus system. Energies. 2023;16:3726. doi: 10.3390/en16093726. [DOI] [Google Scholar]
  • 5.Godwal S.D., Pandya K.S., Vora S.C., Mehta C.R., Rajput V.R. Optimal overcurrent relay coordination for interconnected power systems: A proper approach and improved technique. e-Prime-Adv. Electr. Eng. Electron. Energy. 2023;5:100248. doi: 10.1016/j.prime.2023.100248. [DOI] [Google Scholar]
  • 6.Abdelfattah W., Nagy A., Salama M., Lotfy M.E., Abdelhadi H. Artificial intelligence based optimal coordination of directional overcurrent relay in distribution systems considering vehicle to grid technology. Ain Shams Eng. J. 2024;15:102372. doi: 10.1016/j.asej.2023.102372. [DOI] [Google Scholar]
  • 7.Biswal S., Sharma N.K., Samantaray S. Optimal overcurrent relay coordination scheme for microgrid; Proceedings of the 2020 21st National Power Systems Conference (NPSC); Gandhinagar, India. 17–19 December 2020; pp. 1–6. [Google Scholar]
  • 8.Patnaik B., Mishra M., Bansal R.C., Jena R.K. AC microgrid protection—A review: Current and future prospective. Appl. Energy. 2020;271:115210. doi: 10.1016/j.apenergy.2020.115210. [DOI] [Google Scholar]
  • 9.Beder H., Mohandes B., El Moursi M.S., Badran E.A., El Saadawi M.M. A new communication-free dual setting protection coordination of microgrid. IEEE Trans. Power Deliv. 2020;36:2446–2458. doi: 10.1109/TPWRD.2020.3041753. [DOI] [Google Scholar]
  • 10.Foqha T., Alsadi S., Omari O., Refaat S.S. Optimization Techniques for Directional Overcurrent Relay Coordination: A Comprehensive Review. IEEE Access. 2023;12:1952–2006. doi: 10.1109/ACCESS.2023.3347393. [DOI] [Google Scholar]
  • 11.Tiwari R., Singh R.K., Choudhary N.K. Coordination of dual setting overcurrent relays in microgrid with optimally determined relay characteristics for dual operating modes. Prot. Control Mod. Power Syst. 2022;7:1–18. doi: 10.1186/s41601-022-00226-1. [DOI] [Google Scholar]
  • 12.Tiwari R., Singh R.K., Choudhary N.K. Optimal coordination of dual setting directional over current relays in microgrid with different standard relay characteristics; Proceedings of the 2020 IEEE 9th Power India International Conference (PIICON); Sonepat, India. 28 February–1 March 2020; pp. 1–6. [Google Scholar]
  • 13.Singh D.K., Sarangi S., Singh A.K., Mohanty S.R. Coordination of dual-setting overcurrent and distance relays for meshed distribution networks with distributed generations and dynamic voltage restorer. Smart Sci. 2023;11:135–153. doi: 10.1080/23080477.2022.2046943. [DOI] [Google Scholar]
  • 14.Martin K.T., Marchesan A.C., de Araújo O.C.B., Cardoso G., da Silva M.F. Mixed integer linear programming applied to adaptive directional overcurrent protection considering N-1 contingency. IEEE Trans. Ind. Appl. 2023;59:2807–2821. doi: 10.1109/TIA.2023.3238004. [DOI] [Google Scholar]
  • 15.Langazane S.N., Saha A.K. Effects of particle swarm optimization and genetic algorithm control parameters on overcurrent relay selectivity and speed. IEEE Access. 2022;10:4550–4567. doi: 10.1109/ACCESS.2022.3140679. [DOI] [Google Scholar]
  • 16.Akdag O., Yeroglu C. Optimal directional overcurrent relay coordination using MRFO algorithm: A case study of adaptive protection of the distribution network of the Hatay province of Turkey. Electr. Power Syst. Res. 2021;192:106998. doi: 10.1016/j.epsr.2020.106998. [DOI] [Google Scholar]
  • 17.Wong J.Y.R., Tan C., Che H.S. Selectivity problem in adaptive overcurrent protection for microgrid with inverter-based distributed generators (IBDG): Theoretical investigation and HIL verification. IEEE Trans. Power Deliv. 2021;37:3313–3324. doi: 10.1109/TPWRD.2021.3126897. [DOI] [Google Scholar]
  • 18.Alasali F., El-Naily N., Saidi A.S., Itradat A., Holderbaum W., Mohamed F.A. Highly sensitive multifunction protection coordination scheme for improved reliability of power systems with distributed generation (PVs) IET Renew. Power Gener. 2023;17:3025–3048. doi: 10.1049/rpg2.12820. [DOI] [Google Scholar]
  • 19.Barranco-Carlos A., Orozco-Henao C., Marín-Quintero J., Mora-Flórez J., Herrera-Orozco A. Adaptive protection for active distribution networks: An approach based on fuses and relays with multiple setting groups. IEEE Access. 2023;11:31075–31091. doi: 10.1109/ACCESS.2023.3261827. [DOI] [Google Scholar]
  • 20.Aghaei H., Hashemi-Dezaki H. Optimal communication-aided protection of meshed smart grids considering stability constraints of distributed generations incorporating optimal selection of relay characteristics. IET Renew. Power Gener. 2022;16:2313–2337. doi: 10.1049/rpg2.12525. [DOI] [Google Scholar]
  • 21.Purwar E., Singh S.P., Vishwakarma D.N. A robust protection scheme based on hybrid pick-up and optimal hierarchy selection of relays in the variable DGs-distribution system. IEEE Trans. Power Deliv. 2019;35:150–159. doi: 10.1109/TPWRD.2019.2929755. [DOI] [Google Scholar]
  • 22.Jamali S., Borhani-Bahabadi H. Protection method for radial distribution systems with DG using local voltage measurements. IEEE Trans. Power Deliv. 2018;34:651–660. doi: 10.1109/TPWRD.2018.2889895. [DOI] [Google Scholar]
  • 23.Shen S., Wang H., Jiang K., Zhu L., Gan C., Markham P.N., Liu Y., He B. Regional area protection scheme for modern distribution system. IEEE Trans. Smart Grid. 2018;10:5416–5426. doi: 10.1109/TSG.2018.2882141. [DOI] [Google Scholar]
  • 24.George S.P., Ashok S. Forecast-based overcurrent relay coordination in wind farms. Int. J. Electr. Power Energy Syst. 2020;118:105834. doi: 10.1016/j.ijepes.2020.105834. [DOI] [Google Scholar]
  • 25.Balyith A.A., Sharaf H.M., Shaaban M., El-Saadany E.F., Zeineldin H.H. Non-communication based time-current-voltage dual setting directional overcurrent protection for radial distribution systems with DG. IEEE Access. 2020;8:190572–190581. doi: 10.1109/ACCESS.2020.3029818. [DOI] [Google Scholar]
  • 26.Sarwagya K., Nayak P.K., Ranjan S. Optimal coordination of directional overcurrent relays in complex distribution networks using sine cosine algorithm. Electr. Power Syst. Res. 2020;187:106435. doi: 10.1016/j.epsr.2020.106435. [DOI] [Google Scholar]
  • 27.Ghotbi-Maleki M., Chabanloo R.M., Zeineldin H.H., Miangafsheh S.M.H. Design of setting group-based overcurrent protection scheme for active distribution networks using MILP. IEEE Trans. Smart Grid. 2020;12:1185–1193. doi: 10.1109/TSG.2020.3027371. [DOI] [Google Scholar]
  • 28.Vijayachandran V.V., Shenoy U.J. Implementation of support-vector-machine-based relay coordination scheme for distribution system with renewables. IEEE J. Emerg. Sel. Top. Ind. Electron. 2020;2:324–333. doi: 10.1109/JESTIE.2020.3014875. [DOI] [Google Scholar]
  • 29.Abbaspour E., Fani B., Sadeghkhani I., Alhelou H.H. Multi-agent system-based hierarchical protection scheme for distribution networks with high penetration of electronically-coupled DGs. IEEE Access. 2021;9:102998–103018. doi: 10.1109/ACCESS.2021.3098387. [DOI] [Google Scholar]
  • 30.Hong L., Rizwan M., Wasif M., Ahmad S., Zaindin M., Firdausi M. User-defined dual setting directional overcurrent relays with hybrid time current-voltage characteristics-based protection coordination for active distribution network. IEEE Access. 2021;9:62752–62769. doi: 10.1109/ACCESS.2021.3074426. [DOI] [Google Scholar]
  • 31.Ataee-Kachoee A., Hashemi-Dezaki H., Ketabi A. Optimized adaptive protection coordination of microgrids by dual-setting directional overcurrent relays considering different topologies based on limited independent relays’ setting groups. Electr. Power Syst. Res. 2023;214:108879. doi: 10.1016/j.epsr.2022.108879. [DOI] [Google Scholar]
  • 32.El-Naily N., Saad S.M., Elhaffar A., Zarour E., Alasali F. Innovative Adaptive Protection Approach to Maximize the Security and Performance of Phase/Earth Overcurrent Relay for Microgrid Considering Earth Fault Scenarios. Electr. Power Syst. Res. 2022;206:107844. doi: 10.1016/j.epsr.2022.107844. [DOI] [Google Scholar]
  • 33.Entekhabi-Nooshabadi A.M., Hashemi-Dezaki H., Taher S.A. Optimal microgrid’s protection coordination considering N-1 contingency and optimum relay characteristics. Appl. Soft Comput. 2021;98:106741. doi: 10.1016/j.asoc.2020.106741. [DOI] [Google Scholar]
  • 34.Torshizi N.H., Najafi H., Noghabi A.S., Sadeh J. An adaptive characteristic for overcurrent relays considering uncertainty in presence of distributed generation. Int. J. Electr. Power Energy Syst. 2021;128:106688. doi: 10.1016/j.ijepes.2020.106688. [DOI] [Google Scholar]
  • 35.Sadeghi M.H., Dastfan A., Damchi Y. Robust and adaptive coordination approaches for co-optimization of voltage dip and directional overcurrent relays coordination. Int. J. Electr. Power Energy Syst. 2021;129:106850. doi: 10.1016/j.ijepes.2021.106850. [DOI] [Google Scholar]
  • 36.Alasali F., El-Naily N., Saidi A.S., Itradat A., Saad S.M., Holderbaum W. An advanced dual-setting protection scheme for microgrid resilience based on nonstandard tripping characteristics of overcurrent relays. Electr. Power Syst. Res. 2023;225:109869. doi: 10.1016/j.epsr.2023.109869. [DOI] [Google Scholar]
  • 37.Momesso A.E., Bernardes W.M.S., Asada E.N. Adaptive directional overcurrent protection considering stability constraint. Electr. Power Syst. Res. 2020;181:106190. doi: 10.1016/j.epsr.2019.106190. [DOI] [Google Scholar]
  • 38.Aazami R., Esmaeilbeigi S., Valizadeh M., Javadi M.S. Novel intelligent multi-agents system for hybrid adaptive protection of micro-grid. Sustain. Energy Grids Netw. 2022;30:100682. doi: 10.1016/j.segan.2022.100682. [DOI] [Google Scholar]
  • 39.Merabet O., Kheldoun A., Bouchahdane M., Eltom A., Kheldoun A. An adaptive protection coordination for microgrids utilizing an improved optimization technique for user-defined DOCRs characteristics with different groups of settings considering N-1 contingency. Expert Syst. Appl. 2024;248:123449. doi: 10.1016/j.eswa.2024.123449. [DOI] [Google Scholar]
  • 40.Hong Y.-Y., Yu C.-W., Lee Y.-D., Jiang J.-L., Wang S.-S. Coordination of protective relays in distribution systems considering uncertainty caused by renewables and demands based on orthogonal experiments. Sustain. Energy Grids Netw. 2023;36:101206. doi: 10.1016/j.segan.2023.101206. [DOI] [Google Scholar]
  • 41.Aien M., Hajebrahimi A., Fotuhi-Firuzabad M. A comprehensive review on uncertainty modeling techniques in power system studies. Renew. Sustain. Energy Rev. 2016;57:1077–1089. doi: 10.1016/j.rser.2015.12.070. [DOI] [Google Scholar]
  • 42.Yazdaninejadi A., Nazarpour D., Talavat V. Optimal coordination of dual-setting directional over-current relays in multi-source meshed active distribution networks considering transient stability. IET Gener. Transm. Distrib. 2019;13:157–170. doi: 10.1049/iet-gtd.2018.5431. [DOI] [Google Scholar]
  • 43.Aghdam T.S., Karegar H.K., Abbasi A. Discussion on “Optimal Protection Coordination for Meshed Distribution Systems with DG Using Dual Setting Relays”. IEEE Trans. Smart Grid. 2016;7:1756. doi: 10.1109/TSG.2016.2548878. [DOI] [Google Scholar]
  • 44.Sharaf H.M., Zeineldin H.H., El-Saadany E. Protection coordination for microgrids with grid-connected and islanded capabilities using communication assisted dual setting directional overcurrent relays. IEEE Trans. Smart Grid. 2016;9:143–151. doi: 10.1109/TSG.2016.2546961. [DOI] [Google Scholar]
  • 45.Hatata A.Y., Lafi A. Ant lion optimizer for optimal coordination of DOC relays in distribution systems containing DGs. IEEE Access. 2018;6:72241–72252. doi: 10.1109/ACCESS.2018.2882365. [DOI] [Google Scholar]
  • 46.Al-Bhadely F., İnan A. Improving Directional Overcurrent Relay Coordination in Distribution Networks for Optimal Operation Using Hybrid Genetic Algorithm with Sequential Quadratic Programming. Energies. 2023;16:7031. doi: 10.3390/en16207031. [DOI] [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Data Availability Statement

Data are contained within the article.


Articles from Sensors (Basel, Switzerland) are provided here courtesy of Multidisciplinary Digital Publishing Institute (MDPI)

RESOURCES