Floating photovoltaic systems: photovoltaic cable submersion testing and potential impacts

Ricardo Rebelo 1,a, Luis FIALHO 1,2,b, Maria Helena Novais 1,2,c
PMCID: PMC11459181  PMID: 39380799

Version Changes

Revised. Amendments from Version 1

The changes made in this version aim to address the reviewers' comments. A grammar review was conducted, and decimal places and superscripts were standardized throughout the article. Captions for the equipment were added to Figure 5, the conclusion was revised to make it more concise, and a section titled 'Future Work' was created after the conclusions. The text in the results discussion section was also improved and reviewed.

Abstract

Background

Floating photovoltaics (FPV) is an emerging technology that is gaining attention worldwide. However, little information is still available on its possible impacts in the aquatic ecosystems, as well as on the durability of its components. Therefore, this work intends to provide a contribution to this field, analysing possible obstacles that can compromise the performance of this technology, adding to an increase of its reliability and assessing possible impacts.

The problem under study is related to the potential submersion of photovoltaic cables, that can lead to a degradation of its electrical insulation capabilities and, consequently, higher energy production losses and water contamination.

Methods

In the present study, the submersion of photovoltaic cables (with two different insulation materials) in freshwater and artificial seawater was tested, in order to replicate real life conditions, when FPV systems are located in reservoirs or in the marine environment. Electrical insulation tests were carried out weekly to assess possible cable degradation, the physical-chemical characteristics of the water were also periodically monitored, complemented by analysis to detect traces of copper and microplastics in the water.

Results

The results showed that the submersion of photovoltaic cables with rubber sheath in saltwater can lead to a cable accelerated degradation, with reduction of its electrical insulation and, consequently, copper release into the aquatic environment.

Conclusions

The test results pointed a probable relationship between submersion of cables with rubber outer shell and water freezing temperatures and the occurrence of accelerated degradation of the cable insulation layer. Reduced insulation resistance values were measured in this cable type after the occurrence of such temperatures, both in salt and freshwater, the cable presented visible exterior degradation signs. For this case copper residues were detected in the water.

Keywords: Electrical Insulation, Floating PV, Solar Energy, Water Quality

Introduction

The world population is growing, causing an increase in the use of resources needed to maintain the living standard of the modern societies 1 . The electricity consumption is increasing due to the electrification of various sectors, e.g. electric vehicles 2 . Nearly 95% of the electricity by 2050 would need to be low-carbon, a deep transformation, to achieve the global temperature change below 2°C 3 . The answer to this challenge is the use of renewable energies for the production of electricity, minimizing its ecological footprint and enabling the decarbonization of the electric system 4 . Solar energy can provide an important share of clean electricity, either through decentralized energy production, generating energy closer to the consumption points, or with centralized power production 4 .

The floating photovoltaic (FPV) systems allow the usage of a potentially unoccupied surface, not competing with other applications such as agriculture or urban development, particularly important factors in countries with high population density. FPV systems can also benefit from coexistence with other renewable energy sources ( e.g., hydropower), taking advantage of existing infrastructures, such as electric power transmission lines, electric substations or energy storage systems (pumped-storage hydroelectricity, batteries, etc.) 5 .

In the current market there are different types of floating photovoltaic platforms from different suppliers, but in general the electrical components (modules, cables, inverters, electrical protection devices, etc.) are the same as those used in conventional PV applications on land. In general, the photovoltaic modules are installed on a plastic floating platform which makes the system buoyant 6 . These floating systems are installed with some degrees of freedom, in order to accommodate variations in the water level and wave motion, with stability given to the platforms with a mooring and anchoring setup 7 .

The literature about potential environmental impacts of these systems is reduced, however, some of the potential impacts on aquatic ecosystems that could arise include 5 : 1) reduced sunlight on the reservoir / increased heat generated — can induce changes on the water column characteristics and/or the mixing patterns of the reservoir, uneven surface heating, generate potential heat plume, reduce littoral plant/algae growth, the biota in the limnetic zones and the primary production, increase algae decomposition rate and the oxygen demand at the bottom of the reservoir and the shading of habitats and species; 2) reduced wind and water flow — can increase stratification and limit water mixing, reduce dissolved oxygen (DO) levels, depending on the reservoir covered area/ total area ratio; 3) reduced flow in the areas surrounding the arrays — can increase the sedimentation; 4) leaching of chemicals from the materials / use or accidental release of oil, lubricants from boats and detergents used to clean panels — can impact the water quality and aquatic biota, and accumulate in the sediments; 5) FPV components and anchoring in the littoral and benthic zones (mooring systems, electric cables) — can destroy benthic habitats, cause direct mortality and increase the turbidity; 6) exposure to electromagnetic fields from electric cables on the bottom and littoral zones — may have direct effects on macroinvertebrates and fish.

Therefore, it is necessary to deepen FPV systems testing and study, in order to enhance the understanding of their operation effects and optimize their use through good practices.

Furthermore, despite showing resilience to extreme phenomena of nature, some news has been published about catastrophic failures of these systems 8, 9 , and FPV systems are still perceived as relatively high risk.

The first application of a floating photovoltaic system was in 2007, in Aichi, Japan, with an installed power of 20 kWp 10 . In 2008, the first commercial floating photovoltaic platform was built in a water reservoir in California, with 175 kWp 10 .

After 2008, new FPV plants were installed in countries like Japan, Korea, and the United States of America. Recently, China entered this market and currently dominates the FPV sector regarding total installed capacity 10 .

According to the data collected systematically by the authors, published in multiple news items by the media, in Europe, this technology has had a slow growth, accelerating in the last years and currently the total installed capacity is 47.20 MW ( Figure 1, Figure 2). Portugal may top this list when the construction of 50 MW in the Alentejo region is concluded, estimated to be commissioned by the end of 2023, thus increasing the total European installed capacity to 97.201 MW.

Figure 1. Floating photovoltaic power installed in Europe 1129 .

Figure 1.

Figure 2. Evolution on floating photovoltaic installed capacity in Europe 1129 .

Figure 2.

In this work, possible submersion of photovoltaic cables in water is addressed. The photovoltaic cables, that can be fully or partially submerged, will be exposed to freshwater or salt water, ice, a high humidity environment and solar radiation, which can lead to cable degradation and loss of electrical insulation. Submersion of cables or connectors can be caused by low clearance from the water surface as well as mismatch in module cable length and floats dimension, waves due to wind or a boat passing nearby.

The accelerated degradation of the photovoltaic cables or connectors can cause its failure, reducing the electric insulation characteristics or causing problems to the power line communications. In addition, individual insulation failures can often be difficult to detect in large PV systems and/or PV strings, with added difficulty related to performing operation and maintenance (O&M) tasks in floating plants. In case of electric insulation failure, the photovoltaic inverters are able to detect it and will stop, isolating the faulty system. This leads to increased plant downtime, loss of energy generation and lower overall performance ratios.

The cable tests follow the EN 50618, regarding electric cables for photovoltaic systems, and EN 50395 standards, focused on electrical test methods for low voltage energy cables 30, 31 .

This work intends to evaluate if the submergence of photovoltaic cables can lead to its accelerated degradation, either in freshwater or in saltwater. The degradation of the insulation layers of these cables, can lead to the direct water contact and exposure of their conductors, with potential leaching of contaminants (metals, microplastics) to the aquatic environment. This study also intends to evaluate the possibility of the occurrence of this environmental contamination.

Methodology

Experimental description

Currently, there are multiple types of photovoltaic cables. The conductor material is generally copper or aluminium, either solid or stranded, allowing very good conductivity, malleability, and ductility. The cable cross-sectional area and thickness of insulating layers depends on its current rating. Solar DC cables are intended for outdoor use and single-core cables with double insulation have proven to be a practical solution with high reliability in land installed PV plants 7 .

Among the various requirements for cable selection in the photovoltaic industry, the following are often used: good weather, ozone and UV-resistance; large temperature operating range; able to withstand mechanical stress; abrasion-resistance; acid and base pH resistance; flame retardant and halogen free; high dielectric strength; small outside diameter (space-saving).

After consulting several suppliers of photovoltaic cables, two types of photovoltaic cables frequently used in photovoltaic installations (including FPV plants) in Portugal were selected, depicted in Table 1.

Table 1. Photovoltaic cables.

Cable Conductor Insulation and
outer sheath
Section
Cable 1 Tinned copper grade5
Compliant EN 60228 /
IEC 60228
Cross-linked
polyethylene
(XLPE)
4 mm 2
Cable 2 Class 5 annealed and
tinned electrolytic copper
wires
Compliant EN 60228 /
IEC 60228
Rubber 4 mm 2

Six large tanks were used to simulate freshwater and marine environments, with a radius of 0.75m, 0.3m in height and a total volume of 0.53m 3, made of high-density polyethylene POLYCHOC™ with anti UV treatment, and a food safe rating.

The six tanks were installed outdoors, filled with water, and equipped with a water mixing and oxygenation system in order to prevent algae growth and bacterial organic matter degradation. This system is composed by an air compressor and a compressed air distribution network for the six tanks. A timer system controller was installed, performing 10 daily cycles of 20 minutes, from 9:00 until 18:00. The experimental setup is presented in detail in Table 2.

Table 2. Experimental setup distribution.

Tank Photovoltaic
cable
Water
1 Cable 1 Fresh
2 Cable 1 Salt
3 Cable 2 Fresh
4 Cable 2 Salt
5 (control) - Fresh
6 (control) - Salt

The experimental test period was from 16/10/2020 to 07/01/2021. The outdoor distribution of the test tanks is illustrated in Figure 3. This outdoor test setup was installed in the experimental campus of the University of Évora (Polo da Mitra, GPS coordinates: 38°31'53.3"N, 8°00'43.3"W). The test site is framed in a rural context, with characteristics similar to the framing of these FPV facilities (for instance the FPV 1 MWp plant in Cuba-Este reservoir, GPS coordinates: 38°10'07.2"N 7°50'51.2"W), whether climatic or regarding the surrounding ecosystem, having no major sources of atmospheric pollution or contamination in its neighbourhood.

Figure 3. Experimental setup with the six water tanks.

Figure 3.

The air compressor and timer system are installed inside the red container (top of the image).

To simulate freshwater systems, tanks 1, 3 and 5 were filled with ca. 500 L of tap water, and for marine environments simulation, ca. 18kg of marine salt was added to the tanks 2, 4 and 6, to achieve a salinity level of about 3.5% ( Figure 4a). The salinity value was monitored using a TROLL 9500 PROFILER XP multi parametric probe8 ( Figure 4b).

Figure 4.

Figure 4.

a) Preparation of saltwater; b) physical-chemical characterization with the multiparametric probe.

Weather and ambient variables were continuously monitored by a meteorological station ( Figure 5) installed 100m away from the water tanks, also in the open field 32 . This station is equipped with a two-axis fully automatic sun tracker SOLYS2, with two CMP11 pyranometers to monitor global and diffuse solar radiation, one CHP1 pyrheliometer to measure direct solar radiation, one air temperature and relative humidity sensor and one precipitation sensor. This station is presented in Figure 5.

Figure 5. Onsite meteorological station.

Figure 5.

a) two pyranometers; b) pyrheliometer; c) air temperature and relative humidity sensor; d) precipitation sensor.

Electrical insulation tests

The electrical insulation tests of photovoltaic cables follow a set of standards, namely EN 50618 and EN 50395 30, 31 . After purchasing the cables from the supplier, and before starting the submersion test, an initial dielectric measurement was made. Each cable sample under test is 5 meters long. Special care was taken so that the ends of each cable under test were never submerged, in order to avoid the entry of water or absorption at these points, as well as the contact of the exposed conductor at the ends with water.

For the purpose of this electric tests, a voltage source equipment (model EA-PSI 9000 T) was used, as well as a photovoltaic and electrical installation tester ( Metrel MI 3109 EurotestPV Lite) to measure the insulation resistance. For safety, a galvanic isolation device ( Metrel A 1384 PV Safety Probe) was also used between the electrical installer tester and the cable being measured. For measuring the cable insulation resistance, the following procedure was used:

  • 1.

    Visual inspection of each cable, checking for any fault or degradation of the dielectric layer.

  • 2.

    Measuring of the cable resistance with the electric tester, applying a voltage of 100 V. If the resistance result is above the minimum limit, the next step was carried out. This initial step is important in order to assess the safety conditions of the cable and if it is safe to proceed in the next steps of the test.

  • 3.

    As indicated by the test procedure in the standards, it is necessary to apply a voltage between 80-500 V for one minute to the photovoltaic cable submerged in water, in a small test tank, where the measurements were periodically made. For this, the voltage source was used to apply 100 V to the cable conductor and the water through a solid copper bar ( Figure 6b).

  • 4.

    Finally, the cable resistance is measured with the electric tester equipment ( Figure 6a). After the resistance is measured, the cables were submerged again in the outdoor tanks. Electrical insulation tests were carried out once a week for 12 weeks.

Figure 6.

Figure 6.

a) Resistance measurement with the I-V curve tracer; b) application of 100 V with the voltage source.

Water physicochemical characterization

A physicochemical characterization of the water was carried out weekly, measuring key parameters with the multi parametric probe (TROLL 9500 PROFILER XP), including water temperature (T, °C), electrical conductivity (EC, µS/cm), salinity (Sal. mg L -1), total dissolved solids (TDS, mg L -1), pH, oxidation-reduction potential (ORP, mV) and dissolved oxygen (DO, % of O2 saturation and mg L -1). Whenever the volume of water was higher than the initial volume (due to the precipitation events), the salinity values were adjusted, removing water, and adding salt. To evaluate potential impact in the water or aquatic ecosystems due to the cable degradation, analysis to detect the presence of copper in the water through flame atomic absorption spectroscopy, using the SMEWW 3111B method 33 were carried out at the Water Laboratory of the University of Évora. The copper concentration in the sample is determined by flame atomic absorption spectrometry, where a sample is aspirated into a flame and atomized. A light beam is directed through the flame, into a monochromator, and onto a detector that measures the light spectrum by the atomized element in the flame 33 .

The presence of microplastics in the water was also monitored, with the samples being filtered by a 20 µm mesh and analysed by Fourier-transform infrared spectroscopy (FTIR) with a Perkin Elmer Spotlight 400.

These analysis (copper detection and microplastics analysis) were performed at three different times: 1) initially with the water used to fill the tanks; 2) after 6 weeks of cable submersion and 3) at the end of the test period, with 12 weeks of cable submersion.

Results and discussion

Electrical insulation tests results

In the first measurement, all cables reached the maximum measurement limit of the device, 200 MΩ. The first cable to record electrical insulation losses was cable 2, in salt water in the eighth week, with a resistance value of 27 MΩ, and in the same week the presence of copper was detected with a significant concentration ( Table 3). This decrease in the resistance value occurred when the air temperature dropped below 0°C for the first time in that year, as shown in Figure 7. The cable 2 submerged in saltwater presented resistance values below 200 MΩ during the test period, nevertheless these resistance values were higher than 2.9 MΩ, the minimum insulation resistance value for a 4 mm2 cross-section cable. Cable 2 (freshwater) also presented one low resistance value (21 MΩ at 28/12/2020), recovering to a higher value the next week. Cable 1, either submerged in freshwater, or in saltwater, never presented lower electrical resistance values ( Figure 7).

Figure 7. Air temperature and electric insulation resistance over time.

Figure 7.

Table 3. Copper concentration in water over time [mg L -1].

16/10/2020 03/12/2020 11/12/2020 11/01/2021 29/01/2021
Initial sample - water used to fill the tanks 0.005 0.005 0.005 - -
Tank 1 - Freshwater 0.005 0.015 - - 0.006
Tank 2 - Saltwater 0.005 0.008 - - 0.011
Tank 3 - Freshwater 0.005 0.017 - 0.005 -
Tank 4 - Saltwater 0.005 0.052 0.012 0.005 -
Tank 5 – Freshwater (control) 0.005 0.014 - - 0
Tank 6 – Saltwater (control) 0.005 0.009 - - 0

The cable 2 submerged in saltwater showed visual signs of degradation of the dielectric layer, with increased volume at that location, indicating potential absorption of salt water in the outer layer, as depicted in Figure 8. A possible explanation is related to the occurrence of night temperatures below 0°C and the freezing of the salt water absorbed by the outer layer, with consequent expansion of its volume and acceleration of its degradation.

Figure 8. Cable 2 (saltwater tank) showing signs of physical degradation of the insulation layer.

Figure 8.

That said, this points to the potential failure of this type of cable when submerged. Following this occurrence, more tests should ideally be carried out in a controlled climate chamber, to confirm this behaviour.

Physical and chemical characteristics of water

The test conditions were maintained during the experimental period, in order to have aquatic environments as stable as possible, as depicted in Figure 9.

Figure 9. Physical-chemical characterization during the study period (T1- Tank 1, T2 – Tank 2, T3 – Tank 3, T4 – Tank 4, T5 – Tank 5, T6 – Tank 6).

Figure 9.

In Figure 9 34 is clear that most parameters were stable during the test period, and no major differences between freshwater and saltwater tanks for water temperature and dissolved oxygen were detected. Clearly, all parameters that evaluate the amount of dissolved substances and minerals in the water, as the salinity, electrical conductivity and total dissolved solids, reflect the experimental conditions, distinguishing saltwater and freshwater tanks. In spite of the efforts to keep salinity values around 35 mg L -1, some variations can be observed (it ranges between 32.5 and 41.9 mg L -1), since some dilution occurred due to precipitation events and sometimes an excess of salt was added since heavy precipitation events were predicted. We can also see that oxygenation levels have always been high, so there was a good circulation of water. Water temperature decreased with time, in accordance with the atmospheric temperature decrease and the seasonal changes from Autumn to Winter progression.

Regarding the possible release of copper into the water, on 3/12/2020, copper was detected in the saltwater tank 4 (cable 2) with a concentration of 0.052 mg L -1. Since the copper concentration in the water used to fill the basins was 0.005 mg L -1, an increase of 0.045 mg L -1 was then registered, as can be seen in Table 3.

The decrease in copper in container 4 shortly after its detection is explained by the fact that excess water was removed from the tank due to the heavy precipitation that occurred at that time.

In order to verify a possible water contamination with microplastic released by the cables, this analysis was carried out in all tanks. In Table 4, we can observe that the microplastics concentration is always low, with the control tanks (5 and 6) presenting higher values than the others. Thus, we can conclude that there was no significant release of microplastics by the photovoltaic cables.

Table 4. Microplastics concentration in water (the units in the table are number of particles larger than 20 micrometres in size per litre).

Tank 1 Tank 2 Tank 3 Tank 4 Tank 5 Tank 6
Organic particles ( e.g. , PP, PE, PS) - - - <2 - -
Polyethylene (PE) 2 - - - 2 2
Polypropylene (PP) 4 4 4 - 10 6
Organic particles ( e.g. , PMMA, PUR, PET) - - - <2 - -
Polyester 2 <2 - - 2 -
Ethylene-vinyl acetate (EVA) - - 2 - 6 4
Organic particles with silicone ( e.g. , plastic, rubber) <2 <2 <2 <2 <2 <2
Organic particles with chlorine ( e.g. , PVC) <2 <2 <2 <2 <2 <2
Organic particles with fluorine ( e.g. , PTFE) <2 <2 <2 <2 <2 <2

Legend: PP - Polypropylene; PE - Polyethylene; PS - Polystyrene; PMMA - Polymethyl Methacrylate; PUR - Polyurethane; PET - Polyethylene terephthalate; PVC - Polyvinyl Chloride; PTFE - Polytetrafluoroethylene.

Conclusion

The characteristics of aquatic environments pose new challenges to floating photovoltaic installations, with regard to their reliability and performance, as well as in the assessment of potential impacts on the aquatic ecosystems. The marine saltwater environment should be the most challenging for this new technology, due to its salinity, higher waves and wind speed, as well as additional anchoring and mooring difficulties. Being a recent technology, it does not yet benefit from the maturity and greater experience that conventional photovoltaic installations have on land 35 . This work intended to contribute to the increase of knowledge about these systems, in particular about the consequences of submersion of photovoltaic cables, both in the FPV installation and in the aquatic environment.

It was found that cables with rubber outer shell could fail when submerged in saltwater, with a decrease in its electrical insulation resistance and consequent release of copper into the water, potentially impacting the aquatic ecosystems. There is probably a relationship between submersion of this type of cable with temperatures below 0 °C and the occurrence of accelerated degradation of the cable insulation layer. Reduced resistance values were measured in this cable after the occurrence of such temperatures, both in salt and freshwater. This cable type showed visible exterior degradation signs, when submerged in saltwater.

Cross-linked polyethylene insulation showed higher reliability when submerged, without presenting any reduction of its dielectric parameter. However, faults may appear for longer submersion periods, situation most likely to occur in installations in remote sites and with a lower frequency of inspection and maintenance visits.

The results of this work showed that it is possible the occurrence of electrical insulation failures in submerged photovoltaic cables, as well as the leaching of contaminants in case of failure. The release of microplastics has not been shown to exist with new cables, but should be revaluated for longer periods of time, with the consequent ageing of the cables.

Future works

In future works the same analyses should be carried out, but in an aquatic environment where the remaining components of a floating photovoltaic system are included, such as the floats. Further testing will be needed to determine the likelihood of failure occurring over longer submersion periods, for both cables and connectors.

Ethics and consent

Ethical approval and consent were not required

Acknowledgements

The authors also would like to thank the Water Laboratory of the University of Évora, for the support and collaboration in the physical-chemical characterization, especially the copper analysis.

Funding Statement

This research was financially supported by the European Union’s Horizon 2020 research and innovation programme under the grant agreement No [952879](Accessible, reliable and affordable solar irrigation for Europe and beyond [SolAqua]). This project also received funding from the EERES4WATER project (EAPA_1058/2018), co-financed by the Interreg Atlantic Area Programme through the European Development Regional Fund.

[version 2; peer review: 2 approved, 1 approved with reservations]

Data availability

Underlying data

Zenodo: Experimental data of photovoltaic cable submersion tests. https://doi.org/10.5281/zenodo.7088811 34

This project contains the following underlying data:

  • Experimental Data.xlsx

Extended data

Zenodo: Meteorological data from the experimental period of the submersion test of photovoltaic cables. https://doi.org/10.5281/zenodo.7276616 32

  • Meteo data.xlsx (Data collected from weather station)

Zenodo: Floating Photovoltaics Installed Capacity in Europe in 2020. https://doi.org/10.5281/zenodo.7746070 36

  • FPV-Europe_2020.xlsx

Data are available under the terms of the Creative Commons Attribution 4.0 International license (CC-BY 4.0).

References

Open Res Eur. 2024 Oct 9. doi: 10.21956/openreseurope.20030.r44368

Reviewer response for version 2

Shiva Gorjian 1

The authors have properly addressed the comments and the revised version is satisfactory.

Is the study design appropriate and does the work have academic merit?

Partly

Is the work clearly and accurately presented and does it cite the current literature?

Partly

If applicable, is the statistical analysis and its interpretation appropriate?

Not applicable

Are all the source data underlying the results available to ensure full reproducibility?

Partly

Are the conclusions drawn adequately supported by the results?

Partly

Are sufficient details of methods and analysis provided to allow replication by others?

Partly

Reviewer Expertise:

Renewable Energies; Solar Energy Technologies

I confirm that I have read this submission and believe that I have an appropriate level of expertise to confirm that it is of an acceptable scientific standard.

Open Res Eur. 2024 Oct 7. doi: 10.21956/openreseurope.20030.r44367

Reviewer response for version 2

Sharon Hilarydoss 1

My comments have been addressed

Is the study design appropriate and does the work have academic merit?

Yes

Is the work clearly and accurately presented and does it cite the current literature?

Yes

If applicable, is the statistical analysis and its interpretation appropriate?

I cannot comment. A qualified statistician is required.

Are all the source data underlying the results available to ensure full reproducibility?

Yes

Are the conclusions drawn adequately supported by the results?

Partly

Are sufficient details of methods and analysis provided to allow replication by others?

Partly

Reviewer Expertise:

solar energy, desalination, thermodynamic analysis,

I confirm that I have read this submission and believe that I have an appropriate level of expertise to confirm that it is of an acceptable scientific standard.

Open Res Eur. 2024 Sep 20. doi: 10.21956/openreseurope.20030.r44376

Reviewer response for version 2

Giuseppe Marco Tina 1

Overall, the paper provides valuable insights into the behavior of photovoltaic (PV) cables submerged in two different water types. However, the limited scope of the experiments and the need for further analysis warrant careful consideration of the findings.

Key observations and suggestions:

references:

references and  standards for suitable cable in aquatic and marine environments should be cited. such as https://doi.org/10.4043/2428-A-MS

Cable Submersion:

The solar  gables are used to connect the PV modules and also to connect the string to the inverter that is supposed to be installed on the same floating structure. So it is not common to have such cables always submerged in floating PV plants. It could be happen in submerged PV plants such as the ones described in reference 7. In case of cable always submerged adequate types of cable should be used according to the standards  especially if we are in marine environment.

While submerged cables are less common in floating PV plants, the authors' focus on this aspect is valuable.

The use of appropriate cable types, especially in marine environments, is critical for long-term performance.

Experimental Conditions: The experiments provide a solid foundation for understanding cable behavior in different water types. However, expanding the scope to include a wider range of environmental conditions, such as varying temperatures and salinity levels, could enhance the generalizability of the results.

Insulation Resistance: The lack of significant insulation resistance reduction for most cables is encouraging (see Fig. 7). However, the singularity observed in cable 2 in saltwater during the eighth week warrants further investigation. It's possible that a material defect or a temporary environmental fluctuation contributed to this anomaly.  A statistical approach has to be used to present the results.

Container Degradation: To isolate the effects of the cables on the container material, it would be beneficial to include a control group of containers without cables. This would help determine if the container material itself is susceptible to degradation in the experimental conditions.

Cable Shape and Stress: The coiled shape of the cables in the experiments might not accurately reflect their real-world configuration. Considering the potential impact of cable tension and stress, especially at low temperatures, could provide additional insights into insulation performance.

Current Warming: While current flow can indeed warm the cables, the extent to which this mitigates the effects of low temperatures depends on factors such as cable thickness, current intensity, and the specific environmental conditions. Further analysis or simulations could quantify this effect.

In conclusion, the paper's findings contribute to our understanding of PV cable behavior in submerged environments. However, additional experiments and a more comprehensive analysis of factors such as environmental conditions, cable shape, and current warming are necessary to draw definitive conclusions about the long-term performance of these cables.

Is the study design appropriate and does the work have academic merit?

Partly

Is the work clearly and accurately presented and does it cite the current literature?

Partly

If applicable, is the statistical analysis and its interpretation appropriate?

I cannot comment. A qualified statistician is required.

Are all the source data underlying the results available to ensure full reproducibility?

Yes

Are the conclusions drawn adequately supported by the results?

Partly

Are sufficient details of methods and analysis provided to allow replication by others?

Partly

Reviewer Expertise:

photovoltaic systems, power system analysis

I confirm that I have read this submission and believe that I have an appropriate level of expertise to confirm that it is of an acceptable scientific standard, however I have significant reservations, as outlined above.

Open Res Eur. 2023 Jun 16. doi: 10.21956/openreseurope.16359.r31511

Reviewer response for version 1

Shiva Gorjian 1

The authors have investigated “Floating photovoltaic systems: photovoltaic cable submersion testing and potential impacts”. The following comments should be addressed:

  1. In Figure 2, it is better to add data for the years 2021-2023.

  2. Based on which criteria the authors have chosen the salinity level? Since FPVs can be installed on seawater, lakes, artificial water bodies, etc.

  3. Has the resistance time been considered as a parameter to evaluate the degradation level of the PV cables? If yes, how can it be generalized to real conditions?

  4. According to the results, can water temperature be considered an effective parameter in combination with water salinity?

  5. The results and discussion section should be improved.

Is the study design appropriate and does the work have academic merit?

Partly

Is the work clearly and accurately presented and does it cite the current literature?

Partly

If applicable, is the statistical analysis and its interpretation appropriate?

Not applicable

Are all the source data underlying the results available to ensure full reproducibility?

Partly

Are the conclusions drawn adequately supported by the results?

Partly

Are sufficient details of methods and analysis provided to allow replication by others?

Partly

Reviewer Expertise:

Renewable Energies; Solar Energy Technologies

I confirm that I have read this submission and believe that I have an appropriate level of expertise to confirm that it is of an acceptable scientific standard, however I have significant reservations, as outlined above.

Open Res Eur. 2024 Sep 3.
Luis FIALHO 1

The authors appreciate the reviewer's comments. All comments have been addressed in this version of the document, and we believe they resolve the issues raised. The authors did not collect installed capacity data beyond the final date shown in the graph already included in the article. Regarding comment 3: The authors would like to ask the reviewer to provide a bit more detail about what he intends to make clearer with it. The tests were conducted in a near-real environment, where conditions such as temperature, humidity, etc., vary over time, making it impossible to define the resistance time with precision. In the authors' opinion, temperature and salinity are influential parameters in the degradation of submerged cables, requiring further testing to obtain a more representative sample.

Open Res Eur. 2023 May 17. doi: 10.21956/openreseurope.16359.r31515

Reviewer response for version 1

Sharon Hilarydoss 1

  • Follow uniform decimal format throughout the manuscript including figures.

  • Indicate components by markings in Fig 4, 5, 6 , 8.

  • English language usage must be improved throughout the manuscript.

  • Check the spelling of the sub heading "Water physic-chemical characterization".

  • Superscripts are not properly indicated, check them throughout the manuscript

  • Conclusion section must be revised by shortening it and including only important findings. Move discussion portion from conclusion. In future work section below conclusion section.

Is the study design appropriate and does the work have academic merit?

Yes

Is the work clearly and accurately presented and does it cite the current literature?

Yes

If applicable, is the statistical analysis and its interpretation appropriate?

I cannot comment. A qualified statistician is required.

Are all the source data underlying the results available to ensure full reproducibility?

Yes

Are the conclusions drawn adequately supported by the results?

Partly

Are sufficient details of methods and analysis provided to allow replication by others?

Partly

Reviewer Expertise:

solar energy, desalination, thermodynamic analysis,

I confirm that I have read this submission and believe that I have an appropriate level of expertise to confirm that it is of an acceptable scientific standard, however I have significant reservations, as outlined above.

Open Res Eur. 2024 Sep 3.
Luis FIALHO 1

The authors appreciate the reviewer's comments. All comments have been addressed in this version of the document, and we believe they resolve the issues raised.

Associated Data

    This section collects any data citations, data availability statements, or supplementary materials included in this article.

    Data Citations

    1. Rebelo R, Fialho L, Novais MH: Meteorological data from the experimental period of the submersion test of photovoltaic cables.(Version 1) [Data set]. Zenodo.2022. 10.5281/zenodo.7276616 [DOI]
    2. Fialho L, Novais MH, Rebelo R: Experimental data of photovoltaic cable submersion tests.(Version 1) [Data set]. Zenodo.2022. 10.5281/zenodo.7088811 [DOI]
    3. Fialho L, Novais MH, Rebelo R: Floating Photovoltaics Installed Capacity in Europe in 2020.(Version 1) [Data]. Zenodo.2023. 10.5281/zenodo.7746070 [DOI]

    Data Availability Statement

    Underlying data

    Zenodo: Experimental data of photovoltaic cable submersion tests. https://doi.org/10.5281/zenodo.7088811 34

    This project contains the following underlying data:

    • Experimental Data.xlsx

    Extended data

    Zenodo: Meteorological data from the experimental period of the submersion test of photovoltaic cables. https://doi.org/10.5281/zenodo.7276616 32

    • Meteo data.xlsx (Data collected from weather station)

    Zenodo: Floating Photovoltaics Installed Capacity in Europe in 2020. https://doi.org/10.5281/zenodo.7746070 36

    • FPV-Europe_2020.xlsx

    Data are available under the terms of the Creative Commons Attribution 4.0 International license (CC-BY 4.0).


    Articles from Open Research Europe are provided here courtesy of European Commission, Directorate General for Research and Innovation

    RESOURCES