Abstract
This paper presents a novel Mitochondrial Energy Production Optimization (MEPO) algorithm for enhancing grid-connected inverter control under weak grid conditions. The proposed bio-inspired approach addresses critical challenges in maintaining power quality and system stability in low Short Circuit Ratio (SCR) environments while ensuring robust performance during grid disturbances. A comprehensive LCL filter design achieves
magnitude attenuation with
phase margin at the resonant frequency of
, providing superior harmonic suppression. The MEPO controller demonstrates exceptional performance with current Total Harmonic Distortion (THD) of
, significantly outperforming Particle Swarm Optimization (
) and Genetic Algorithm (
) approaches. Dynamic response tests confirm rapid settling times of
for current control and voltage regulation within
, while maintaining a power factor of 0.998. Experimental validation on a
prototype verifies the algorithm’s effectiveness, achieving precise d-q axis current control with steady-state errors below
and robust frequency tracking at
. Rigorous statistical analysis across 100 independent trials validates the algorithm’s reliability with a
success rate and
faster convergence than conventional methods. The proposed MEPO solution represents a significant advancement in grid-connected inverter technology, particularly beneficial for renewable energy integration in weak grid environments.
Keywords: Grid-connected inverter, Weak grid control, MEPO algorithm, Power quality optimization, Renewable energy integration, Bio-inspired optimization
Subject terms: Electrical and electronic engineering, Computational science
Introduction
Integrating renewable energy sources into modern power grids has fundamentally transformed the landscape of power electronics and control systems design. Grid-connected inverters, serving as the crucial interface between renewable sources and the utility grid, demand increasingly sophisticated control strategies to meet stringent performance requirements1. The conventional approaches to inverter control, while providing foundational reliability, often fall short in achieving optimal performance across the broad spectrum of operating conditions demanded by contemporary grid standards2–4. This limitation becomes particularly evident in the context of increasing renewable energy penetration, where system dynamics are characterized by inherent nonlinearities, multiple competing objectives, and strict operational constraints5,6.
The significance of optimizing grid-connected inverter control systems extends far beyond basic functionality. In the realm of power quality, enhanced control strategies directly impact harmonic suppression, voltage regulation, and power factor correction capabilities7,8. These improvements translate into more stable grid operation, reduced equipment stress, and enhanced system reliability. From an economic perspective, optimized control systems contribute to higher energy conversion efficiency, reduced maintenance requirements, and improved return on investment for renewable energy installations9. The technical advancement brought about by sophisticated control optimization pushes the boundaries of what’s achievable in terms of system performance and grid support capabilities10.
Traditional design approaches for grid-connected inverter controllers have predominantly relied on classical control theory and empirical tuning methods11–13. While these approaches have served the industry well, they often result in suboptimal performance when faced with the complexities of modern power systems. The variable nature of renewable energy sources, coupled with increasingly stringent grid codes, necessitates more adaptive and intelligent control strategies14,15. This challenge is further compounded by the need to simultaneously optimize multiple performance metrics while maintaining system stability and respecting operational constraints16.
The present work introduces the Mitochondrial Energy Production Optimization (MEPO) algorithm, a novel bio-inspired optimization approach specifically designed for grid-connected inverter control systems. The algorithm draws inspiration from cellular energy production processes, mapping biological concepts such as electron transport chains, proton gradients, and ATP synthesis to mathematical optimization mechanisms. This unique approach enables the algorithm to effectively handle the multi-objective nature of inverter control optimization while maintaining robust performance across varying operating conditions17.
The development of MEPO was motivated by several critical factors in the current power electronics landscape. Existing optimization methods often struggle to effectively balance multiple competing objectives while maintaining system stability and respecting operational constraints. The increasing stringency of grid codes and growing demand for higher efficiency and reliability have created a need for more sophisticated optimization approaches. Furthermore, advancements in computational capabilities and improved understanding of biological systems have opened new possibilities for bio-inspired optimization strategies.
The novelty of the proposed approach lies in its comprehensive integration of biological principles with control system optimization. The algorithm’s transfer operator, inspired by electron transport chain mechanisms, enables effective exploration of the solution space while maintaining solution quality. The gradient estimation method, based on proton gradient principles, provides efficient local optimization capabilities. The local search mechanism, modeled after ATP production, ensures fine-tuning of control parameters. These components work in concert to achieve superior performance compared to traditional optimization methods.
The implementation strategy for MEPO addresses several practical considerations in grid-connected inverter applications. The algorithm incorporates efficient computational structures and advanced parallelization schemes to enable real-time optimization capabilities. Novel convergence mechanisms ensure reliable optimization outcomes, while robust adaptation capabilities allow the system to respond effectively to changing operating conditions. The integration of stability preservation mechanisms and constraint handling approaches ensures practical applicability in real-world systems.
This paper presents a comprehensive analysis of the proposed MEPO algorithm, beginning with a thorough literature review examining existing optimization methods and control strategies for grid-connected inverters. The mathematical framework is then developed in detail, including system modelling, optimization variable definition, objective function formulation, and update rule derivation. Implementation details are presented, covering control signal generation, performance metric evaluation, and practical considerations. Extensive simulation results demonstrate the algorithm’s effectiveness across various operating conditions, with experimental validation verifying practical applicability.
The anticipated contributions of this work are multifaceted. The novel bio-inspired optimization algorithm represents a significant advancement in grid-connected inverter control optimization. The comprehensive mathematical framework provides a solid foundation for future developments in this field. Detailed performance analysis and experimental validation demonstrate the practical benefits of the proposed approach. Through these contributions, this work advances the state-of-the-art in power electronics control optimization while providing practical solutions for industry implementation.
The remainder of this paper is organized to systematically present the theoretical development, implementation details, and validation results of the proposed approach. Following the literature review, the mathematical framework of MEPO is developed in detail. Implementation considerations and practical aspects are then discussed, followed by comprehensive simulation studies and experimental validation. The paper concludes with a discussion of results and future research directions, providing a complete examination of this novel optimization approach for grid-connected inverter control systems.
Bio-inspired optimization framework
The core innovation of MEPO lies in its systematic mapping of cellular energy production mechanisms to mathematical optimization operators. This mapping establishes a unique framework that combines biological principles with control theory to achieve robust optimization performance Fig. 1.
Fig. 1.
MEPO’s biological-mathematical mapping framework. The electron transport chain (ETC) inspires solution transfer mechanisms, proton gradients guide optimization direction, and ATP synthesis processes inform local search strategies.
Fundamental mapping components
MEPO’s architecture comprises three primary biological-mathematical mappings. First, the electron transport chain (ETC) mechanism is translated into a transfer operator that enables effective solution space exploration:
![]() |
1 |
where
and
represent candidate solutions and
. The transfer probability follows biological principles:
![]() |
2 |
with
representing fitness difference and T controlling exploration-exploitation balance.
Second, the proton gradient across mitochondrial membranes inspires a gradient-based optimization operator:
![]() |
3 |
where
follows an adaptive schedule:
![]() |
4 |
Third, ATP synthesis processes are mapped to a local search mechanism:
![]() |
5 |
featuring controlled exploration through variance decay:
![]() |
6 |
Integrated optimization process
These biological-mathematical mappings work in concert through a combined update rule:
![]() |
7 |
This integration ensures balanced optimization by combining global exploration through the transfer operator, directed search via gradient information, and local refinement through controlled perturbations.
The framework’s convergence is guaranteed under standard conditions including function continuity and appropriate parameter scheduling. Notably, the probability of reaching the global optimum approaches unity as iterations progress:
![]() |
8 |
where
denotes the global optimum.
Mathematical formulation
Solution space definition
The optimization process is defined within a bounded search space
:
![]() |
9 |
where each component
is bounded by:
![]() |
10 |
Here,
and
represent the lower and upper bounds for the
-th decision variable.
A population of
solutions is represented as:
![]() |
11 |
where each row of
corresponds to a solution vector within the search space
.
Transfer operator
The transfer operator is responsible for exchanging information between two solutions
and
. It is defined as:
![]() |
12 |
where
is a random vector sampled from
.
The operator is applied probabilistically based on the fitness difference:
![]() |
13 |
Here,
denotes the fitness difference,
represents the electron transfer rate, and
is a temperature-like parameter controlling randomness.
The transfer operator ensures that better solutions are more likely to influence the population while maintaining diversity. Its properties include:
- Conservation:

14 - Reversibility:

15 Ergodicity: The operator ensures that all regions of the search space can be explored given sufficient time.
Gradient operator
The gradient operator is responsible for guiding solutions toward optimal regions of the fitness landscape. It is defined as:
![]() |
16 |
where
represents the gradient of the fitness function, and
is a time-varying step size:
![]() |
17 |
In population-based optimization, the gradient is approximated as:
![]() |
18 |
where
are the
-nearest neighbors of
, and the weights
are defined as:
![]() |
19 |
The step size
is designed to satisfy the Robbins-Monro conditions:
![]() |
20 |
ensuring convergence over iterations.
Local search operator
The local search operator introduces stochastic perturbations to refine promising solutions. It is defined as:
![]() |
21 |
where
is a Gaussian perturbation with variance
that decreases over time:
![]() |
22 |
The decay parameter
is given by:
![]() |
23 |
where
is the total number of iterations.
The local search operator focuses on exploiting the neighborhood of promising solutions while gradually reducing exploration as the algorithm converges.
Combined update rule
The sequential application of the operators produces the complete update rule:
![]() |
24 |
Alternatively, the operators can be applied in parallel with weighted contributions:
![]() |
25 |
where
and
.
Constraint handling
For bounded decision variables, the following projection is applied:
![]() |
26 |
For general constraints
, a penalty function modifies the fitness as:
![]() |
27 |
where
is a penalty parameter.
Convergence properties
The error between the solution and the optimum decreases exponentially:
![]() |
28 |
where
.
The optimization process satisfies the first-order optimality condition:
![]() |
29 |
and the second-order condition:
![]() |
30 |
indicating that
is a local minimum.
The stability of the process is ensured by the Lyapunov function:
![]() |
31 |
which satisfies:
![]() |
32 |
This guarantees that
converges to
as
.
MEPO process
The algorithm progresses through initialization, iterative operator application, and termination phases. Each phase is systematically derived to ensure population diversity, adaptive exploration, and convergence toward the global optimum.
Initialization phase
The initial population is generated within the defined search space:
![]() |
33 |
where
for
. Each element of
is initialized as:
![]() |
34 |
where
and
are the lower and upper bounds for the
-th dimension, and
is a uniform random variable.
Purpose: Ensures uniform coverage of the search space and promotes initial population diversity.
Main loop
The iterative process applies three operators: transfer, gradient, and local search. The population is updated in each iteration to improve the quality of solutions.
Transfer phase
The transfer operator combines solutions probabilistically:
![]() |
35 |
where
. The application of the operator is controlled by:
![]() |
36 |
Properties: Preserves high-quality solutions, enables exploration through controlled mixing and balances exploitation and diversity via the temperature parameter
.
Gradient phase
The gradient operator refines solutions based on the estimated fitness landscape:
![]() |
37 |
where
is the step size:
![]() |
38 |
The gradient
is estimated using population-based dynamics:
![]() |
39 |
where
are the
-nearest neighbors of
, and
are weights based on distance:
![]() |
40 |
Properties: Drives solutions toward optimal regions adapts the step size dynamically for convergence and incorporates population-level information for robust gradient estimation.
Local search phase
The local search operator refines the top
solutions:
![]() |
41 |
where
decreases exponentially over time:
![]() |
42 |
The refined solution is accepted if it improves the fitness:
![]() |
43 |
Properties: Focuses on exploiting promising regions of the search space, reduces exploration over time through variance decay and maintains elite solutions for convergence.
Selection and update
The population is updated by selecting the best solutions from the combined set of old and new candidates:
![]() |
44 |
The selection probability is governed by the Boltzmann distribution:
![]() |
45 |
Properties: Ensures elitist selection to retain high-quality solutions and maintains diversity through probabilistic selection pressure.
Termination criteria
The algorithm terminates when one of the following conditions is satisfied:
- The fitness improvement between consecutive iterations is below a threshold:

46 - The maximum number of iterations is reached:

47 - The gradient norm is sufficiently small:

48
Properties: Prevents unnecessary iterations by detecting convergence and ensures algorithm stability and efficiency.
Integrated update rule
The overall update process combines the three operators sequentially:
![]() |
49 |
Properties: Balances exploration and exploitation and guarantees that the population improves or maintains its quality over iterations.
The MEPO algorithm, as shown in Fig. 2 represents a systematic optimization process that begins with population initialization, where solutions are randomly distributed within the search space bounds. The main loop consists of three key biologically inspired operators: Electron Transfer (
), which performs solution mixing with probability
; Gradient Update (
), which moves solutions along estimated descent directions with adaptive step size
; and Local Search (
), which refines solutions through controlled Gaussian perturbations
.
Fig. 2.
MEPO algorithm block diagram.
Each iteration progresses through these operators sequentially, with solutions evaluated and selected based on fitness improvement. The transfer operator enables exploration through solution mixing, while the gradient operator guides the search toward promising regions, and the local search operator fine-tunes the best solutions. Selection maintains population diversity while preserving elite solutions through a Boltzmann-based probability distribution:
![]() |
The convergence check evaluates three criteria: fitness improvement threshold
, maximum iterations
, and gradient magnitude
. If any criterion is met, the algorithm terminates; otherwise, it loops back to the transfer phase. This process continues until optimal or near-optimal solutions are found, with each operator’s parameters (
,
,
) adapted over time to transition from exploration to exploitation.
The MEPO algorithm’s block diagram represents a sophisticated optimization framework starting with the initialization phase, where the population
is generated within the bounded search space
. Each solution vector contains control parameters structured as
, initialized using a uniform random distribution to ensure diverse starting points. This initialization block feeds into three parallel processing phases that form the core of the MEPO algorithm.
The Electron Transfer Phase, depicted in the left branch of the diagram, implements the biological analogue of electron transport chain mechanics through the transfer operator
. The mathematical formulation
is governed by the acceptance probability
, where the temperature parameter T controls the exploration-exploitation balance. This block dynamically adapts
as
, ensuring proper scaling of the transfer probability throughout the optimization process. The central branch represents the Gradient Update Phase, employing population-based gradient estimation for directed search. The update mechanism
utilizes an adaptive step size
that satisfies the Robbins-Monro conditions for convergence. The gradient approximation
incorporates information from the K-nearest neighbours, weighted by distance-based kernels to ensure robust estimation.
The Local Search Phase, shown in the right branch, implements fine-tuning through controlled Gaussian perturbation. The operation
, where
, includes variance scheduling via
to transition from exploration to exploitation. This block selectively applies the local search to the top-performing solutions, ensuring efficient refinement of promising regions in the parameter space. The Selection and Update block combines outputs from all three phases through a Boltzmann-based selection mechanism. The selection probability
maintains population diversity while preserving elite solutions. The population update
ensures monotonic improvement in the population’s quality over iterations. The Convergence Check diamond implements multiple termination criteria: fitness improvement threshold
, maximum iterations
, and gradient magnitude
. These criteria form a logical OR operation, where the satisfaction of any criterion triggers termination. The feedback loop enables iterative improvement until convergence conditions are met.
The entire system operates under the integrated update rule
![]() |
50 |
where the sequential application of operators ensures comprehensive search capabilities. The block diagram emphasizes both the parallel nature of the core operators and their sequential integration through the selection mechanism, creating a robust framework for optimizing the complex parameter space of grid-connected inverter control systems.
Parameter control and convergence analysis
Parameter control
The MEPO algorithm incorporates adaptive parameter control mechanisms to balance exploration and exploitation dynamically, as shown in Fig. 3.
Fig. 3.
MEPO parameter control block diagram.
Electron transfer rate control
The electron transfer rate
is dynamically adjusted over iterations:
![]() |
51 |
where
is the initial rate,
is the maximum number of iterations, and
is the decay factor (typically 1-2). Success-based adaptation further refines
:
![]() |
52 |
where
is the adaptation rate, typically 0.1-0.2.
Gradient step size control
The step size for the gradient operator is updated dynamically:
![]() |
53 |
where
is the initial step size, and
is the decay parameter (typically 0.01-0.1). An adaptive version adjusts
based on gradient norm:
![]() |
54 |
where
is the adaptation rate (typically 0.05-0.15).
Local search variance control
The variance of the local search operator decreases exponentially over time:
![]() |
55 |
where
is the initial variance, and
is the decay rate (typically 0.01–0.05). Success-based adaptation modifies
as follows:
![]() |
56 |
where
is the adaptation rate (typically 0.1–0.2).
Convergence analysis
The convergence of the MEPO algorithm is analyzed under established mathematical conditions.
Global convergence theorem
If
is continuous and bounded below, the algorithm satisfies:
![]() |
57 |
where
is the global optimum. Convergence requires:
,
,
.
Convergence rate analysis
For local convergence, the following inequality holds:
![]() |
58 |
where
is the strong convexity parameter. The convergence rate is linear:
![]() |
59 |
where
are constants.
Stability analysis
Stability is ensured through a Lyapunov function:
![]() |
60 |
which satisfies:
![]() |
61 |
where
is a positive constant.
Error bounds
The expected error satisfies:
![]() |
62 |
where
is the Lipschitz constant of
, and
is the step size.
Population diversity
Diversity within the population is measured as:
![]() |
63 |
The diversity is maintained if:
![]() |
64 |
where
is a small positive constant.
Implementation foundations
Implementing the MEPO algorithm is based on three core operators: transfer operation, gradient estimation, and local search. These operators are mathematically designed to balance exploration and exploitation in the solution space.
The algorithm progresses through initialization, iterative operator application, and termination phases. Each phase is systematically derived to ensure population diversity, adaptive exploration, and convergence toward the global optimum. The complete execution flow of the MEPO algorithm is illustrated in Fig. 4, which provides a step-by-step visualization of the optimization process from initialization through convergence.
Fig. 4.

MEPO algorithm flowchart.
Core operators
Transfer operation
The transfer operation mixes two solutions
and
probabilistically to explore new regions of the search space. The operation is defined as:
![]() |
65 |
where
is a mixing coefficient. The probability of transfer depends on the fitness difference:
![]() |
66 |
where
is the fitness difference,
is the electron transfer rate, and
is the temperature parameter controlling acceptance probability.
Gradient estimation
The gradient estimation operator directs solutions toward promising regions based on population dynamics. The gradient at a solution
is estimated as:
![]() |
67 |
where
are the
-nearest neighbors of
, and
are weights computed as:
![]() |
68 |
This operator combines local fitness information with distance-based weighting to approximate the descent direction.
Local search
The local search operator refines solutions by introducing stochastic perturbations. It is defined as:
![]() |
69 |
where
is the variance of the perturbation, decreasing exponentially over iterations:
![]() |
70 |
This operator enables fine-tuning in the vicinity of high-quality solutions, balancing exploration and exploitation.
Complexity analysis
Time complexity components
The time complexity of the algorithm arises from three key operations:
- Population operations:
for pairwise interactions during the transfer operation.
71 - Gradient estimation:
where
72
is the number of nearest neighbors used in gradient computation. - Local search:
for perturbation and fitness evaluation.
73
Runtime and convergence rate
The runtime bounds and convergence rate are characterized as follows:
![]() |
74 |
where
is the desired accuracy and
is the strong convexity parameter. The convergence rate satisfies:
![]() |
75 |
with a linear convergence rate:
![]() |
76 |
Extensions
Multi-objective framework
The algorithm can be extended to handle multi-objective problems using Pareto dominance:
![]() |
77 |
The diversity of Pareto solutions is measured as:
![]() |
78 |
The archive of non-dominated solutions is updated dynamically:
![]() |
79 |
where
denotes the non-dominated set operator, and the archive size is limited by
.
Constraint handling
Constraints are handled using penalty functions:
![]() |
80 |
where
increases over iterations. Feasibility is enforced by projecting solutions onto the feasible set:
![]() |
81 |
where
.
Dynamic optimization
For dynamic environments, changes in the objective function are detected using:
![]() |
82 |
and variance-based metrics:
![]() |
83 |
Parameters are adapted dynamically:
![]() |
84 |
where
and
are adaptation rates. The memory of past solutions is updated as:
![]() |
85 |
where
contains the best solutions in the population.
System modelling for grid-connected inverter using MEPO
Basic circuit analysis
The grid-connected inverter is modelled using an LCL filter. The differential equations governing the filter dynamics are given as:
![]() |
86 |
![]() |
87 |
![]() |
88 |
where:
: Inductances of the inverter and grid sides, respectively.
: Filter capacitance.
: Inverter voltage, capacitor voltage, and grid voltage, respectively.
: Inverter-side and grid-side currents, respectively.
State-space representation
Defining the state vector
and the input vector
, the state-space model is represented as:
![]() |
89 |
where:
![]() |
90 |
![]() |
91 |
Transfer functions
The transfer function from inverter voltage to grid current is derived as:
![]() |
92 |
Similarly, the transfer function from inverter voltage to capacitor voltage is:
![]() |
93 |
Power flow equations
The active (
) and reactive (
) power in the
-frame are expressed as:
![]() |
94 |
![]() |
95 |
where
and
are the voltage and current components in the
-frame.
Control system model
The current control loop dynamics are characterized by the natural frequency (
) and damping ratio (
):
![]() |
96 |
![]() |
97 |
where
is the proportional gain of the current controller.
Stability analysis
The stability of the system is determined by analyzing the poles of the state-space system. The characteristic equation is:
![]() |
98 |
and the system is stable if all eigenvalues (
) satisfy:
![]() |
99 |
MEPO optimization variables derivation
Control parameters vector
The optimization parameters for the controller are represented as:
![]() |
100 |
where the subscripts denote:
: Proportional and integral gains of the current controller.
: Proportional and integral gains of the voltage controller.
: Proportional and integral gains of the phase-locked loop (PLL).
Parameter bounds derivation
The bounds for the control parameters are determined by the system dynamics:
![]() |
101 |
![]() |
102 |
![]() |
103 |
where
and
are the current and voltage controller bandwidths, respectively.
Search space normalization
The parameter vector is normalized as:
![]() |
104 |
where
and
define the parameter bounds.
Objective functions derivation
Current control objective
The objective for the current control loop minimizes tracking error and current dynamics:
![]() |
105 |
where
is a weighting factor for current slope.
Voltage control objective
The voltage control loop objective incorporates tracking error, voltage dynamics, and total harmonic distortion (THD):
![]() |
106 |
where THD is calculated as:
![]() |
107 |
PLL performance objective
The PLL objective minimizes phase tracking error and frequency stability:
![]() |
108 |
Combined objective function
The total multi-objective cost is:
![]() |
109 |
where
penalizes constraint violations.
Time-domain metrics
Performance metrics include:
- Settling time:

110 - Overshoot:

111 - Steady-State Error:

112
Result and disscusion
Convergence characteristics
The comparative analysis of MEPO with traditional optimization algorithms (PSO, GA, and DE) highlights its superior convergence properties, as illustrated in Fig. 5. MEPO achieves an exponential decay rate of
, outperforming PSO (
), GA (
), and DE (
), resulting in a 25% reduction in iterations to reach steady-state. The confidence bands (
) indicate MEPO maintains the smallest variance (
) compared to PSO (
), GA (
), and DE (
), ensuring consistent optimization performance. The boxplot analysis further reveals MEPO’s median final objective value (
) is significantly lower than PSO (
), GA (
), and DE (
), with a compact interquartile range (
) and minimal outliers, indicating highly consistent results across multiple runs.
Fig. 5.
MEPO convergence analysis and comparison.
MEPO demonstrates rapid initial convergence, achieving 85% of the total objective reduction within the first 20 iterations, compared to 65%, 55%, and 70% for PSO, GA, and DE, respectively. This advantage is maintained throughout the optimization process, with MEPO requiring an average of 85 iterations to converge (
), compared to 120, 150, and 110 for PSO, GA, and DE. Additionally, MEPO exhibits a near-Gaussian distribution of final solutions with tight clustering around the optimal value (
) and a low coefficient of variation (0.051). The algorithm achieves a 95% success rate in reaching the global optimum, outperforming PSO (87%), GA (82%), and DE (89%), with superior robustness demonstrated across varying initial conditions and computational scenarios.
Controller parameter optimization results
The MEPO algorithm performs well in optimizing grid-connected inverter controller parameters, as shown in Fig. 6. For current control, MEPO achieves optimal gains (
,
) with a 7.6% improvement over traditional methods. The voltage controller parameters (
,
) and PLL settings (
,
) exhibit enhanced stability margins and dynamic response.
Fig. 6.
Controller parameter optimization results.
Dynamic performance metrics reveal MEPO’s advantages with a faster rise time (0.8 ms) and reduced settling time (2.5 ms), representing a 34.2% improvement over PSO and GA, shown in Fig. 7. The overshoot is maintained at 4.2%, while the total harmonic distortion (THD) is reduced to 1.8%, ensuring superior power quality. Frequency response analysis shows an improved phase margin of
and a bandwidth of 1.2 kHz.
Fig. 7.
Step and frequency response.
The robustness index (0.95) confirms MEPO’s stability under parameter variations, maintaining performance within
tolerance. Computational efficiency is evident with 25% faster convergence compared to conventional methods, requiring only 85 iterations to reach the optimal solution. These results validate MEPO’s effectiveness in achieving balanced control performance while meeting grid code requirements.
Technical analysis of MEPO under different grid condition
The analysis of time-domain waveforms and THD comparisons highlight significant differences in grid performance under varying conditions, as shown in Figs. 8 and 9. Strong grid scenarios exhibit minimal voltage distortion and low THD levels (voltage THD
, current THD
), indicating stable and high-quality power delivery. Weak grid conditions, however, show amplitude fluctuations (
–
) and increased THD levels (voltage THD up to
, current THD exceeding
), while very weak grids present the highest distortion, exceeding grid code limits. These findings emphasize the correlation between waveform distortions, harmonic pollution, and grid strength, with weaker grids experiencing higher harmonic content and more severe waveform degradation.
Fig. 8.
Voltage and current profile under different THD.
Fig. 9.
Voltage and current profile under different impedance.
The power factor and voltage profiles illustrate the diminishing stability of weak grids, where power factors drop below 0.9 and voltage levels dip to 0.9 pu or lower, as shown in Fig. 10. Fluctuation analysis confirms increased volatility, with voltage fluctuations reaching
and power fluctuations exceeding
in very weak grids. The visualizations collectively demonstrate that weak grid conditions exacerbate harmonic distortion, reduce power factor, and impair voltage stability. These insights underscore the critical need for enhanced voltage support and harmonic mitigation to maintain grid performance in challenging scenarios.
Fig. 10.
Weak grid overall performance.
The performance comparison between MEPO, PSO, GA, and PI controllers highlights MEPO’s better performance across key metrics as shown in Tables 3, 1 and 2. MEPO achieves faster rise time (0.8 ms), settling time (2.5 ms), and minimal overshoot (4.2%), while maintaining lower THD (1.8%) and higher power factor (0.998), ensuring better grid compliance. Computationally, MEPO converges faster (1.2 s) with lower cost (45 ms per iteration), making it ideal for real-time applications. Statistical analysis over 100 trials confirms its robustness with a 95% success rate and a low objective value of
. In grid fault scenarios, MEPO excels with faster recovery (35 ms for three-phase faults) and voltage restoration (92–95%). MEPO demonstrates a 25–65% performance improvement, making it highly suitable for grid-connected inverters, particularly in weak grid conditions.
Table 3.
Grid fault response analysis.
| Fault type | MEPO | PSO | GA | PI |
|---|---|---|---|---|
| Three-phase fault | ||||
| Recovery time (ms) | 35 | 48 | 52 | 65 |
| Voltage recovery (%) | 92 | 85 | 82 | 75 |
| THD during recovery (%) | 2.8 | 3.5 | 3.8 | 4.5 |
| Single-phase fault | ||||
| Recovery time (ms) | 28 | 38 | 42 | 55 |
| Voltage recovery (%) | 95 | 88 | 85 | 80 |
| THD during recovery (%) | 2.2 | 3.0 | 3.2 | 4.0 |
| Phase-to-phase fault | ||||
| Recovery time (ms) | 32 | 45 | 48 | 60 |
| Voltage recovery (%) | 93 | 86 | 84 | 78 |
| THD during recovery (%) | 2.5 | 3.2 | 3.5 | 4.2 |
Table 1.
Comprehensive performance comparison of optimization methods.
| Performance metrics | MEPO | PSO | GA | PI |
|---|---|---|---|---|
| Dynamic response characteristics | ||||
| Rise time (ms) | 0.8 | 1.2 | 1.5 | 1.8 |
| Settling time (ms) | 2.5 | 4.2 | 4.8 | 6.5 |
| Overshoot (%) | 4.2 | 7.8 | 8.5 | 12.3 |
| Steady-state error (%) | 0.2 | 0.4 | 0.5 | 0.8 |
| Power quality metrics | ||||
| THD (%) | 1.8 | 2.5 | 2.7 | 3.2 |
| Power factor | 0.998 | 0.992 | 0.990 | 0.985 |
| Voltage regulation (%) | 1.2 | 1.8 | 2.1 | 2.5 |
| Computational performance | ||||
| Convergence time (s) | 1.2 | 2.8 | 3.5 | N/A |
| Computational cost (ms) | 45 | 85 | 120 | 5 |
| Memory usage (MB) | 2.5 | 3.8 | 4.2 | 0.5 |
| Robustness analysis | ||||
| Success rate (%) | 95 | 87 | 82 | N/A |
Mean objective ( ) |
2.34 | 3.56 | 4.12 | N/A |
Standard deviation ( ) |
1.2 | 2.8 | 3.5 | N/A |
| Grid fault response | ||||
| Fault recovery time (ms) | 35 | 48 | 52 | 65 |
| Voltage dip recovery (%) | 92 | 85 | 82 | 75 |
| Frequency stability (Hz) | ±0.1 | ±0.2 | ±0.25 | ±0.3 |
| Cost function analysis | ||||
Final cost value ( ) |
1.8 | 2.4 | 2.7 | 3.5 |
| Iteration count | 85 | 120 | 150 | N/A |
| Convergence rate | 0.95 | 0.88 | 0.85 | N/A |
Table 2.
Statistical performance analysis (100 Trials).
| Statistical metric | MEPO | PSO | GA | PI |
|---|---|---|---|---|
| Success rate (%) | 95 | 87 | 82 | N/A |
Mean total cost ( ) |
2.34 | 3.56 | 4.12 | N/A |
Standard deviation ( ) |
1.2 | 2.8 | 3.5 | N/A |
Minimum cost ( ) |
2.15 | 3.28 | 3.85 | N/A |
Maximum cost ( ) |
2.52 | 3.95 | 4.45 | N/A |
| Coefficient of variation (%) | 5.1 | 7.9 | 8.5 | N/A |
| Confidence level (95%) | ±0.12 | ±0.28 | ±0.35 | N/A |
| Convergence reliability (%) | 98 | 92 | 88 | N/A |
The results highlight the effectiveness of the MEPO algorithm compared to PSO and GA in d-q axis current control under fault conditions, as shown in Fig. 11. During the fault period (0.2 s to 0.3 s), the MEPO-optimized controller demonstrates superior dynamic response with minimal oscillations, faster recovery, and reduced steady-state error. This behaviour can be attributed to MEPO’s bio-inspired design, which adaptively balances global exploration and local exploitation, enabling precise parameter tuning for grid-connected inverter systems. In contrast, PSO and GA exhibit larger deviations and prolonged settling times due to their limited adaptive capabilities and slower convergence. The zoomed sections of the d-axis and q-axis current plots illustrate MEPO’s ability to suppress current spikes and stabilize the system more rapidly, maintaining grid code compliance.
Fig. 11.
q and d-axis current response under fault.
MEPO’s enhanced performance is particularly evident in its smoother current transitions and reduced harmonic distortions, critical for power quality in weak or faulted grids. These results underscore MEPO’s robustness and suitability for dynamic grid conditions, making it a promising optimization approach for inverter-based renewable energy integration.
The performance of different control optimization methods—MEPO, PSO, GA, and PI—under various grid conditions, including normal operation, weak grids, and fault scenarios, is analyzed. The results are evaluated for frequency deviation, rate of change of frequency (ROCOF), and active power responses to assess each method’s stability, adaptability, and resilience.
The evaluation of grid control methods highlights the distinctive advantages of the MEPO controller across diverse grid conditions, as shown in Fig. 12. MEPO’s adaptive gain mechanism in frequency response analysis enables superior performance, particularly under challenging scenarios. For normal grid conditions (SCR = 20), MEPO maintains frequency deviations within
Hz. In weak grids (SCR = 2), MEPO effectively limits deviations to
Hz, a 40% improvement compared to the conventional PI controller, which exhibits deviations of
Hz. Optimization-based methods such as PSO and GA provide intermediate performance, achieving frequency nadirs of
Hz and
Hz, respectively, in weak grid conditions.
Fig. 12.
Frequency response comparison of MEPO, PSO, GA, and PI under varying grid conditions.
ROCOF (Rate of Change of Frequency) analysis reveals MEPO’s enhanced system stability. By leveraging dynamic feedback and feed-forward compensation, MEPO limits ROCOF to
Hz/s across all grid conditions, as shown in Fig. 13. This robustness is particularly evident during fault scenarios, where its augmented damping coefficient (
) effectively suppresses oscillatory behaviour. Conversely, PSO and GA controllers exhibit higher ROCOF peaks of
Hz/s and
Hz/s during fault recovery. The PI controller faces significant challenges, with ROCOF spikes reaching
Hz/s, indicating potential instability.
Fig. 13.
ROCOF response comparison of MEPO, PSO, GA, and PI under varying grid conditions.
Power response evaluations further underscore MEPO’s advantages. The adaptive feedback mechanism (
) integrated within MEPO achieves settling times of 0.8-1.2 seconds across varying grid conditions, as shown in Fig. 14. Power oscillations are controlled within
of steady-state values, demonstrating rapid disturbance rejection capabilities. In contrast, PSO and GA controllers exhibit longer settling times of 1.5-2.0 seconds, while the PI controller requires 2.5-3.0 seconds to stabilize, especially under weak grid scenarios (SCR
).
Fig. 14.
Power response comparison of MEPO, PSO, GA, and PI under varying grid conditions.
Fault resilience analysis highlights MEPO’s robust performance under severe conditions, such as three-phase faults with voltage dips to 0.1 pu. MEPO effectively maintains stability, limiting frequency deviations to
Hz through condition-specific gain adaptation. Its dynamic response optimally balances disturbance rejection and stability margins via a multi-loop control framework. Compared, PSO and GA methods show slower recovery and 25-30% higher settling times, while the PI controller exhibits pronounced deviations and prolonged instability.
The direct-axis current (d) primarily governs active power control, while the quadrature-axis current (q) regulates reactive power, as shown in Fig. 15. A transient oscillatory response is observed upon connection due to the control system adjusting to stabilize the inverter currents. The system achieves a steady state with minimal ripples in both currents, indicating successful active and reactive power decoupling. The d-axis current stabilizes around its reference value, ensuring consistent active power delivery. In contrast, the q-axis current remains near zero, reflecting minimal reactive power exchange, as shown in Fig. 16. The transient behavior results from dynamic load balancing and control loop adaptation, and the steady-state performance demonstrates efficient power exchange with minimal impact on grid voltage stability.
Fig. 15.
The direct-axis (d) and quadrature-axis (q) currents.
Fig. 16.
Transient responses of active and reactive power.
Figures 17 and 18 show the grid voltage and inverter current. The waveforms closely match the grid frequency ( 49.9 Hz), demonstrating synchronization with the grid. The result confirms that the inverter’s synchronization mechanisms effectively track the grid frequency and minimize disturbances during power injection.
Fig. 17.
Grid voltage waveform.
Fig. 18.
Inverter current waveform.
Figure 19 shows that the inverter current and voltage were both in phase. The sine PWM is shown in Fig. 20, where the modulation index is close to 9. The LCL filter’s frequency response exhibits critical performance characteristics across multiple frequency bands, as shown in Fig. 21. At low frequencies (100 Hz – 1 kHz), it maintains stable attenuation between -70 dB and -80 dB with phase oscillation between
and
, ensuring fundamental frequency tracking. The resonant point occurs near 100 kHz, showing a magnitude of -53.31 dB and a phase angle of
, requiring careful stability consideration. High-frequency behavior (above 1 MHz) demonstrates strong harmonic attenuation below -30 dB with a -60 dB/decade slope, confirming effective third-order filtering performance.
Fig. 19.
Inverter current and voltage waveforms.
Fig. 20.
Sine PWM waveform with a modulation index 0.9.
Fig. 21.
Frequency response of the LCL filter.
Detailed system, filter, controller, and algorithm parameters are provided in the supplementary materials. Table S1 presents the complete system parameters including grid frequency, voltage levels, and rated power specifications. Table S2 details the LCL filter design parameters with inverter-side and grid-side inductances, filter capacitance, and resonant frequency characteristics. Table S3 lists the optimized controller gains for current control, voltage regulation, and phase-locked loop obtained through the MEPO algorithm. Table S4 provides the MEPO algorithm hyperparameters including initial step size, decay rate, transfer rate, and local search radius. Table S5 summarizes the grid operating conditions ranging from very weak (SCR = 1.5) to strong (SCR = 20) grid scenarios used in the validation studies.
Conclusion
This paper has introduced the Mitochondrial Energy Production Optimization (MEPO) algorithm, an innovative bio-inspired optimization approach that significantly advances the state-of-the-art in grid-connected inverter control systems. Through systematic mathematical formulation and comprehensive experimental validation, MEPO demonstrates substantial improvements in both optimization performance and grid stability enhancement, particularly in challenging weak grid scenarios.
The proposed algorithm exhibits remarkable convergence characteristics, achieving an exponential decay rate of
and maintaining the lowest variance (
) among contemporary optimization methods. This performance represents a significant advancement over existing approaches, with MEPO demonstrating a 25% reduction in optimization time compared to Particle Swarm Optimization (
), Genetic Algorithm (
), and Differential Evolution (
). The algorithm’s superior dynamic response is evidenced by its achievement of
rise time and
settling time, marking a 34.2% improvement over traditional control methodologies.
In weak grid conditions (SCR = 2), MEPO demonstrates exceptional stability characteristics, effectively limiting frequency deviations to
and Rate of Change of Frequency (ROCOF) to
. This performance represents a 40% improvement over conventional PI controllers, while maintaining superior power quality metrics with Total Harmonic Distortion (THD) at
and power factor at 0.998. The algorithm’s robustness index of 0.95 confirms its stability under parameter variations, consistently maintaining performance within
tolerance across diverse operating conditions.
Extensive statistical validation through 100 independent trials establishes MEPO’s reliability with a 95% success rate and consistent achievement of the lowest objective value (
). The algorithm’s computational efficiency, evidenced by its
convergence time, validates its applicability for real-time grid control applications. These results collectively establish MEPO as a robust solution for grid-connected inverter optimization, particularly in scenarios demanding high reliability and rapid adaptation to grid disturbances.
Future research directions should explore three key areas: the extension of MEPO to coordinate multiple inverters within microgrid environments, its integration with hybrid energy storage systems, and the development of adaptive real-time optimization capabilities. These advancements would further enhance MEPO’s practical utility in increasingly complex grid environments and contribute to the robust integration of renewable energy sources in modern power systems.
Supplementary Information
Acknowledgements
The authors sincerely thank the ReX Lab, National Institute of Technology Arunachal Pradesh, for providing essential hardware for this study’s experiments.
Author contributions
Mrinal Kanti Rajak: Conceptualization of the research problem and methodology; development of mathematical models and algorithms; software implementation and simulation; formal analysis and validation of results; writing—original draft preparation; writing—review and editing; visualization and data presentation. Rajen Pudur: Supervision and project administration; methodology verification; resources and funding acquisition; validation of mathematical formulations; writing—review and editing; investigation support.
Funding
No external funding was received for this research.
Data availability
The data presented in this study are available from the corresponding author upon reasonable request.
Declarations
Competing interests
The authors declare no competing interests.
Footnotes
Publisher’s note
Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Supplementary Information
The online version contains supplementary material available at 10.1038/s41598-025-28884-9.
References
- 1.Boscaino, V. et al. Grid-connected photovoltaic inverters: Grid codes, topologies and control techniques. Renew. Sustain. Energy Rev.189, 113903 (2024). [Google Scholar]
- 2.Zhong, Q. C. & Hornik, T. Control of Power Inverters in Renewable Energy and Smart Grid Integration (John Wiley & Sons, 2012). [Google Scholar]
- 3.Kenyon, R. W. et al. Stability and control of power systems with high penetrations of inverter-based resources: An accessible review of current knowledge and open questions. Solar Energy210, 149–168 (2020). [Google Scholar]
- 4.Xu, S., Xue, Y. & Chang, L. Review of power system support functions for inverter-based distributed energy resources-standards, control algorithms, and trends. IEEE Open J. Power Electron.2, 88–105 (2021). [Google Scholar]
- 5.ElDemery, H. A., Hasanien, H. M., Alharbi, M., & Sun, C. Dynamic performance improvement of oscillating water column wave energy conversion system using optimal walrus optimization algorithm-based control, Ain Shams Engineering Journal, (2024).
- 6.Bouhadji, F., Bouyakoub, I., Mehedi, F., & Kacemi, W. M.: Optimization of grid power quality using third order sliding mode controller in PV systems with multilevel inverter, Energy Reports, (2024).
- 7.Guo, W. & Xu, W. Research on optimization strategy of harmonic suppression and reactive power compensation of photovoltaic multifunctional grid-connected inverter. Int. J. Elect. Power & Energy Syst.145, 108649 (2023). [Google Scholar]
- 8.Reveles-Miranda, M., Flota-Bañuelos, M., Chan-Puc, F., Ramirez-Rivera, V. & Pacheco-Catalán, D. A hybrid control technique for harmonic elimination, power factor correction, and night operation of a grid-connected PV inverter. IEEE J. Photovolt.10(2), 664–675 (2020). [Google Scholar]
- 9.Zhang, X., Gong, L. J., Zhang, Y., Ma, X., & Han, L.: A Novel Virtual Inductor Optimization Methodology of Virtual Synchronous Generators for Enhanced Power Decoupling, SSRN, (2024).
- 10.Annaswamy, A. M. & Amin, M. Smart Grid Research: Control Systems–IEEE Vision for Smart Grid Controls: 2030 and Beyond. IEEE, pp. 1–168, (2013).
- 11.Babu, T. S. et al. A comprehensive review of hybrid energy storage systems: Converter topologies, control strategies and future prospects. IEEE Access8, 148702–148721 (2020). [Google Scholar]
- 12.Babu, N. Adaptive grid-connected inverter control schemes for power quality enrichment in microgrid systems: Past, present, and future perspectives. Electric Power Syst. Res.230, 110288 (2024). [Google Scholar]
- 13.Ward, L., Subburaj, A., Demir, A., Chamana, M. & Bayne, S. B. Analysis of grid-forming inverter controls for grid-connected and islanded microgrid integration. Sustainability16(5), 2148 (2024). [Google Scholar]
- 14.Badrudeen, T. U., Nwulu, N. I. & Gbadamosi, S. L. Low-inertia control of a large-scale renewable energy penetration in power grids: A systematic review with taxonomy and bibliometric analysis. Energy Strategy Rev.52, 101337 (2024). [Google Scholar]
- 15.Ma, M. Grid-connected PV system modelling based on grid-forming inverters, (2024).
- 16.Yan, L., Zhao, Z., Ullah, Z., Deng, X., & Zhang, Y. Optimization of optical storage VSG control strategy considering active power deviation and virtual inertia damping parameters, Ain Shams Engineering Journal, (2024).
- 17.Abdolrahimi, H., & Khaburi, D. A. Model predictive control of a Brushless Cascade Doubly-Fed Induction Generator with torque regulation for stand-alone applications, Heliyon, (2024).
Associated Data
This section collects any data citations, data availability statements, or supplementary materials included in this article.
Supplementary Materials
Data Availability Statement
The data presented in this study are available from the corresponding author upon reasonable request.