Skip to main content
Antimicrobial Stewardship & Healthcare Epidemiology : ASHE logoLink to Antimicrobial Stewardship & Healthcare Epidemiology : ASHE
. 2025 Aug 22;5(1):e190. doi: 10.1017/ash.2025.10077

Effectiveness and acceptability of ventilation modifications in healthcare facilities, Liberia 2022–2023

Ronan F Arthur 1,#,, Ashley Styczynski 1,#, Krithika Srinivasan 2, Amos Tandanpolie 3, Philip Bemah 4, Ethan Bell 1, Jason R Andrews 1, Tom Baer 5, Jorge L Salinas 1
PMCID: PMC12394025  PMID: 40893129

Abstract

Objective:

To evaluate the effectiveness and acceptability of ventilation interventions in naturally ventilated hospitals in Liberia.

Design:

Difference-in-differences analysis of pre- and post-air changes per hour of intervention and control spaces.

Setting:

Hospitals in Bong and Montserrado Counties, Liberia.

Participants:

Seventy patient care spaces were evaluated at baseline. Six spaces underwent physical intervention modifications, while 2 spaces were assessed for indirect effects and 2 others used as controls. Healthcare workers were interviewed to assess ventilation knowledge and acceptability.

Interventions:

Ventilation interventions included the installation of window screens, louvered doors and windows, and wind turbines.

Methods:

We measured carbon dioxide levels with portable meters and documented persons per room to estimate per-person ventilation rates in both L/s/person for the initial assessment and air changes per hour (ACH) in the intervention. Measurements were taken in patient care spaces in 7 hospitals in Liberia. Healthcare worker acceptability was evaluated via structured interviews.

Results:

Two-thirds (46/70) of patient care spaces were below the WHO-recommended ventilation threshold of 60 L/s/person. Six spaces underwent ventilation interventions, including placement of window screens (3), wind turbines (2), and louvered doors and windows (1), with 2 additional spaces being indirectly affected by these interventions and 2 more spaces serving as controls. Ventilation improved by an average of 2 ACH in the spaces with wind turbines and louvered doors and windows. Overall acceptability of the interventions was high.

Conclusions:

Implementing interventions to improve ventilation in naturally ventilated healthcare facilities is efficacious, feasible, and acceptable, though longer-term evaluations should assess sustainability.

Background

Many healthcare facilities in low-resource settings are under-equipped to prevent respiratory disease spread among patients or healthcare workers. Factors such as multiple-bed wards that are common in such settings can increase the risk for respiratory disease spread. 1 Ventilation is a critical pillar of infection prevention and control (IPC) for preventing respiratory disease transmission. Healthcare-associated transmission of SARS-CoV-2, for example, was found to correspond with facilities having poorer ventilation. 2 IPC programs typically focus on interventions such as hand hygiene, use of personal protective equipment, and environmental cleaning, while ventilation is less prioritized. 3

Mechanical ventilation is generally recommended in healthcare settings for its filtration capabilities, consistency, and efficiency. 4 Yet, many hospitals in low- and middle-income countries (LMICs) cannot afford the installation costs, do not have continuously available electricity to power mechanical ventilation systems, and do not have access to trained personnel to perform the required maintenance. 5 Optimized natural ventilation has been found to perform at least as well as, if not better than, mechanical ventilation in promoting air exchange and reducing infectious disease transmission risk. 68 Moreover, contaminated mechanical ventilation systems have been implicated in the spread of nosocomial infections, including pathogens not typically regarded as respiratory pathogens. 912 Thus, mechanical ventilation may not be a panacea for solving ventilation in low-resource healthcare settings, particularly those without extreme temperature fluctuations.

Rebreathed air and, as an extension, the risk of indoor airborne disease transmission, can be measured and inferred from indoor carbon dioxide (CO2) concentration. 1314 These techniques have been used to optimize ventilation in naturally ventilated healthcare facilities in LMICs to better protect against airborne disease transmission. 67,15 Augmentation of ventilation in naturally ventilated spaces can be achieved through building modifications or assistive devices. Strategies for improving ventilation in naturally ventilated healthcare facilities can range from opening existing windows and doors to more complex mixed-mode (hybrid) ventilation strategies that employ mechanical fans; the effectiveness of these various interventions depends on structural constraints, weather patterns, and electricity access. 5,16

Liberia is considered one of the most vulnerable countries in the world to infectious disease. Frontline healthcare facilities are the first to face novel cases of respiratory and emerging diseases, placing patients and healthcare workers at risk and often leading to disease amplification during outbreaks. 1718 Pathogens transmitted in hospital settings through the air pose a particular threat because they can be easily dispersed between infected and uninfected patients via shared airspaces when ventilation is inadequate. 5

Few low-cost ventilation improvements have been deployed in LMIC healthcare facilities, and little is known about what interventions may be most cost-effective, acceptable, and effective for improving ventilation with limited resources. We aimed to evaluate ventilation in Liberian healthcare facilities, identify and implement contextually appropriate low-cost ventilation interventions, and evaluate the impact of the interventions to improve ventilation and strengthen the resiliency of healthcare facilities.

Methods

Study design

The study was conducted across two phases: Phase 1 involved primary data collection with a baseline ventilation assessment to determine appropriate locations for intervention, while Phase 2 consisted of physical ventilation interventions as well as measurements of impact and acceptability among hospital staff.

Phase 1: Hospital baseline ventilation assessment

Cross-sectional ventilation measurements were collected in patient care areas in hospitals in both urban and rural areas of Montserrado and Bong Counties in Liberia. Hospitals were selected in collaboration with the National Public Health Institute of Liberia and the Ministry of Health of Liberia. Ventilation measurements were performed using portable CO2 meters (AmprobeⓇ CO2-100 CO2 meter, Amprobe Test Tools, Everett, WA) to measure levels of indoor and outdoor CO2, temperature, and humidity. In a single visit, the number of individuals present in a closed space was recorded once, and the existing ventilation infrastructure was documented. CO2 levels were collected twice per room in accordance with WHO-recommended protocols.

Absolute ventilation (L/s) was estimated using CO2 concentration differentials between indoor and outdoor air, following standard methodologies. 9,13 Ventilation per person (L/s/p) was then calculated and compared to the WHO-recommended threshold of 60 L/s/p for general patient wards. 5

Phase 2: Hospital ventilation infrastructure interventions

Hospitals with inadequate ventilation were selected for intervention in collaboration with national health authorities. Through review of the literature and discussion with ventilation experts, we identified potential ventilation interventions for enhancing natural ventilation in each space selected. We assigned specific interventions to individual spaces based on logistical considerations, including physical infrastructure, geography, and availability of materials, as well as anticipated impact on ventilation. Construction personnel were consulted and contracted to complete the installation of designed physical interventions and for the acquisition or fabrication of required materials. Materials not easily found available in Liberia (ie, whirlybird turbine vents) were procured in the United States.

Existing ventilation features, such as open brick structures for cross-ventilation, had been sealed off in one of the hospitals (Supplementary Figure 2). Neither hospital had negative pressure capacities.

Healthcare worker interviews

To assess healthcare worker knowledge about ventilation, identify ventilation challenges, and solicit input for ventilation improvements, we conducted open-ended interviews with a subset of healthcare workers in the selected hospitals using convenience sampling. Interviewers asked about knowledge of ventilation, importance of ventilation, and questions about doors, windows, and air-conditioning, including preferences and suggestions. Interviews were recorded and transcribed, and key themes were identified using constant comparison analysis and grounded theory. 19

Assessment of intervention impact

Longitudinal CO2 measuring devices (Aranet4, SAF North America LLC, Aurora, CO) were placed in each of the intervention and control spaces. Baseline CO2 values were measured in 5-minute intervals over 1 week. To assess the average number of people in the space, research associates visited each space at different times of day. The volume (m3) of the space was calculated by laser measurements. Following the implementation of the interventions, CO2 measurements were again collected over a week in both the intervention and control spaces. We calculated absolute ventilation as above, which we converted to air changes per hour (ACH) based on room volume (m3).

To assess the impact of the physical interventions on ACH in treatment versus control spaces, we employed a difference-in-differences framework, whereby the difference between pre- and post-intervention phases for direct (louvered doors and whirlybirds), indirect (whirlybird-adjacent), screen, and control arms was assessed. The analysis utilized a Gaussian linear mixed-effects regression model to account for data hierarchy. Fixed effects included time (pre- vs post-intervention), intervention group (direct, indirect, screen, and control), and their interaction. Random effects accounted for variation across locations. Residuals from the model were assessed for normality. All statistical analyses were conducted in R, using the lme4 package for mixed-effects modeling.

Acceptability assessment

We conducted acceptability assessments of the interventions through surveys and interviews with healthcare workers in the intervention spaces. Healthcare workers were selected through convenience sampling. The questionnaire was an adaptation of a theoretical framework of accessibility for healthcare interventions. 20

Institutional review

The Stanford University Institutional Review Board (protocol #67822) and the Atlantic Center for Research and Evaluation Institutional Review Board in Liberia (Assurance #FWA00032198) approved this study.

Results

Baseline ventilation assessment

From August 2022 to February 2023, we sampled all patient care areas in 7 hospitals. Measurements collected from one of the hospitals registered indoor CO2 values lower than 400 ppm. As this was presumed to be due to a calibration error, these data were dropped from further analysis. The remaining data included 70 patient care areas across 6 hospitals. Of the 70 rooms, 46 (66%) of the spaces were below the ventilation threshold of 60 L/s/person for general patient care activities (Supplementary Figure 1). Notably, there were several instances where existing ventilation infrastructure had been blocked in the setting of air-conditioning unit introductions (Supplementary Figure 2).

Healthcare worker interviews

Interviews were conducted with 21 healthcare workers from 2 hospitals selected for ventilation interventions, including 13 nurses, 6 nursing supervisors, an IPC focal person, and a midwife. Responses highlighted healthcare worker knowledge and awareness about ventilation as well as existing ventilation challenges within healthcare facilities (Table 1). Some healthcare workers recognized the importance of ventilation, citing it as a means of preventing respiratory disease spread. However, other healthcare workers equated climate control with ventilation, citing air-conditioning as a preferred ventilation modality. Several barriers to opening existing windows and doors were noted, including privacy concerns, concerns over mosquitoes and vermin, air pollution, and countering the cooling effects of air-conditioning. Recommendations for improving ventilation included the addition of window screens and expansion of windows.

Table 1.

Key themes around ventilation knowledge and challenges among Liberian healthcare workers (N = 21).

Theme Main findings Key quotes
Knowledge about ventilation Ventilation protects against infectious risks “Ventilation…helps to reduce the risk of infection of the patient especially within the hospital setting like where I’m working now.”
“When the windows and doors are open, the one that can make you feel safer is ventilation because when they come in with a respiratory disease like TB you catering to that patient, the place need to be well ventilated and to open the windows so that good air can come in and bad air goes out.”
Lack of awareness of ventilation Equating temperature
control with ventilation
“I’m telling you now like I said previously—to improve ventilation, to you people now I will say, that we need AC.”
“On my ward I have air cool, so it is not necessary for the windows and doors to be open.”
“Actually I will love to see clean environment and all wards be properly ventilated by air conditions, standby fan, and electricity.”
Barriers to opening windows or doors Privacy concerns “Okay yes, when the windows are open you don’t have privacy for your patient, because everything that will be said in your assessment area, passerby will hear them, so sometimes we like to see our patients close door and say what between us.”
Competition with air-conditioning “Yes, right now we are not opening doors and windows because of the AC and fan.”
Concerns over insects and other vermin “Because, most often especially overnight, mosquitoes and other things you can’t open the window when you have babies.”
Concerns over air pollution “Air that is coming in windows and doors are all open air that is coming in is polluted, I will not feel safe to work in that kind of place.”
Suggestions to improve ventilation Expansion of windows “Expansion of windows by creating another window elsewhere.”
Addition of window screens “Like if the window have a screen all around it will prevent insects and other things from entering but just open window, harmful things will enter and it will not be safe.”

Review of ventilation strategies

Six patient care spaces in 2 hospitals were selected for ventilation interventions with 2 additional spaces to serve as controls. Because of the physical layout of the rooms, 2 rooms were incompletely sealed from adjacent care areas. These adjacent rooms were assigned as “indirect” intervention spaces. Six potential ventilation interventions were considered for possible implementation (Table 2). Given structural considerations and availability of materials, 1 space was selected for placement of louvered windows and doors with screens, 2 spaces were selected for placement of wind turbines, and 3 spaces were selected for placement of window screens. Two adjacent rooms were indirectly served by the wind turbines (Supplementary Figure 3). Although window screens do not intrinsically improve ventilation, it was thought that cross-ventilation could be enhanced by addressing key barriers to keeping windows open (eg, mosquitoes) through placement of window screens. Cost was an additional consideration in selection of interventions as a key aim of the intervention was to identify solutions that would be feasible in LMICs. Healthcare workers in each of the spaces were sensitized to the interventions and counseled on the importance of ventilation for reducing the risk of transmission of airborne infectious diseases to both patients and healthcare workers.

Table 2.

Ventilation modification strategies to enhance natural ventilation.

Strategy Anticipated cost Requires structural modifications Requires behavioral inputs Requires electricity Other considerations
Cross ventilation via open windows/doors $–$$ +/– + • May be difficult to employ continuously because of temperature, climate, or security concerns.
• May not keep out insects or vermin unless combined with screens.
• Most effective when windows or doors are on opposite walls and on windward/leeward sides of the building.
Louvered windows/doors $$ + +/– • Can usually be left open during rain.
• Can be engineered to prevent full closure.
• May not keep out insects or vermin unless combined with screens.
• Provides less ventilation than a fully open window/door.
Honeycomb bricks/vents $$ + • Can also produce an added cooling effect when placed near the top of the space via stack effect.
• May not keep out insects or vermin unless combined with screens.
Wind turbines/wind tower $$$ + • Requires constant breeze to be effective.
Chimney/stack tower $$$$ + • Dependent on temperature differential, can be augmented with solar atria.
• Many possible configurations.
Exhaust fans $$$ + • Requires ‘sealing’ of the space to obtain significant air draw.
• Can be used to create negative pressure and ensure outward flow of air.

Wind turbines were placed in single-story buildings located in relative proximity to the ocean to capitalize on the continuous breeze. Galvanized wind turbines were selected to prevent accelerated rusting in a high salinity context. The wind turbines were not available locally and had to be imported. Four 14-inch diameter turbines were distributed over the roof of the 2 adjacent spaces, which was anticipated to improve the ventilation by up to 4 ACH in each of the spaces. During placement, it was noted that there was a 2–3-foot gap between the roofline and the ceiling. Metal sheeting was used to create a conduit connecting the wind turbine to the ceiling (Supplementary Figure 4).

Louvered windows and doors and screens were manufactured locally. The louvered windows and doors were designed to prevent them from being fully shut to ensure at least some degree of continuous cross-ventilation (Supplementary Figure 5). Screens were overlaid on these windows and doors, which were placed on opposite walls in a space that was on the first floor of a multi-storied building.

Assessment of intervention impact

At baseline, each of the selected spaces was noted to have ventilation rates below the WHO threshold. Substantial variability was noted in CO2 values by time of day, and ACH values in both pre- and post-data align with this observation (Figure 1). Each intervention type (direct, indirect, screen, and control) had a distinct impact on ACH measurements compared with preintervention measurements (Table 3). Direct interventions (ie, the immediate interiors where louvered windows, doors, and/or whirlybird installations were made) had the highest levels of improvement after installation of any intervention type (average ACH increases from .45 to 3.60). Hospital 2 ER, one of the 2 indirect interventions (ie, the spaces proximate to infrastructure improvement), demonstrated little effect from the intervention (ACH decrease of 2.0), though ventilation was more than adequate both before and after (overall average ACH of 22.91). The other space demonstrated substantial improvement only at night (overall ACH increase of 1.69). The greatest improvement was seen in the space where louvered windows and doors were added (3.29 average ACH at post vs 1.26 ACH prior to intervention). Some of the screen interventions also performed better at night compared with baseline, while one performed more poorly after the intervention. The controls saw little change to ACH measurements (average ACH changes of .18 and −.63).

Figure 1.

Figure 1.

Air changes per hour (ACH) by time of day across all hospital rooms pre- (yellow) and post- (green) intervention installation. Each hospital space was designated an intervention type: direct (immediate interiors to infrastructure changes), indirect (proximate interiors), screen (immediate interiors to screen installations), and control (no changes).

Table 3.

Comparison of pre- and post-intervention air changes per hour (ACH) in each intervention and control ward space.

Location Intervention type Intervention PreACH IQR PostACH IQR Δ ACH
Hosp 1 ER Direct Louvered doors/windows (.65–1.49) (1.72–4.45) 2.03
Hosp 2 Peds Direct Whirlybird (7.9–12.43) (9.23–16.64) 3.6
Hosp 2 ER 2 Direct Whirlybird (3.63–4.96) (3.49–5.53) .45
Hosp 2 NICU Indirect Whirlybird-adjacent (3.65–6.74) (5.45–8.68) 1.69
Hosp 2 ER Indirect Whirlybird-adjacent (18.4–27.6) (17.56–25.28) −2.0
Hosp 1 NICU Screen Screen (1.12–4.32) (.98–1.75) −1.35
Hosp 1 Peds Screen Screen (1.34–3.41) (2.1–3.51) .49
Hosp 1 ICU Screen Screen (.75–1.65) (.97–2.48) .33
Hosp 1 OB Control Control (1.06–1.84) (1.15–2.01) .18
Hosp 1 Gyn Control Control (2.69–4.8) (2.19–3.86) .63

Results from the linear mixed-effects model (Table 4) indicate that the improvements in ACH following the direct infrastructure interventions were substantial and significant compared to control spaces, adjusting for pre-intervention ACH levels (β = 2.30, P < .001). By contrast, changes in ACH in the indirect and screen interventions were not significant from the pre- to post-intervention phases.

Table 4.

Results from the Gaussian linear mixed-effects model.

Term Estimate 95% CI P-value
Baseline (intercept) 2.73 (−4.05, 9.51) .50
Post-intervention (class) −.27 (−.45, −.09) <.01
Direct intervention 2.68 (−6.07, 11.44) .51
Indirect intervention 12.0 (2.41, 21.59) <.05
Screen intervention .32 (−9.08, 8.44) .94
Scaled time (truncated) .22 (.18, .26) <.001
Interaction: post × direct 2.3 (2.07, 2.53) <.001
Interaction: post × indirect .12 (−.14, .37) .34
Interaction: post × screen .08 (−.15, .31) .49

Discussion

Ventilation represents a key vulnerability for healthcare IPC in LMICs. Most healthcare delivery spaces evaluated in Phase 1 had lower than recommended ventilation rates at baseline. The impact of infrastructure interventions on ventilation rates in Phase 2 was variable with some spaces demonstrating substantive improvements, while other spaces showed no significant differences compared to baseline.

Ventilation inadequacies and challenges in Liberian hospitals are reflected in other low-resource settings. 15,21 Healthcare workers demonstrated variable understanding of the importance of ventilation for reducing infectious disease transmission. This may at least partially explain the large number of spaces with inadequate ventilation across 6 hospitals. The finding that some clinical staff viewed ventilation as relatively unimportant is reflected in the literature. 22

A major competing priority in many spaces was climate control (i.e. air-conditioning) as evidenced by the sealed-off remnants of prior ventilation infrastructure observed during baseline assessments. The importance placed on air-conditioning was also highlighted during interviews with staff whose main focus was climate control, which was often equated with ventilation or considered to be at odds with ventilation (e.g. keeping windows shut when the air-conditioning is running). The air-conditioning units typically placed in these spaces recirculate cooled air rather than drawing in external air, and, therefore, do not contribute to ventilation. The increasing use of air-conditioning to decrease temperature but without an impact on air exchanges is particularly problematic for infectious disease transmission risk. 23

Yet, ventilation and climate control do not have to be at odds. In fact, thresholds for ACH in healthcare settings were largely driven by their impact on patient comfort. 24 Many ventilation interventions provide both improved ventilation as well as climate control through continuous air movement and/or removal of hot air through stack effect. Interventions relying on stack effects may have greater impact on climate control, though these interventions were not undertaken in this study because they would have required more expensive structural modifications, and it was unclear if temperature differentials were sufficient to achieve the desired outcome. If further climate control is required, augmented ventilation systems can be employed. 2527 Furthermore, maintaining open windows or doors while running air-conditioning units is thought to impede the impact of climate control and substantially raise energy costs. However, these may not be as oppositional as anticipated, as the estimated additional energy costs associated with operating air-conditioning while maintaining partially open windows are in the order of $6/month (assuming energy costs of $.15 USD/KwH). 28

In this study, several of the spaces were observed to have varying ventilation when assessed by time of day. In general, ventilation rates were lower at night, presumably driven by closing windows and doors. This likely explains the limited impact of screens. Ventilation rates were highest during the afternoon, however, presumably driven by opening windows and doors for relief from higher temperatures. However, the time of open windows was not measured in this study, so the lack of impact may be related to a lack of change in practice rather than a failure of the intervention. Window screens also did not address 2 other stated concerns—privacy and air pollution—which may have discouraged any change in window opening patterns.

The wind turbines were anticipated to have the most appreciable impact on ventilation, though the observed changes were more modest. One key reason may be because of the large gap between the roofline and the ceiling, which necessitated crafting of air conduits. Flow decreases as the length of a cylinder increases, so the effect may have been dampened by the added length of the conduit. Additionally, the team had planned to install twice as many turbines over the designated spaces, but there were changes in the hospital administration that prevented approval for the installation of all the turbines. Turbines may still have strong potential for low-cost ventilation solutions in hospital settings as they can both circulate air and provide a cooling effect by withdrawing hot air from the ceiling space.

Limitations of this study include the small number of spaces and interventions that were included in the assessment, which limits the generalizability of the specific interventions. Additionally, we did not assess long-term sustainability. If staff perceived the interventions as reducing the impact of climate control, the interventions could be reversed, such as with the sealed honeycomb bricks, which could undermine the ventilation improvements we documented in that space. Moreover, while CO2 measurements were collected every 5 minutes by an automatic sensor, the measurement of people in the room was done by research personnel more infrequently and never in the middle of the night—thus, the number of people in the room may have been overestimated as nighttime traffic through the hospitals was likely less than during the day. Furthermore, we did not assess process measures, such as time of open windows or other behavior changes, which would more accurately characterize impact of interventions such as window screens.

Building resilient healthcare systems to prepare for future epidemics requires practical, cost-effective solutions that align with local cultural and resource constraints. Our findings demonstrate the feasibility of implementing natural ventilation interventions in Liberian healthcare facilities. These modifications were both efficacious and acceptable, though longer-term evaluations are necessary to assess sustainability. Future research should explore cost-effectiveness, feasibility in other low-income settings, and integration into broader infection prevention strategies to ensure that these interventions are both impactful and scalable.

Supporting information

Arthur et al. supplementary material

Arthur et al. supplementary material

DOI: 10.1017/ash.2025.10077.sm001

Acknowledgments

The authors acknowledge the healthcare workers and administrators who participated in or facilitated data collection and the National Public Health Institute of Liberia. We also thank Harris M. Woniyou for assistance with acceptability interviews.

Supplementary material

The supplementary material for this article can be found at https://doi.org/10.1017/ash.2025.10077.

Author contribution

RA, AS, KS, JA, TB, and JLS conceptualized the study design. KS and EB contributed background research to inform the study design. RA, AT, PB contributed to study implementation. RA and AS led initial manuscript drafting. KS, AT, PB, EB, JA, TB, and JLS contributed to manuscript revisions.

Financial support

This study was supported by the Stanford Center for Innovation in Global Health. The funders had no role in the study design, interpretation of results, or decision to publish.

Competing interests

The authors have no conflicts of interest to declare.

References

  • 1. Beggs CB, Kerr KG, Noakes CJ, Hathway EA, Sleigh PA. The ventilation of multiple-bed hospital wards: review and analysis. Am J Infect Control 2008;36:250–259. [DOI] [PubMed] [Google Scholar]
  • 2. Cooper BS, Evans S, Jafari Y, et al. The burden and dynamics of hospital-acquired SARS-CoV-2 in England. Nature 2023;623:132–138. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 3. Infection prevention and control assessment framework at the facility level. World Health Organization. 2018. https://www.who.int/publications/i/item/WHO-HIS-SDS-2018.9. Accessed January 17, 2025. [Google Scholar]
  • 4. Sehulster L, Chinn RYW, CDC, HICPAC. Guidelines for environmental infection control in health-care facilities. Recommendations of CDC and the Healthcare Infection Control Practices Advisory Committee (HICPAC). MMWR Recomm Rep 2003;52:1–42. [PubMed] [Google Scholar]
  • 5. Atkinson J, Chartier Y, Pessoa-Silva CL, et al. (eds). Natural Ventilation for Infection Control in Health-Care Settings. Geneva: World Health Organization; 2009. [PubMed] [Google Scholar]
  • 6. Escombe AR, Oeser CC, Gilman RH, et al. Natural ventilation for the prevention of airborne contagion. PLoS Med 2007;4:68. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 7. Qian H, Li Y, Seto WH, Ching P, Ching WH, Sun HQ. Natural ventilation for reducing airborne infection in hospitals. Build Environ 2010;45:559–565. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 8. Chen WQ, Ling WH, Lu CY, et al. Which preventive measures might protect health care workers from SARS? BMC Public Health 2009;9:81. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 9. Kumari DNP, Haji TC, Keer V, et al. Ventilation grilles as a potential source of methicillin-resistant Staphylococcus aureus causing an outbreak in an orthopaedic ward at a district general hospital. J Hosp Infect 1998;39: 127–133. [DOI] [PubMed] [Google Scholar]
  • 10. Correia G, Rodrigues L, Gameiro da Silva M, et al. Airborne route and bad use of ventilation systems as non-negligible factors in SARS-CoV-2 transmission. Med Hypotheses 2020;141:109781. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 11. Cotterill S, Evans R, Fraise AP. An unusual source for an outbreak of methicillin-resistant Staphylococcus aureus on an intensive therapy unit. J Hosp Infect 1996;32:207–216. [DOI] [PubMed] [Google Scholar]
  • 12. Allen KD, Green HT. Hospital outbreak of multi-resistant Acinetobacter anitratus: an airborne mode of spread? J Hosp Infect 1987;9:110–119. [DOI] [PubMed] [Google Scholar]
  • 13. Persily AK. Evaluating building IAQ and ventilation with indoor carbon dioxide. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.; 1997. Available at: https://www.osti.gov/biblio/349956-evaluating-building-iaq-ventilation-indoor-carbon-dioxide. [Google Scholar]
  • 14. Rudnick SN, Milton DK Risk of indoor airborne infection transmission estimated from carbon dioxide concentration. Indoor Air 2003;13:237–245. [DOI] [PubMed] [Google Scholar]
  • 15. Escombe AR, Ticona E, Chávez-Pérez V et al. Improving natural ventilation in hospital waiting and consulting rooms to reduce nosocomial tuberculosis transmission risk in a low resource setting. BMC Infect Dis 2019;19:88. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 16. Yau YH, Chandrasegaran D, Badarudin A. The ventilation of multiple-bed hospital wards in the tropics: a review. Build Environ 2011;46:1125–1132. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 17. Allegranzi B, Bagheri Nejad S, Combescure C, et al. Burden of endemic health-care-associated infection in developing countries: systematic review and meta-analysis. Lancet 2011;377:228–241. [DOI] [PubMed] [Google Scholar]
  • 18. Chiarello LA, Tapper ML Healthcare settings as amplifiers of infectious disease. Emerg Infect Dis 2004;10:2048–2049. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 19. Strauss AL, Corbin JM. Basics of Qualitative Research: Procedures and Techniques for Generating Grounded Theory. Thousand Oaks: Sage Publications; 1998. [Google Scholar]
  • 20. Sekhon M, Cartwright M, Francis JJ. Development of a theory-informed questionnaire to assess the acceptability of healthcare interventions. BMC Health Serv Res 2022;22:279. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 21. Styczynski A, Hemlock C, Hoque KI, et al. Assessing impact of ventilation on airborne transmission of SARS-CoV-2: a cross-sectional analysis of naturally ventilated healthcare settings in Bangladesh. BMJ Open 2022;12:e055206. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 22. Sagha Zadeh R, Shepley MM, Owora AH, et al. The importance of specific workplace environment characteristics for maximum health and performance: healthcare workers’ perspective. J Occup Environ Med 2018;60:e245–e252. [DOI] [PubMed] [Google Scholar]
  • 23. Nardell E, Lederer P, Mishra H, et al. Cool but dangerous: how climate change is increasing the risk of airborne infections. Indoor Air 2020;30:195–197. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 24. Sundell J, Levin H, Nazaroff WW, et al. Ventilation rates and health: multidisciplinary review of the scientific literature. Indoor Air 2011;21:191–204. [DOI] [PubMed] [Google Scholar]
  • 25. Rahman NMA, Haw LC, Fazlizan A. A literature review of naturally ventilated public hospital wards in tropical climate countries for thermal comfort and energy-saving improvements. Energies 2021;14:435. [Google Scholar]
  • 26. Bhagat RK, Linden PF. Displacement ventilation: a viable ventilation strategy for makeshift hospitals and public buildings to contain COVID-19 and other airborne diseases. R Soc Open Sci 2020;7:200680. [DOI] [PMC free article] [PubMed] [Google Scholar]
  • 27. Adamu Z, Price A. The design and simulation of natural personalized ventilation (NPV) system for multi-bed hospital wards. Buildings 2015;5:381–404. [Google Scholar]
  • 28. Scheuring L, Weller B. An investigation of ventilation control strategies for louver windows in different climate zones. Int J Vent 2021;20:226–235. [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Supplementary Materials

Arthur et al. supplementary material

Arthur et al. supplementary material

DOI: 10.1017/ash.2025.10077.sm001

Articles from Antimicrobial Stewardship & Healthcare Epidemiology : ASHE are provided here courtesy of Cambridge University Press

RESOURCES