Skip to main content
Scientific Reports logoLink to Scientific Reports
. 2026 Jan 27;16:3741. doi: 10.1038/s41598-025-34481-7

A hybrid fuzzy-PIDD² control strategy for coordinated LFC and AVR in renewable-integrated multi-area power systems

Mohamed H T Omar 1, Ragi A Hamdy 1, Hossam Kotb 1,
PMCID: PMC12852113  PMID: 41593142

Abstract

This paper presents a novel hybrid control strategy that integrates a Fuzzy Proportional–Integral–Derivative Double Derivative (FPIDD²) controller with a conventional PIDD² controller for Load Frequency Control (LFC) and Automatic Voltage Regulation (AVR) in multi-area interconnected power systems, respectively. The proposed FPIDD²+PIDD² hybrid scheme enhances the overall dynamic stability and robustness of power systems operating under high renewable energy penetration. Controller parameters are optimally tuned using different metaheuristic algorithms, namely the Particle Swarm Optimization (PSO), Gorilla Troops Optimizer (GTO), and Marine Predators Algorithm (MPA). The proposed hybrid controller’s performance is evaluated against conventional PID and standalone PIDD² controllers under various disturbances, including step load changes, random load variations, and renewable energy fluctuations, where control performance is evaluated based on the Integral of Time-weighted Absolute Error (ITAE) criterion. Within the simulated test cases, the proposed FPIDD²+PIDD² controller achieves notable performance improvement, reducing ITAE by up to 94% and 90% compared to conventional PID and standalone PIDD² controllers, respectively. These results confirm the hybrid controller’s smooth transient response, enhanced damping, and improved robustness against nonlinearities and system uncertainties.

Keywords: Fuzzy control, Load frequency control, Optimization, Automatic voltage regulation, Renewable energy, Two area interconnected power system

Subject terms: Energy science and technology, Engineering, Mathematics and computing

Introduction

Background and research gap

Modern power systems have become increasingly complex due to the global surge in electricity demand and the extensive integration of renewable energy sources (RES) such as wind and solar power1. The intermittent and uncertain nature of these resources, combined with unpredictable load variations, generator outages, and nonlinear interactions between interconnected areas, makes system stability and reliability more difficult to maintain24. These fluctuations lead to deviations in both frequency and voltage, which can degrade efficiency, damage sensitive equipment, and even trigger large-scale cascading blackouts57. Traditional control frameworks employing Load Frequency Control (LFC) and Automatic Voltage Regulation (AVR) schemes, which are typically based on conventional PID controllers, have long been used to stabilize power systems8. However, PID controllers are generally tuned for nominal operating points and exhibit degraded performance under nonlinear, time-varying, and highly coupled conditions9,10. Their inability to dynamically adapt to the changing dynamics of systems with high renewable penetration, electric vehicle (EV) charging variability, and random load disturbances limit their effectiveness in ensuring overall system robustness. While recent years have witnessed progress in intelligent and optimization-based controllers, there remains a lack of a unified, adaptive, and optimally tuned control strategy that simultaneously manages LFC, AVR, and tie-line power deviations under complex real-world conditions involving nonlinearities, RES integration, EVs, and stochastic load variations1114. Therefore, addressing this specific gap is crucial for improving the resilience and reliability of future power systems, ensuring stable operation despite uncertain and rapidly changing grid environments1517.

Literature review

Modern power systems have witnessed increasing complexity due to the growing penetration of renewable energy and the need for robust control mechanisms. In this context, several enhanced control strategies have been proposed to improve system dynamic performance, stability, and resilience under varying operational conditions. Gu et al.18 presented a comprehensive survey of modern control architectures for resilient power grids, emphasizing the integration of adaptive, predictive, and intelligent controllers to ensure operational reliability under disturbances. Building on this foundation, Sahu et al.19 developed and analyzed a Proportional–Integral–Derivative Double Derivative (PIDD²) controller for load frequency control (LFC) in deregulated environments, demonstrating superior damping and faster convergence compared with classical PID controllers. Ray and Paital20 further improved the robustness of the PIDD² approach for hybrid power systems, achieving better frequency regulation under renewable variability. Dash et al.21 investigated the impact of advanced thyristor-controlled series capacitors in dual-area LFC–AVR systems using interval type-2 fuzzy PID structures, confirming the advantages of higher-order control approaches under nonlinear conditions. Recent advancements have also focused on fractional-order and hybrid PID-based control. Gupta22 introduced a fractional-order PID controller for LFC in deregulated hybrid systems, reporting significant robustness improvements, while Wang et al.23 applied fractional-order control in systems integrated with hydrogen energy storage. Alnefaie et al.24 further optimized multi-area LFC–AVR performance through advanced cascaded controllers under renewable uncertainty.

In parallel, fuzzy logic control has been recognized as a powerful alternative to conventional methods. Zadeh25 originally formulated the concept of fuzzy logic for control systems, establishing the basis for reasoning under uncertainty. Building on this principle, Mishra and Das26 applied an adaptive fuzzy logic–based LFC scheme in renewable-integrated power systems and demonstrated its superior robustness under parameter variations. Hannan et al.27 provided a critical review of fuzzy logic applications for smart grids, confirming its effectiveness in handling nonlinearities and model uncertainties. A. Ali, G. Biru and Bantyirga28 examined the design and potential application of fuzzy logic-based AGC and AVR schemes for multi-area systems, validating their capability in improving voltage and frequency stability. Khan et al.29 further extended fuzzy logic concepts to vehicle-to-grid applications, integrating an adaptive fuzzy AVR controller for ancillary services support in smart grid environments. More recently, Mansour et al.30 enhanced combined LFC–AVR operation using a fuzzy PID controller, and Kalyan et al.31 proposed a hybrid fuzzy PID approach optimized via the HAEFA algorithm to improve coordinated control performance.

Optimization-based controller tuning has also gained widespread attention in the literature. Gad32 offered a systematic review of Particle Swarm Optimization (PSO) and its applications, emphasizing its simplicity and efficiency in handling multidimensional search spaces. Houssein et al.33 discussed major advances in PSO theory and application, focusing on convergence improvements. Fang et al.34 provided a recent survey highlighting algorithmic trends and hybridization techniques for PSO. Sengupta et al.35 and Grassi et al.36 introduced hybridized PSO frameworks that enhance exploration and exploitation balance, while Sienz and Innocente37 demonstrated PSO’s application in engineering scheduling problems, confirming its suitability for practical optimization tasks in control systems. Izci et al.38 recently optimized advanced PID controllers using hybrid metaheuristics for dynamic load frequency control, while Doan and Nguyen39 proposed a multi-stage hybrid smart controller considering renewable and HVDC integration.

Beyond PSO, the Marine Predator Algorithm (MPA) and Gorilla Troops Optimizer (GTO) have emerged as effective metaheuristics for complex optimization challenges. Faramarzi et al.40 first introduced the MPA inspired by predator-prey dynamics, offering fast convergence and strong global search capability. Singh et al.41 applied the MPA to engineering design optimization, validating its efficiency. Su et al.42 enhanced the algorithm through Lévy flight and Brownian motion mechanisms, while Jang et al.43 provided a detailed review of MPA variants and engineering applications. Xie et al.44 and Zadeh et al.45 evaluated MPA performance against other global optimizers, highlighting its adaptability, and Zhang et al.46 analyzed the impact of environmental factors on MPA’s convergence characteristics. Similarly, Mirjalili and Kazem47 proposed the Gorilla Troops Optimizer (GTO), a social-behavior–inspired metaheuristic demonstrating strong exploration properties. Fard and Wang48 combined GTO with genetic algorithms to improve multi-objective optimization performance, and Chen et al.49 applied GTO for solving multimodal engineering problems. Zhang et al.50 improved the exploration–exploitation balance within GTO, while Wang et al.51 analyzed its performance in real-world engineering design problems. Araujo and Andrade52 hybridized GTO with PSO to address multi-objective scenarios effectively, and Yadav and Bhavsar53 conducted a comparative study confirming its competitiveness against other evolutionary algorithms. Mishra et al.54 applied adaptive optimization techniques for LFC in multi-area power systems with energy storage, illustrating the practical relevance of these algorithms. Wang and Li55 further showed that coordinated LFC–AVR control, optimized through such algorithms, enhances overall system dynamic performance under renewable integration. Complementary reviews such as Raja Sathish Kumar et al.56 have emphasized the importance of smart control strategies in achieving these improvements.

Because power systems are inherently complex and geographically distributed, accurate yet tractable modeling techniques are essential. Zhang et al.57 discussed challenges associated with managing the growing complexity of modern grids and proposed methods for reducing model order without compromising essential dynamics. Gupta and Chakrabarti58 compared different modeling techniques for stability analysis, highlighting the trade-off between computational efficiency and dynamic accuracy. Alam and Saha59 validated two-area interconnected power system models for renewable integration studies, confirming their accuracy in replicating real-world conditions. Wang et al.60 proposed simplified dynamic models to facilitate stability and control analysis, while Pandey and Bansal61 introduced reduced-order modeling approaches for large-scale power systems. To represent the interconnection characteristics between regions, Chen et al.62 studied two-area to multi-area system dynamics, showing how tie-line interactions affect overall stability. Fernandez et al.63 conducted a detailed two-area case study on power flow coordination, and Li and Mi64 identified frequency regulation challenges associated with inter-area coupling. Kundur and Morison65 contributed foundational insights into the dynamic behavior of interconnected systems, establishing the two-area model as a benchmark for theoretical and experimental studies. Recent works have continued refining these modeling approaches. Bevrani and Hiyama66 emphasized balancing modeling accuracy and computational simplicity in power system simulations. Sharma et al.67 proposed computationally efficient dynamic models for real-time studies, and Eltamaly et al.68 extended these frameworks from two-area to large-scale configurations. Recent review studies such as Sharma and Patel69, and Doan and Nguyen70 have further highlighted the growing need for intelligent and hybrid control strategies to address LFC–AVR coordination challenges in renewable-rich environments. Based on the insights from these studies, the two-area interconnected power system model is adopted in this work as a practical yet accurate representation of large-scale systems. This model facilitates the evaluation of the proposed control strategy while maintaining computational efficiency and ensuring dynamic fidelity.

Paper organization and contribution

The paper begins with system modeling shown in Sect. 2, followed by the proposed controllers’ structures in Sect. 3, while Sect. 4 provides performance evaluations through simulation results and comparative analyses conducted across four case studies. The study concludes in Sect. 5 with key findings, practical insights, and future research directions, ensuring a logical and reproducible flow throughout. The main contributions of this study could be summarized as the following:

  • Introducing a hybrid FPIDD² controller, integrating fuzzy logic with the PIDD² structure to effectively enhance the two-area interconnected power systems dynamic stability.

  • Demonstrating the adaptability of controllers, including PID, PIDD², and FPIDD²+PIDD² across diverse scenarios, including various load disturbances, high renewable penetration, and grid conditions.

  • Conducting a detailed comparison between the proposed control scheme (FPIDD²+PIDD²) and the traditional PID as well as standard PIDD² controllers, using transient response metrics and ITAE as the fitness function.

  • Employing diverse metaheuristic algorithms, including PSO, MPA, and GTO for controller tuning, and evaluates their influence on performance and consistency.

Investigated system

System description

As shown per Fig. 1, the study investigates a two-area interconnected power system, in which each area contains conventional generation units with a nominal load of 1740 MW and a capacity of 2000 MW. The generation mix includes thermal (1000 MW), gas (240 MW), and hydro (500 MW) plants. Furthermore, the system incorporates renewable energy sources (RES), with a 420 MW wind power unit connected to Area-2 and a 300 MW photovoltaic (PV) unit injected in Area-1, producing a total of 720 MW71. Each area also includes electric vehicle (EV) charging units, adding complexity to system dynamics. Detailed system configuration and parameters are presented in Table 1. The study illustrates the following two key nonlinearities that affect system performance:

Fig. 1.

Fig. 1

Block diagram of the investigated two-area interconnected power system.

Table 1.

Power system parameters.

Model Constant Initial Magnitude Model Constant Initial Magnitude Model Constant Initial Magnitude
B g 0.0490 s PF Th 0.5747 T n 1
C g 1 PFWT, PFPV 0.025 Tps1, Tps2 11.49
K a 10 RTh, Rhyd, Rg 2.4 Hz/MW T r 10.2000 s
Ke, Kn, Ks 1 T 12 0.0433 MW T rh 28.7490 s
K EV 1 T a 0.1 T rs 4.9000 s
Kps1, Kps2 68.96 T cd 0.2000 s T s 0.01
K r 0.3 T cr 0.0100 s T sg 0.0600 s
N 1 0.8 T e 0.4 T t 0.3000 s
N 2 − 0.2/π T EV 1 T w 1.1000 s
PF g 0.138 T f 0.2390 s X g 0.6000 s
PF hyd 0.287 T gh 0.2000 s Y g 1.1000 s
  • Generation Rate Constraint (GRC), which is driven by physical limitations of thermal and hydro units, restricts how fast generators can change output, introducing nonlinear dynamics.

  • Governor Dead Band (GDB), which creates a non-responsive zone where minor input changes do not affect governor output, reducing control sensitivity during small disturbances72.

For hydropower, the GRC is 360% p.u./min (0.06 p.u. MW/s) for decreasing and 270% p.u./min (0.045 p.u. MW/s) for increasing output; for thermal units, it is 10% p.u./min (0.0017 p.u. MW/s) in both directions73. Accurate modeling of these effects is essential for reliable simulation and control design74,75.

Automatic voltage regulation

The generator’s terminal voltage (Vg) can fluctuate in response to changes in reactive power load, as illustrated in Fig. 2.

Fig. 2.

Fig. 2

Schematic diagram of the Automatic Voltage Regulation (AVR) loop with coupling coefficients.

As a result, the AVR system seeks to reduce reactive power losses brought on by voltage discrepancies between the target output voltage (Vout) and the terminal voltage (Ve) of the exciter. In this case, the generator’s terminal voltage is sensed via a single-phase potential transformer. Next, a reference voltage (Vref) is compared to this sensed voltage, represented by the symbol (Vs). In order to manage the exciter’s field and, consequently, the terminal voltage, the ensuing error signal is amplified to be (Va). The induced electromotive force (emf) fluctuates as a result of this action, changing the field current of the generator.

The detailed coupling coefficient of the Automatic Voltage Regulation (AVR) unit for the system under study is shown per Table 276.

Table 2.

AVR coupling Coefficients.

Coupling Coefficient Description Value
K1 Represents the sensitivity of terminal voltage (Vout) to internal EMF variations 1.5
K2 Reflects how small changes in stator EMF influence real power 0.3
K3 Denotes the impact of rotor angle changes on terminal voltage 0.1
K4 Demonstrates how rotor angle variances affect stator EMF 1.4
K5 Quantifies how variations in stator EMF affect rotor angle 0.5

PV generation unit

The Photovoltaic (PV) unit model in Area 1 is presented as shown in Fig. 377. In this model, the white-noise block is deployed to produce random output fluctuations, which are then multiplied by the typical output power of an actual PV plant.

Fig. 3.

Fig. 3

System model for PV unit77.

The fluctuations of the output power generated by the PV plant are shown in Fig. 4.

Fig. 4.

Fig. 4

Output power of the PV unit.

Wind generation unit

Figure 5 illustrates the output power of the 93 wind units, each generating 0.75 MW, resulting in a total wind farm output of approximately 70 MW. The figure represents the power trend based on actual wind farm data, and the corresponding model, shown in Fig. 6, employs a white-noise block to generate an arbitrary wind speed profile, which is multiplied by the wind speed. The wind turbine output power (Pw) is 750 kW and the rated wind speed (Vw) is 15 m/s78.

Fig. 5.

Fig. 5

Output power of the wind-turbine unit.

Fig. 6.

Fig. 6

System model of the wind power plant78.

Electric vehicle

Electric vehicle (EV) integration into modern power systems, especially with two-area interconnected grids, has become an important research area79,80. EVs are increasingly seen as not only mobile loads but also as potential distributed energy resources that can help improve grid stability81. When aggregated and controlled properly, EVs can support load frequency control (LFC) by acting as flexible demand or storage units, capable of discharging and/or charging according to the frequency deviations of the power system82. Because of this, EVs are particularly helpful in power systems that have a high penetration of renewable energy, where frequency and voltage fluctuations are more frequent83. In most control studies, EV dynamics are modeled using simplified linear models for easier system analysis, controller tuning, and performance evaluation84. This simplification is especially useful when incorporating EVs into the overall system dynamics in LFC studies, where multiple control loops, such as AVR, LFC, governor, turbine, and EV units, interact85. A widely used linear model for EV response is the first-order transfer function86. This model is favored because it captures the typical first-order lag behavior seen in load and response delays in aggregated EV systems. In addition, it provides a balance between simplicity and dynamic accuracy, enabling researchers to evaluate the interaction of EVs with conventional control elements in the system87. In this study, the first-order transfer function model of EV is presented as follows88,89:

graphic file with name d33e1840.gif 1

Proposed controllers

Controllers’ structures

As mentioned earlier, this study proposes an intelligent control strategy that employs two types of controllers. The first is a Proportional–Integral–Derivative–Double–Derivative (PIDD²) controller, implemented in the Automatic Voltage Regulation (AVR) loops. The second is a hybrid intelligent controller, referred to as the FPIDD² controller, which integrates the PIDD² structure with a Fuzzy Logic algorithm and is applied to the Load Frequency Control (LFC) loops. The detailed architectures of both the PIDD² and FPIDD² controllers are presented in the following sections.

PIDD2 controller

The layout of the PIDD2 controller is shown in Fig. 7.

Fig. 7.

Fig. 7

Block diagram of the PIDD² controller.

The mathematical formulation of the PIDD² controller is expressed as follows90,91:

graphic file with name d33e1881.gif 2

The corresponding time-domain representation is:

graphic file with name d33e1887.gif 3

Fuzzy logic controller

The fuzzy logic controller produces an output Inline graphic based on the centroid (centre-of-gravity) defuzzification method, expressed as follows92,93:

graphic file with name d33e1908.gif 4

Where Inline graphic is the aggregated output membership function of the fuzzy inference system and Ω is the universe of discourse of the output variable.

Fuzzy proportional integral derivative double derivative (FPIDD2) controller

The FPIDD² controller integrates the fuzzy inference mechanism with the PIDD² control structure. The general expression for the combined Fuzzy–PIDD² (FPIDD²) controller is given by:

graphic file with name d33e1926.gif 5

Substituting the time-domain formulation of the PIDD² controller yields the resulting FPIDD² formula, as follows:

graphic file with name d33e1932.gif 6

Figure 8 illustrates the structure of the FPIDD² controller, which receives two input signals, including error (E) and rate of error change (CE). The gain constants (KE) and (KCE) represent the scaling factors of the input signals, respectively92,93.

Fig. 8.

Fig. 8

Architecture of the proposed Fuzzy PIDD² (FPIDD²) controller.

The two input signals Error (E) and Rate of Change of Error CE) are processed by the fuzzy logic controller, which then converts them into five linguistic variables: Large Negative (LN), Small Negative (SN), Zero (Z), Small Positive (SP), and Large Positive (LP). The number of linguistic terms in a fuzzy logic controller reflects a trade-off between control resolution and computational complexity94. Although three-term configurations are often adopted for simplicity, designs with seven or more terms can offer finer control precision95. In this study, five fuzzy sets (NL, NS, Z, PS, PL) were employed, representing a balanced choice widely reported in the literature as an effective compromise between performance and computational cost96. However, future work may be required to investigate alternative configurations with a higher number of linguistic terms to assess potential improvements in control accuracy97. Table 3 displays the Fuzzy Logic Controller’s rule basis, on which the Fuzzy Inference System (FIS) is based on Mamdani.

Table 3.

The fuzzy logic controller’s rule basis.

Error (E) Rate of Change of Error (CE)
LN
(Large Negative)
SN
(Small Negative)
Z
(Zero)
SP
(Small Positive)
LP
(Large Positive)

LN

(Large Negative)

LN

(Large Negative)

LN

(Large Negative)

SN

(Small Negative)

SN

(Small Negative)

Z

(Zero)

SN

(Small Negative)

LN

(Large Negative)

SN

(Small Negative)

SN

(Small Negative)

Z

(Zero)

SP

(Small Positive)

Z

(Zero)

SN

(Small Negative)

SN

(Small Negative)

Z

(Zero)

SP

(Small Positive)

SP

(Small Positive)

SP

(Small Positive)

SN

(Small Negative)

Z

(Zero)

SP

(Small Positive)

SP

(Small Positive)

LP

(Large Positive)

LP

(Large Positive)

Z

(Zero)

SP

(Small Positive)

SP

(Small Positive)

LP

(Large Positive)

LP

(Large Positive)

The inputs and outputs of the fuzzy logic controller are both triangular membership functions, as shown in Fig. 9.

Fig. 9.

Fig. 9

The Membership functions for fuzzy logic controllers.

The ranges and specifications of fuzzy variable sets including (E), (CE), and (O) are presented in Table 4.

Table 4.

Crisp range and specifications of both inputs and output variables.

Fuzzy variable Applied MF Interval Crisp ranges for
LN SN Z SP LP

Error

(E)

Triangle [−0.1, 0.1]

[−0.12

−0.0805

−0.03835]

[−0.0791

−0.0384 0.000794]

[−0.0389

0

0.0389]

[0.00132 0.0415 0.0807]

[0.04047 0.0815

0.12]

Change of Error

(CE)

Triangle [−1, 1]

[−1.2

−0.805

−0.4153]

[−0.791

−0.394

−0.0132]

[−0.399

0

0.3942]

[0.007938 0.421

0.802]

[0.41

0.805

1.2]

Output (O) Triangle [−0.2, 0.2]

[−0.24

−0.16

−0.0799]

[−0.1624

−0.0802

−0.01957]

[−0.07531 0.00871 0.08469] [0.0291 0.0832 0.1604]

[0.07885 0.16

0.24]

The fuzzy membership functions, intervals, crisp ranges, and the scaling factors (KE, KCE) were determined through a series of preliminary tuning trials conducted prior to the main simulations. These trials aimed to identify parameter values that ensured satisfactory closed-loop performance and stable system response. While the selected parameters provided adequate results for the presented studies, further systematic optimization and sensitivity analysis may improve the controller’s performance and will be addressed in future work. The rule-surface plot of the FLC Controller is shown per Fig. 10.

Fig. 10.

Fig. 10

Three-dimensional rule-surface plot of the fuzzy inference system (FIS).

In the final phase, which is defuzzification, the Fuzzy Logic Controller (FLC) converts linguistic variables into crisp values. This is achieved using the Center of Gravity (COG) method, also known as the centroid technique, to generate the fuzzy output Control Law (CL).

Optimization methods

Although several new metaheuristic algorithms have been proposed recently, the selection of PSO, GTO, and MPA in this study was motivated by their complementary search characteristics, maturity, and proven robustness in nonlinear control-optimization problems. PSO is a classical swarm-intelligence algorithm that provides rapid convergence with a well-understood parameter structure, making it an excellent benchmark for performance comparison98. GTO, introduced in 2021, is known for its strong balance between exploration and exploitation, which is particularly relevant to power-system control contexts99. MPA, on the other hand, is also a recent bio-inspired optimizer (introduced circa 2020), providing high diversity and strong convergence stability100,101. Using this trio allows for a fair evaluation across algorithmic generations, ensuring both benchmarking consistency and verification of tuning robustness. The focus of this work is on evaluating the proposed hybrid FPIDD²+PIDD² controller across well-established optimization frameworks rather than introducing a new algorithmic variant.

Particle swarm optimization (PSO)

Each particle updates its velocity and position according to:

graphic file with name d33e2293.gif 7
graphic file with name d33e2297.gif 8

Where.

Inline graphic​: Velocity of the ith particle at iteration k.

Inline graphic​: Position of the ith particle.

Inline graphic​: Best position found by the ith particle.

Inline graphic: Global best position found by the swarm.

w: The inertia weight (in this work they were set to 0.7).

c1​ & c2: The cognitive and social learning factors (in this work they were set to 2).

r1 & r2: Random numbers in [0, 1].

Gorilla troops optimizer (GTO)

The GTO algorithm mimics the collective and leadership behaviors of gorilla troops. The position of each agent is updated using:

graphic file with name d33e2339.gif 9

Where.

Inline graphic: Position of the ith agent at iteration t.

Inline graphic​: Position of the leading agent (best solution) at iteration t.

F: Adaptive coefficient controlling the degree of movement toward the leader (in this study ∈ [0.1,0.5].

A: Parameter regulating the balance between exploration and exploitation (In this study ∈ [0,1])

rand (0,1): Uniformly distributed random number in the range [0, 1].

Marine predators algorithm (MPA)

The MPA simulates the foraging behavior of marine predators and employs three phases:

  1. Exploration (high-velocity motion).

  2. Transition.

  3. Exploitation (low-velocity motion).

The agent position update is defined as:

graphic file with name d33e2388.gif 10

Where

Inline graphic​: Position of the ith predator at iteration t.

Inline graphic​: Best solution (elite predator) found so far.

P, S, and L: Random step coefficients in [0, 1] controlling the exploration and exploitation phases.

R: Random vector used to introduce stochasticity.

Inline graphic​: Maximum number of iterations.

Control techniques

To evaluate the performance of the proposed control strategy, simulations are conducted across four distinct case studies, each representing a different operating condition of the interconnected two-area power system. Within each case study, three experimental trials are performed, and each trial corresponds to a specific control scheme. Furthermore, within each trial, three independent runs are executed using different optimization algorithms for controller auto-tuning, including Particle Swarm Optimization (PSO), Gorilla Troops Optimizer (GTO), and Marine Predators Algorithm (MPA).

Table 5 summarizes the complete set of control techniques applied across all case studies, showing the combination of control schemes, optimization methods, and ontroller assignments for both Load Frequency Control (LFC) and Automatic Voltage Regulation (AVR) loops.

Table 5.

Control techniques applied across all case studies.

Trail No. Run
No.
Control
Scheme
Optimization Method Controller Controller Loop Assignment
LFC Loops AVR Loops
Inline graphic Inline graphic Inline graphic Inline graphic
1 st Trial 1 st Run PID PSO PID PID PID PID PID
2nd Run GTO PID PID PID PID PID
3rd Run MPA PID PID PID PID PID
2nd Trial 1 st Run PIDD² PSO PIDD² PIDD² PIDD² PIDD² PIDD²
2nd Run GTO PIDD² PIDD² PIDD² PIDD² PIDD²
3rd Run MPA PIDD² PIDD² PIDD² PIDD² PIDD²
3rd Trial 1 st Run

Inline graphic

Inline graphic

Inline graphic

PSO FPIDD²+PIDD² FPIDD² FPIDD² PIDD² PIDD²
2nd Run GTO FPIDD²+PIDD² FPIDD² FPIDD² PIDD² PIDD²
3rd Run MPA FPIDD²+PIDD² FPIDD² FPIDD² PIDD² PIDD²

This study evaluates three distinct control schemes, as outlined in Table 5, to progressively enhance system performance. The first scheme employs conventional PID controllers in both the Load Frequency Control (LFC) and Automatic Voltage Regulation (AVR) loops, establishing a baseline for comparison. Building on this, the second scheme replaces the PID controllers with PIDD² controllers, leveraging an additional second-derivative term to improve damping and transient response. The third and proposed scheme introduces a novel hybrid configuration (FPIDD²+PIDD²), which strategically deploys FPIDD² controllers for the LFC loops and PIDD² controllers for the AVR loops.

This hybrid architecture is designed to address the distinct dynamic characteristics of each subsystem. The LFC subsystem, characterized by slower dynamics and high sensitivity to load disturbances and inter-area power exchanges, benefits from the adaptive capabilities of the FPIDD² controller. In contrast, the AVR subsystem exhibits faster dynamics, higher inherent stability margins, and limited parameter variations, where the precise and computationally efficient PIDD² controller is sufficient, and further complexity yields diminishing returns102105.

In this work, the proposed control scheme is mainly founded on the PIDD² structure, where the second-derivative term provides a critical advancement over standard PID control. While the first derivative offers velocity feedback, the second derivative acts as an acceleration feedback mechanism. This enables anticipatory control, allowing the controller to preemptively counteract abrupt dynamic changes, thereby increasing the damping ratio, accelerating settling times, and enhancing robustness against disturbances and parameter variations. From a frequency-domain perspective, this introduces an additional zero, improving phase margin and mid-to-high-frequency stability106,107. The FPIDD² controller augments this robust foundation with fuzzy logic, enabling real-time, nonlinear adaptation of the entire control output based on instantaneous error and its derivative. This sets it apart from other advanced controllers: unlike standard Fuzzy-PID controllers that only adjust gains and lack high-frequency derivative action, FPIDD² provides full adaptive control. While Fractional-Order PID (FOPID) and ANFIS controllers can achieve high-order behavior, they are hampered by the complexity of fractional calculus and extensive training requirements, respectively108118. As summarized in Table 6, the proposed FPIDD² uniquely combines high-order derivative control, real-time adaptability, and computational simplicity.

Table 6.

Comparison of PID, Fuzzy-PID, FOPID, and FPIDD2 controllers.

Controller Adaptation Main features
PID None Slow transient, limited damping.
Fuzzy–PID Gains fuzzy-tuned

No double derivative term.

Limited high-frequency response.

FOPID Fractional order

Complex tuning.

May need fractional calculus.

ANFIS Data-driven neuro-fuzzy learning Requires extensive training datasets and high computational resources.
FPIDD² (proposed) Fuzzy multiplies entire output Improves transient response, damping, and adaptability without fractional calculus.

Furthermore, the hybrid FPIDD²+PIDD² framework shown in Fig. 11 delivers enhanced performance by strategically aligning controller complexity with subsystem requirements. The adaptive FPIDD² controller manages the nonlinear, time-varying dynamics of the LFC loop, while the PIDD² controller provides efficient and precise voltage regulation for the AVR loop. This selective assignment optimizes the trade-off between performance, computational cost, and implementation practicality, resulting in a robust and highly effective control strategy for interconnected power systems.

Fig. 11.

Fig. 11

Schematic representation of the proposed hybrid FPIDD²+PIDD² control architecture for the two-area interconnected power system.

Fitness function and boundaries

In control system design, performance indices play a crucial role in evaluating how effectively a system responds to disturbances, influencing both transient and steady-state behavior. Commonly employed indices include IAE, ISE, ITSE, and ITAE. Each index emphasizes different aspects of performance. IAE quantifies the total accumulated error, ISE penalizes large deviations more severely, ITSE highlights errors that persist over time, and ITAE assigns greater weight to errors occurring at later stages of the response. Among these, the ITAE criterion is widely regarded as the most effective due to its balanced trade-off between speed, smoothness, and stability. By penalizing prolonged errors more heavily than initial deviations, ITAE effectively minimizes sustained oscillations, reduces steady-state error, and enhances system damping. These characteristics produce a smooth and well-damped transient response with minimal overshoot and improved robustness. Moreover, ITAE-tuned systems typically yield responses that align closely with human perception of control quality, as operators prefer gradual, stable responses rather than aggressive or sluggish ones. The ITAE index also offers analytical convenience since optimal controller parameters for many standard system models have been tabulated, facilitating both theoretical and numerical optimization. Consequently, ITAE has become one of the most widely adopted objective functions in modern control engineering due to its proven ability to achieve smooth, stable, and well-damped system performance with minimal steady-state error. Accordingly, a wide range of recent control design literature deploys ITAE for LFC/AVR performance evaluation/119,120. In this work, the performance of each control technique is assessed using the Integral of Time-weighted Absolute Error (ITAE) index, which is mathematically expressed as:

graphic file with name d33e2777.gif 11

The tuning parameters [KP, KI, KD1, N1, KD2, N2, KE, KCE] applied to all controllers are constrained within specified lower and upper bounds as follows:

graphic file with name d33e2800.gif 12

During the optimization of controller parameters using the PSO, GTO, and MPA algorithms, the bounds were selected based on preliminary simulations to guarantee stable and practically implementable solutions. Future work may further refine these ranges to enhance convergence and robustness. The complete range of parameter boundaries used for all case studies is summarized in Table 7.

Table 7.

Upper and lower bounds of tuning parameters for LFC and AVR systems.

Tuning Parameter LFC Bounds AVR Bounds Basis for Selection
Lower Upper Lower Upper
Inline graphic 0.1 100 0.1 2 Proportional range for system stability; prevents excessive actuation
Inline graphic 0.1 2 0.1 2 Ensures integral action eliminates ESS without causing slow recovery.
Inline graphic 0.1 2 0.1 2 Avoids amplification of high-frequency noise while maintaining damping.
Inline graphic 0.1 2 0.1 2 Provides adequate derivative filtering bandwidth
Inline graphic 0.1 10 0.1 2 Avoids amplification of high-frequency noise while maintaining damping.
Inline graphic 0.1 100 0.1 100 Provides adequate derivative filtering bandwidth
Inline graphic 0.01 2 - - Maintains normalized fuzzy I/O mapping for adaptive control stability.
Inline graphic 0.01 0.1 - -

where “–” indicates parameters not used in the AVR controller structure.

Each optimization algorithm was initialized with uniformly distributed random values within the specified bounds for all decision variables. The population size for each algorithm was set to 20 agents, and the number of iterations was fixed at 30. The stopping criterion for all optimization runs was therefore met at the end of the 30th iteration. The population size and number of iterations were determined through a series of initial trials that took place prior to the main simulations. These values were selected to achieve an appropriate balance between satisfactory optimization and reasonable computational effort. Future work will focus on developing a more systematic methodology for selecting these parameters.

Case studies

Case study no. 1: effect of step load perturbations

System description

This case study is exactly the same as the two-area interconnected power system illustrated in Fig. 11, but without any renewable energy sources. In addition, 2.5% SLP injected in the second area at 150 s and 2.5% SLP injected into the first area at 50 s.

Simulation results

The convergence curves of the Integral Time Absolute Error (ITAE) are shown along with Time Absolute Error trends are illustrated in Fig. 12, while the power system dynamic responses are presented in Fig. 13.

Fig. 12.

Fig. 12

Convergence behavior of the ITAE during controller optimization in Case Study No.1. The curves correspond to: PID–PSO (Purple), PID–GTO (Olive Green), PID–MPA (Light Brown), PIDD²–PSO (Cyan), PIDD²–GTO (Magenta), PIDD²–MPA (Yellow), (FPIDD²+PIDD²)–PSO (Light Green), (FPIDD²+PIDD²)–GTO (Red), and (FPIDD²+PIDD²)–MPA (Blue).

Fig. 13.

Fig. 13

Fig. 13

Fig. 13

Dynamic responses of the two-area system of Case Study No.1. a ∆f₁, b ∆f₂, c ΔPtie, d Vout1, e Vout2. The curves correspond to: PID–PSO (Purple), PID–GTO (Olive Green), PID–MPA (Light Brown), PIDD²–PSO (Cyan), PIDD²–GTO (Magenta), PIDD²–MPA (Yellow), (FPIDD²+PIDD²)–PSO (Light Green), (FPIDD²+PIDD²)–GTO (Red), and (FPIDD²+PIDD²)–MPA (Blue).

Figure 12 shows that almost all control schemes start with relatively high ITAE values, indicating substantial system error prior to optimization. Among them, the proposed FPIDD²+PIDD² control scheme, particularly when tuned using the MPA algorithm, exhibits the most rapid and significant improvement, reducing the ITAE from approximately 350 to below 50 within the first 15 iterations. When optimized using PSO and GTO, the same controller also demonstrates strong performance, achieving almost the same ITAE. In contrast, both the conventional PID and PIDD² controllers converge more slowly and settle at considerably higher ITAE values, ranging from approximately 530 to 590, indicating lower effectiveness in minimizing dynamic error. These results clearly confirm that the FPIDD²+PIDD² controller offers superior dynamic performance and enhanced system stability, consistently achieving the lowest ITAE across all tested configurations.

As illustrated in Fig. 10, the dynamic responses of frequency deviation in Area-1 (∆f1) and Area-2 (∆f2) reveal distinct performance differences among the examined control schemes. The conventional PID controllers (dark purple, dark green, and brown curves) exhibit pronounced oscillations and large undershoots following the load disturbance, indicating weaker damping characteristics and slower recovery. The PIDD² controllers (cyan, magenta, and yellow curves) improve system stability by reducing oscillation amplitude, resulting in a faster and more stable transition toward steady state.

In contrast, the proposed FPIDD²+PIDD² configuration (green, red, and blue curves) delivers markedly superior performance. It demonstrates the most rapid and well-damped frequency response, with negligible overshoot and the shortest settling time. This reflects enhanced damping capability, faster disturbance rejection, and robust inter-area coordination, ensuring superior frequency stabilization across the interconnected system. Regarding the tie-line power deviation (∆Ptie), the conventional PID curves show the largest oscillation amplitudes, indicating limited synchronization capability and higher power exchange fluctuations during transients. The PIDD² controllers significantly mitigate these oscillations and achieve faster convergence; however, small steady-state deviations remain observable. Conversely, the proposed FPIDD²+PIDD² controller provides the most stable and well-damped tie-line response, achieving smooth and coordinated power exchange between interconnected areas while maintaining overall transient stability. For the voltage responses in Area-1 (Vout1) and Area-2 (Vout2), all controllers initially exhibit transient behavior before settling near the nominal voltage of 1.0 p.u. Nonetheless, the response characteristics differ considerably among the control schemes. The proposed FPIDD²+PIDD² control approach achieves the fastest settling time, minimal overshoot, and smoothest transient profile. In contrast, the conventional PID and PIDD² controllers, regardless of the optimization algorithm employed, display higher overshoot and slower voltage recovery, showing the most pronounced overshoot and sluggish damping. Overall, these findings confirm that the FPIDD²+PIDD² control structure significantly enhances both frequency and voltage regulation performance by providing faster settling, reduced overshoot, improved damping, and superior robustness under load disturbances.

The optimal controllers’ sittings obtained for case study No.1 are shown per Table 8, and Table 9, while the power system dynamic responses are presented in Table 10.

Table 8.

Optimal controllers’ settings for the LFC loop in the first and second area.

Controller Optim. Algorithm Inline graphic Inline graphic
KP KI KD1 N 1 KD2 N 2 KE KCE KP KI KD1 N 1 KD2 N 2 KE KCE
PID PSO 97.9 2.0 2.0 1.7 - - - - 100.0 2.0 1.9 2.0 - - - -
PID GTO 99.9 2.0 2.0 2.0 - - - - 99.9 2.0 0.7 2.0 - - - -
PID MPA 63.4 2.0 1.2 2.0 - - - - 76.1 2.0 1.5 1.8 - - - -
PIDD² PSO 100.0 2.0 2.0 2.0 10.0 100.0 - - 100.0 2.0 1.7 2.0 10.0 100.0 - -
PIDD² GTO 100.0 2.0 1.4 2.0 10.0 33.9 - - 100.0 2.0 2.0 1.7 7.5 50.7 - -
PIDD² MPA 99.5 2.0 0.7 2.0 10.0 100.0 - - 100.0 2.0 0.8 0.7 9.9 98.8 - -
FPIDD²+PIDD² PSO 100.0 2.0 2.0 2.0 8.5 100.0 2.0 0.1 100.0 2.0 2.0 2.0 10.0 100.0 2.0 0.1
FPIDD²+PIDD² GTO 100.0 2.0 1.7 1.9 10.0 91.1 2.0 0.1 100.0 2.0 2.0 0.7 10.0 100.0 2.0 0.0
FPIDD²+PIDD² MPA 100.0 2.0 1.9 2.0 2.3 100.0 2.0 0.1 100.0 2.0 2.0 2.0 10.0 92.8 2.0 0.0
Table 9.

Optimal controllers’ settings for the AVR loop in the first and second area.

Controller Optim. Algorithm Inline graphic Inline graphic
KP KI KD1 N 1 KD2 N 2 KE KCE KP KI KD1 N 1 KD2 N 2 KE KCE
PID PSO 0.7 2.0 1.4 1.1 - - - - 1.7 1.4 2.0 0.9 - - - -
PID GTO 0.4 1.7 2.0 0.3 - - - - 2.0 1.7 1.9 0.2 - - - -
PID MPA 0.1 1.9 1.3 1.7 - - - - 0.2 2.0 2.0 1.6 - - - -
PIDD² PSO 2.0 2.0 1.9 2.0 2.0 6.7 - - 2.0 2.0 2.0 2.0 2.0 100.0 - -
PIDD² GTO 1.4 2.0 0.3 0.7 1.5 8.8 - - 1.7 1.8 1.0 1.2 0.5 95.9 - -
PIDD² MPA 2.0 2.0 2.0 2.0 2.0 99.8 - - 2.0 1.1 0.1 2.0 1.6 94.2 - -
FPIDD²+PIDD² PSO 2.0 2.0 2.0 2.0 1.9 100.0 - - 1.8 2.0 2.0 2.0 2.0 100.0 - -
FPIDD²+PIDD² GTO 2.0 2.0 2.0 2.0 2.0 100.0 - - 2.0 2.0 1.4 2.0 1.1 100.0 - -
FPIDD²+PIDD² MPA 2.0 2.0 2.0 2.0 0.7 98.4 - - 0.5 0.2 1.9 1.6 1.0 95.4 - -
Table 10.

Dynamic responses of the system.

Controller Optim. Algorithm ∆f1 ∆f2 Ptie Vout1 Vout2
MO∆f1
(Hz)
MU∆f1
(Hz)
MO∆f2
(Hz)
MU∆f2
(Hz)
MOP
(p.u)
MUP
(p.u)
MP− V1
(p.u)
Tr−V1
(Sec.)
Ts−V1
(Sec.)
MP− V2
(p.u)
Tr−V2
(Sec.)
Ts−V2
(Sec.)
PID PSO 0.033 −0.068 0.031 −0.069 0.001 −0.002 0.701 0.269 11.923 0.694 0.252 14.215
PID GTO 0.009 −0.055 0.021 −0.064 0.001 −0.001 0.302 0.312 5.699 0.585 0.267 7.008
PID MPA 0.044 −0.090 0.043 −0.103 0.004 −0.005 0.672 0.319 9.362 0.728 0.250 17.350
PIDD² PSO 0.010 −0.066 0.006 −0.063 0.001 −0.001 0.412 0.070 3.452 0.164 0.144 3.204
PIDD² GTO 0.006 −0.049 0.006 −0.046 0.000 0.000 0.345 0.238 2.884 0.262 0.246 3.338
PIDD² MPA 0.081 −0.132 0.021 −0.108 0.003 −0.003 0.376 0.068 3.700 0.177 0.157 3.012
FPIDD²+PIDD² PSO 0.004 −0.021 0.001 −0.019 0.000 0.000 0.388 0.069 3.451 0.359 0.067 3.439
FPIDD²+PIDD² GTO 0.004 −0.021 0.001 −0.012 0.000 0.000 0.364 0.067 3.645 0.136 0.197 2.948
FPIDD²+PIDD² MPA 0.007 −0.024 0.001 −0.012 0.000 −0.001 0.269 0.135 2.143 0.136 0.206 2.792

Table 10 demonstrates that the proposed FPIDD²+PIDD² controller consistently outperforms both conventional PID and PIDD² controllers across all tested optimization algorithms.

Regarding frequency deviation, the FPIDD²+PIDD² scheme achieves the lowest overshoot and undershoot in both control areas. For example, under MPA optimization, the peak frequency deviations for Area-1 and Area-2 (∆f₁ and ∆f₂) are limited to 0.0066 Hz and 0.0005 Hz, respectively. Similarly, the tie-line power deviation peaks at only 0.0002 p.u., indicating excellent inter-area stability.

In terms of voltage response, the FPIDD²+PIDD² controller also exhibits superior performance, delivering the fastest settling times and the lowest overshoot. Specifically, with MPA optimization, Vout1 settles in 2.14 s and Vout2 in 2.79 s. Moreover, the voltage transients are smoother, with minimal overshoot value 0.2692 p.u. for Vout1 and 0.1358 p.u. for Vout2, highlighting the controller’s effectiveness in managing dynamic voltage behavior.

The Integral Time Absolute Error (ITAE) values for each of the three control schemes, tuned using the three optimization algorithms, are presented in Table 11.

Table 11.

The optimism integral time absolute error (ITAE) for all controllers.

Controller Optimization Algorithm Best ITAE
PSO GTO MPA Value Algorithm
PID 585.24 528.84 550.15 528.84 GTO
PIDD² 549.29 549.37 548.02 548.02 MPA
FPIDD²+ PIDD² 53.64 53.91 53.21 53.21 MPA

Table 11 shows that the proposed FPIDD²+PIDD² control scheme achieves a significant improvement over both the PID and PIDD² controllers under all optimization algorithms. Notably, when tuned using the MPA algorithm, the ITAE was reduced sharply reaching nearly one-tenth of the values achieved by the PID and PIDD² controllers.

Results summary

Although traditional PID controllers delivered acceptable dynamic performance in this case study, they were limited by considerable overshoot and prolonged settling times, resulting in a best-achieved Integral of Time-weighted Absolute Error (ITAE) of approximately 529. In comparison, the PIDD² controllers provided a marginal improvement, with the MPA yielding a modest 3.6% reduction in ITAE.

In contrast, the proposed hybrid control configuration (FPIDD²+PIDD²) demonstrated superior performance across all evaluated metrics. This setup achieved minimal steady-state error, reduced overshoot, faster rise times, and shorter settling durations. Notably, the hybrid scheme tuned by MPA led to a significant reduction in ITAE: 89.9% compared to the PID controllers and 90.3% compared to the PIDD² controllers, confirming its enhanced control accuracy and system robustness.

Furthermore, the analysis of optimization techniques revealed that for PID controllers, MPA offered a slight advantage over the Gorilla Troops Optimizer (GTO), which in turn marginally outperformed Particle Swarm Optimization (PSO). However, for both the PIDD² and FPIDD²+PIDD² controllers, all three optimization methods produced nearly identical results. This suggests that when advanced control structures are employed, the controller architecture has a more pronounced impact on system performance than the specific optimization algorithm used.

Collectively, these findings demonstrate that the FPIDD²+PIDD² hybrid control strategy is the most effective solution for load frequency and voltage regulation in multi-area power systems, offering a level of precision, stability, and responsiveness that surpasses both conventional and intermediate designs.

Case study no. 2: effect of renewable energy sources (PV + WT)

System description

This case study is exactly the same as the two-area interconnected power system illustrated in Fig. 4, but with a Photovoltaic unit is connected to the first area after 20 s and a wind turbine a unit is inserted to the second area at 70 s. In addition, 2.5% SLP injected in the second area at 150 s and 2.5% SLP injected to the first area at 50 s.

Simulation results

The convergence curves of the Integral Time Absolute Error (ITAE) are shown along with Time Absolute Error trends are illustrated in Fig. 14, while the power system dynamic responses are presented in Fig. 15.

Fig. 14.

Fig. 14

Convergence behavior of the ITAE during controller optimization in Case Study No. 2. The curves correspond to: PID–PSO (Purple), PID–GTO (Olive Green), PID–MPA (Light Brown), PIDD²–PSO (Cyan), PIDD²–GTO (Magenta), PIDD²–MPA (Yellow), (FPIDD²+PIDD²)–PSO (Light Green), (FPIDD²+PIDD²)–GTO (Red), and (FPIDD²+PIDD²)–MPA (Blue).

Fig. 15.

Fig. 15

Fig. 15

Fig. 15

Dynamic responses of the two-area system of Case Study No.2: a ∆f₁, b ∆f₂, c ΔPtie, d Vout1, e Vout2. The curves correspond to: PID–PSO (Purple), PID–GTO (Olive Green), PID–MPA (Light Brown), PIDD²–PSO (Cyan), PIDD²–GTO (Magenta), PIDD²–MPA (Yellow), (FPIDD²+PIDD²)–PSO (Light Green), (FPIDD²+PIDD²)–GTO (Red), and (FPIDD²+PIDD²)–MPA (Blue).

Figure 14 demonstrates that the hybrid (FPIDD²+PIDD²) controllers consistently outperform both conventional PID and second-order PIDD² structures in terms of convergence speed and final ITAE value. These controllers achieve the lowest ITAE levels while exhibiting smooth and stable convergence behavior. While PIDD²-based designs offer moderate improvements over classical PID, they still fall short of the performance achieved by the hybrid structure. In contrast, traditional PID configurations display relatively poor convergence, likely due to instability in initial parameter tuning or sensitivity to the optimization algorithm. Overall, the figure highlights that the (FPIDD²+PIDD²) controllers, particularly when optimized using advanced metaheuristic algorithms, significantly enhance tuning accuracy and dynamic response, resulting in superior performance in minimizing ITAE and accelerating convergence during control parameter optimization.

As illustrated in Fig. 15, the dynamic response of the system frequency deviation reveals clear distinctions among the three control strategies. The conventional PID controllers exhibit the largest oscillations and the and the highest peaks, indicating limited damping capability and reduced robustness against inter-area load disturbances in both areas. This behavior reflects their weak resilience to dynamic fluctuations and limited ability to suppress frequency deviations effectively. The PIDD² controllers yields a noticeable improvement, characterized by reduced overshoot and smaller oscillation amplitudes. Nevertheless, these controllers still require a relatively long duration to reach steady-state conditions, suggesting that damping performance, while enhanced, remains suboptimal. In contrast, the proposed FPIDD²+PIDD² control scheme demonstrates the most stable frequency response with minimal overshoot. This superior transient performance highlights its strong damping capability and enhanced robustness under varying load conditions.

Regarding the tie-line power deviation (∆Ptie), the conventional PID controllers produce the largest oscillations and the highest peaks, indicating poor regulation of inter-area power exchange and limited damping effectiveness. The PIDD² controllers improve performance by reducing the magnitude of oscillations as well as overshoots, though transient ripples remain noticeable. In comparison, the proposed FPIDD²+PIDD² controllers achieve the most efficient tie-line response, characterized by minimal overshoot, smooth transients, and rapid convergence to steady state. These attributes lead to improved power flow regulation and stronger synchronization between interconnected areas. The enhanced damping and negligible steady-state error confirm the effectiveness of the proposed approach in maintaining tie-line power stability under load disturbances.

With respect to voltage performance, all controllers initially exhibit a sharp rise in response to the applied step disturbance. The conventional PID-based schemes show pronounced overshoots and oscillations before eventually settling at the nominal value. The PIDD²-based controllers demonstrate improved damping and reduced overshoot compared with the conventional PID group, though minor oscillations persist before steady state is reached, indicating only moderate enhancement in robustness. Conversely, the proposed hybrid FPIDD²+PIDD² configuration exhibits the most stable and well-damped voltage response. The output voltage swiftly returns to unity with negligible overshoot and minimal oscillations. Among all configurations, reflecting superior dynamic performance and effective voltage regulation under disturbance conditions.

In this case study, the optimal controllers’ gains obtained for case study No.2 are shown per Table 12, and Table 13, while the power system dynamic responses are presented in Table 14.

Table 12.

Optimal controllers’ settings for the LFC loop in the first and second area.

Controller Optim.
Algorithm
Inline graphic Inline graphic
KP KI KD1 N 1 KD2 N 2 KE KCE KP KI KD1 N 1 KD2 N 2 KE KCE
PID PSO 0.1 0.1 0.1 0.3 - - - - 17.4 0.2 0.2 1.4 - - - -
PID GTO 0.1 0.6 0.6 0.5 - - - - 0.1 0.2 0.5 0.2 - - - -
PID MPA 3.2 2.0 1.7 0.9 - - - - 86.2 1.9 1.9 0.3 - - - -
PIDD² PSO 100.0 2.0 2.0 2.0 10.0 100.0 - - 100.0 2.0 2.0 2.0 10.0 100.0 - -
PIDD² GTO 99.6 2.0 2.0 0.1 10.0 100.0 - - 100.0 2.0 2.0 0.2 1.9 100.0 - -
PIDD² MPA 100.0 2.0 0.3 2.0 10.0 100.0 - - 99.8 2.0 1.0 1.9 10.0 99.8 - -
FPIDD²+PIDD² PSO 100.0 2.0 1.0 2.0 6.4 100.0 2.0 0.1 44.0 2.0 2.0 0.7 9.6 75.4 1.1 0.1
FPIDD²+PIDD² GTO 100.0 2.0 0.7 2.0 7.1 0.1 2.0 0.1 100.0 2.0 2.0 2.0 10.0 100.0 2.0 0.0
FPIDD²+PIDD² MPA 80.1 2.0 2.0 2.0 9.9 100.0 2.0 0.1 44.8 2.0 2.0 0.4 10.0 99.1 2.0 0.1
Table 13.

Optimal controllers’ settings for the AVR loop in the first and second area.

Controller Optim. algorithm Inline graphic Inline graphic
KP KI KD1 N 1 KD2 N 2 KE KCE KP KI KD1 N 1 KD2 N 2 KE KCE
PID PSO 0.5 0.6 0.1 1.9 - - - - 0.7 0.7 0.2 1.4 - - - -
PID GTO 0.7 0.9 0.2 0.5 - - - - 0.6 0.9 0.7 0.7 - - - -
PID MPA 0.2 0.9 0.4 0.7 - - - - 0.9 1.9 1.2 1.8 - - - -
PIDD² PSO 2.0 2.0 2.0 2.0 2.0 100.0 - - 2.0 2.0 2.0 2.0 2.0 100.0 - -
PIDD² GTO 1.7 2.0 1.5 0.2 0.4 7.6 - - 2.0 2.0 1.4 2.0 0.6 100.0 - -
PIDD² MPA 0.8 2.0 2.0 0.3 2.0 0.1 - - 2.0 2.0 2.0 0.1 2.0 0.9 - -
FPIDD²+PIDD² PSO 1.0 1.3 2.0 1.3 2.0 0.0 - - 1.5 2.0 1.0 1.2 2.0 100.0 - -
FPIDD²+PIDD² GTO 2.0 2.0 0.8 2.0 1.1 0.0 - - 1.9 2.0 1.1 1.4 0.7 100.0 - -
FPIDD²+PIDD² MPA 2.0 2.0 2.0 2.0 0.2 77.4 - - 0.8 2.0 1.4 2.0 0.6 14.9 - -
Table 14.

Dynamic responses of the system.

Controller Optim. Algorithm ∆f1 ∆f2 Ptie Vout1 Vout2
MO∆f1
(Hz)
MU∆f1
(Hz)
MO∆f2
(Hz)
MU∆f2
(Hz)
MOP
(p.u)
MUP
(p.u)
MP− V1
(p.u)
Tr−V1
(Sec.)
Ts−V1
(Sec.)
MP− V2
(p.u)
Tr−V2
(Sec.)
Ts−V2
(Sec.)
PID PSO 1.188 −0.977 0.188 −0.332 0.093 −0.145 0.379 0.543 9.133 0.398 0.430 6.311
PID GTO 0.695 −1.196 0.350 −1.214 0.054 −0.048 0.465 0.432 11.602 0.364 0.386 5.230
PID MPA 0.208 −0.445 0.049 −0.146 0.011 −0.059 0.477 0.558 6.601 0.751 0.268 16.110
PIDD² PSO 0.010 −0.065 0.010 −0.065 0.000 0.000 0.364 0.067 3.703 0.364 0.067 3.703
PIDD² GTO 0.033 −0.083 0.053 −0.102 0.003 −0.003 0.314 0.200 2.593 0.248 0.171 1.891
PIDD² MPA 0.014 −0.063 0.013 −0.065 0.001 −0.001 0.444 0.257 4.721 0.434 0.188 3.356
FPIDD²+PIDD² PSO 0.018 −0.041 0.001 −0.031 0.000 0.000 0.315 0.068 17.796 0.153 0.154 4.311
FPIDD²+PIDD² GTO 0.003 −0.022 0.001 −0.012 0.000 −0.001 0.179 0.174 1.824 0.191 0.186 1.873
FPIDD²+PIDD² MPA 0.001 −0.014 0.001 −0.023 0.001 0.000 0.454 0.191 3.263 0.355 0.181 4.112

The data presented in Table 14 clearly indicate that the hybrid FPIDD²+PIDD² controller offers superior dynamic performance compared to both conventional PID and second-order PIDD² controllers. This advanced structure enhances transient stability, effectively suppresses oscillations, and enables faster recovery following disturbances, resulting in a well-damped and stable system response. In terms of frequency deviation, the FPIDD²+PIDD² controller consistently achieves the lowest overshoot and undershoot values. Notably, when optimized using the GTO algorithm, it limits ∆f1 to 0.0025 Hz and ∆f2 to 0.0005 Hz, substantially better than the best-performing PIDD² controller (∆f1 = 0.0103 Hz, ∆f2 = 0.0104 Hz) and significantly outperforming the PID controller (∆f1 = 0.2078 Hz, ∆f2 = 0.0486 Hz). Similarly, for tie-line power deviation (ΔPtie), the FPIDD²+PIDD²–GTO configuration achieves a near-negligible deviation of approximately 0.0001 p.u., demonstrating excellent inter-area power coordination. FPIDD²+PIDD² controller also excels in voltage response, where it provides the fastest and smoothest transient profile. When tuned with GTO, it achieves a settling time of approximately 1.8 s in both areas and registers the lowest voltage overshoots, reaching 0.1786 p.u. in Area 1 and 0.1913 p.u. in Area 2. These results underscore the FPIDD²+PIDD² controller’s effectiveness across multiple performance metrics, confirming its advantage over traditional control strategies.

The Integral Time Absolute Error (ITAE) values for each of the three control schemes, tuned using the three optimization algorithms, are presented in Table 15.

Table 15.

The optimism integral time absolute error (ITAE) for all controllers.

Controller Optimization Algorithm Best ITAE
PSO GTO MPA Value Algorithm
PID 1060.23 858.83 599.90 599.90 MPA
PIDD² 535.35 534.59 535.78 534.59 GTO
FPIDD²+ PIDD² 66.09 52.18 54.76 52.18 GTO

The results presented in Table 15 confirm that the proposed FPIDD²+PIDD² controller offers a significant enhancement in system performance compared to conventional PID and PIDD² controllers. This is particularly evident in terms of the Integral of ITAE metric, where the FPIDD²+PIDD² controller, when optimized using the GTO, achieves the lowest ITAE value of 52.18. This exceptionally low value reflects the controller’s enhanced damping capability and its effectiveness in minimizing errors rapidly. In comparison, the best-performing configurations of PID and PIDD² controllers yield considerably higher ITAE values of 599.90 and 534.59, respectively, indicating slower dynamic responses and less effective error suppression.

Among the three metaheuristic optimization methods evaluated, MPA and GTO emerge as the most effective in fine-tuning controllers in most cases. They consistently produce the fastest, most stable transient responses, with minimal frequency and voltage deviations, further underscoring their suitability for optimizing advanced control structures in load frequency control applications.

Results summary

To further assess controller resilience under more complex conditions, this case study introduces both a photovoltaic (PV) unit in the first area at 20 s and a wind turbine in second area at 70 s. Under these stressed conditions, the conventional PID controller faced significant challenges, as evidenced by prolonged settling times in both deviation profiles of system frequency and tie line power. The best recorded ITAE under PID control was approximately 600. The PIDD² controller delivered marked improvements, reducing the ITAE was by approximately 10.9% compared to the conventional PID controller. Further enhancements were achieved using a hybrid control strategy, employing FPIDD² for LFC and PIDD² for AVR. This configuration delivered the most robust performance, characterized by minimal overshoot, and negligible steady-state error. Compared to the PID controller, ITAE was reduced by 91% and by 90% relative to PIDD² controller. Regarding optimization algorithms, when applied to PID controllers, the MPA achieved the best ITAE performance, followed closely by the GTO, then PSO, which was nearly 177% higher than that of MPA. However, for the PIDD² configuration, all three optimization algorithms yielded nearly identical results. A different pattern was observed for the FPIDD²+PIDD² hybrid setup, where GTO and MPA achieved comparable performance, while PSO resulted in an ITAE approximately 20% higher.

In summary, these results underscore a clear trend of progressive performance improvement, highlighting the superior control capabilities of the hybrid FPIDD²+PIDD². Notably, while optimization algorithms influence controller performance, particularly for simpler architectures like PID, their relative impact diminishes as more advanced controllers are employed. This suggests that controller architecture plays a more dominant role in determining overall system robustness. One plausible explanation is that advanced controllers such as PIDD² and FPIDD² incorporate additional degrees of freedom and adaptive features, which inherently enhance their ability to handle disturbances and parameter variations. As a result, they become less sensitive to fine-tuning by optimization algorithms, thereby narrowing the performance gap between optimizers. These findings imply that investing in better controller design may yield more substantial performance gains than focusing on optimization techniques.

Case study no. 3: sensitivity analysis

System description

This case study is exactly the same as the pervious case study (case study No.2), but with some changes in parameters setting of power system, as shown per Table 16.

Table 16.

Modified power system settings.

Model Constant Model
Value
Model Constant Model
Value
Model Constant Model
Value
Model Constant Model
Value
Tt 0.15 s Kps2 100 Kn, Ke 1.5 Tn, Te 0.6, 1.5
Tgh 0.12 s T12 0.0867 MW Tps2 10 s Rg, RTh, Rhyd 1.2 Hz/MW

Simulation results

The convergence curves of the Integral Time Absolute Error (ITAE) are shown along with Time Absolute Error trends are illustrated in Fig. 16, while the power system dynamic responses are presented in Fig. 17.

Fig. 16.

Fig. 16

Convergence behavior of the ITAE during controller optimization in Case Study No. 3. The curves correspond to: PID–PSO (Purple), PID–GTO (Olive Green), PID–MPA (Light Brown), PIDD²–PSO (Cyan), PIDD²–GTO (Magenta), PIDD²–MPA (Yellow), (FPIDD²+PIDD²)–PSO (Light Green), (FPIDD²+PIDD²)–GTO (Red), and (FPIDD²+PIDD²)–MPA (Blue).

Fig. 17.

Fig. 17

Fig. 17

Fig. 17

Dynamic responses of the two-area system of Case Study No.3: a ∆f₁, b ∆f₂, c ΔPtie, d Vout1, e Vout2. The curves correspond to: PID–PSO (Purple), PID–GTO (Olive Green), PID–MPA (Light Brown), PIDD²–PSO (Cyan), PIDD²–GTO (Magenta), PIDD²–MPA (Yellow), (FPIDD²+PIDD²)–PSO (Light Green), (FPIDD²+PIDD²)–GTO (Red), and (FPIDD²+PIDD²)–MPA (Blue). The conventional PID controller responses were omitted from the zoomed-in view to improve clarity, as they exhibit sever oscillations.

Figure 16 shows that the proposed hybrid FPIDD²+PIDD² controllers demonstrate the most efficient convergence behavior. Their ITAE values drop sharply to near-zero within the early iterations, reflecting enhanced robustness and stability in parameter tuning. In comparison, the PIDD²-based controllers exhibit moderately improved convergence characteristics over conventional PID controllers, achieving lower ITAE values overall. Conversely, the conventional PID-based controllers exhibit extremely high ITAE values across the optimization process, reflecting slower convergence rates and limited optimization capability.

As depicted in Fig. 16, the classical PID controllers applied to the Load Frequency Control (LFC) loops in both Area-1 and Area-2 exhibit clear signs of instability. The frequency deviations ∆f1​ and ∆f2​ experience significant and sustained oscillations, indicating the limitations of traditional PID structures in maintaining frequency stability, particularly under the influence of system disturbances and nonlinear dynamics. In contrast, the PIDD²-based controllers provide notable improvements. These controllers effectively suppress oscillations and demonstrate enhanced damping characteristics, leading to a more stable frequency response compared to their classical counterparts. The most superior performance is delivered by the proposed hybrid FPIDD²+PIDD² control configurations. These advanced controllers maintain frequency deviations near zero throughout the entire simulation period, exhibiting excellent dynamic regulation and confirming their robustness and resilience under varying system conditions.

In terms of tie-line power deviation (ΔPtie​), the classical PID controllers again perform poorly, displaying significant oscillations that reflect an inability to maintain power exchange equilibrium between interconnected areas. The PIDD² controllers show moderate improvement, reducing the amplitude and persistence of the oscillations. However, the FPIDD²+PIDD² controllers clearly outperform both groups, maintaining near-zero tie-line power deviations and demonstrating strong disturbance rejection and sustained optimal inter-area power exchange. This underscores their effectiveness in preserving tie-line power stability in interconnected power systems.

Regarding the dynamic behavior of the Automatic Voltage Regulator (AVR) output voltages Vout1​ and Vout2​, the conventional PID-based controllers exhibit large-amplitude oscillations and instability, especially toward the end of the simulation. This indicates poor transient performance and limited robustness in voltage regulation. The PIDD²-based controllers improve voltage stability to some extent, offering smoother responses characterized by zero steady-state error, and enhanced damping. The hybrid FPIDD²+PIDD² controllers show the most stable and well-damped response among all configurations, maintain an almost constant voltage level throughout the simulation with negligible deviation, indicating excellent damping, rapid convergence, and high robustness.

In this case study, the optimal controllers’ sittings obtained for case study No.3 are shown per Tables 17, and 18, while the power system dynamic responses are presented in Table 19.

Table 17.

Optimal controllers’ settings for the LFC loop in the first and second area.

Controller Optim Algorithm Inline graphic Inline graphic
KP KI KD1 N 1 KD2 N 2 KE KCE KP KI KD1 N 1 KD2 N 2 KE KCE
PID PSO 18.5 2.0 2.0 1.1 - - - - 92.9 1.3 1.8 1.5 - - - -
PID GTO 0.2 0.2 0.2 0.1 - - - - 3.2 1.3 0.2 0.1 - - - -
PID MPA 0.1 1.7 1.9 0.2 - - - - 2.9 0.1 2.0 0.2 - - - -
PIDD² PSO 100.0 2.0 2.0 2.0 10.0 100.0 - - 100.0 2.0 0.8 2.0 10.0 100.0 - -
PIDD² GTO 100.0 2.0 1.2 1.6 10.0 100.0 - - 100.0 2.0 2.0 1.4 1.1 98.1 - -
PIDD² MPA 100.0 2.0 2.0 2.0 4.2 96.1 - - 100.0 2.0 2.0 1.8 3.2 94.8 - -
FPIDD²+PIDD² PSO 65.5 2.0 2.0 1.8 10.0 100.0 2.0 0.1 91.6 2.0 1.6 2.0 7.7 54.5 1.9 0.1
FPIDD²+PIDD² GTO 100.0 2.0 0.1 2.0 1.3 100.0 2.0 0.1 100.0 2.0 2.0 2.0 0.1 100.0 2.0 0.1
FPIDD²+PIDD² MPA 100.0 2.0 2.0 2.0 8.4 47.0 2.0 0.1 99.5 2.0 2.0 1.7 4.8 98.2 2.0 0.1
Table 18.

Optimal controllers’ settings for the AVR loop in Area-1 and Area-2.

Controller Optim Algorithm Inline graphic Inline graphic
KP KI KD1 N 1 KD2 N 2 KE KCE KP KI KD1 N 1 KD2 N 2 KE KCE
PID PSO 1.5 1.0 1.9 1.3 - - - - 1.1 2.0 0.8 1.1 - - - -
PID GTO 0.2 0.1 0.1 0.1 - - - - 0.1 0.1 0.1 0.1 - - - -
PID MPA 0.1 0.5 0.1 0.2 - - - - 0.1 0.6 0.1 0.1 - - - -
PIDD² PSO 2.0 2.0 1.5 2.0 2.0 100.0 - - 2.0 2.0 1.7 2.0 2.0 100.0 - -
PIDD² GTO 1.2 2.0 2.0 1.9 1.2 65.5 - - 0.8 1.6 0.6 2.0 2.0 98.4 - -
PIDD² MPA 2.0 2.0 0.8 2.0 2.0 100.0 - - 2.0 2.0 2.0 2.0 1.7 95.1 - -
FPIDD²+PIDD² PSO 2.0 2.0 1.5 1.6 2.0 100.0 - - 2.0 1.8 1.2 1.7 2.0 100.0 - -
FPIDD²+PIDD² GTO 2.0 2.0 2.0 2.0 1.1 96.2 - - 0.1 0.1 2.0 1.3 1.7 100.0 - -
FPIDD²+PIDD² MPA 0.7 2.0 2.0 0.2 1.4 0.1 - - 2.0 2.0 0.9 1.5 1.0 60.5 - -
Table 19.

Dynamic responses of the system.

Controller Optim. Algorithm ∆f1 ∆f2 Ptie Vout1 Vout2
MO∆f1
(Hz)
MU∆f1
(Hz)
MO∆f2
(Hz)
MU∆f2
(Hz)
MOP
(p.u)
MUP
(p.u)
MP− V1
(p.u)
Tr−V1
(Sec.)
Ts−V1
(Sec.)
MP− V2
(p.u)
Tr−V2
(Sec.)
Ts−V2
(Sec.)
PID PSO N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
PID GTO N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
PID MPA N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
PIDD² PSO 0.006 −0.074 0.024 −0.100 0.002 −0.001 0.463 0.083 3.057 0.285 0.136 2.120
PIDD² GTO 0.023 −0.103 0.065 −0.148 0.002 −0.001 0.482 0.109 5.722 0.286 0.136 2.122
PIDD² MPA 0.026 −0.099 0.028 −0.100 0.001 −0.001 0.191 0.138 2.098 0.305 0.144 2.152
FPIDD²+PIDD² PSO 0.001 −0.018 0.001 −0.020 0.000 0.000 0.451 0.084 5.583 0.292 0.147 2.135
FPIDD²+PIDD² GTO 0.045 −0.054 0.004 −0.035 0.000 −0.001 0.437 0.110 2.659 0.274 0.146 2.123
FPIDD²+PIDD² MPA 0.001 −0.010 0.001 −0.015 0.001 0.000 0.341 0.295 4.697 0.313 0.181 2.195

Table 19 clearly demonstrate that the proposed FPIDD²+PIDD² controller outperforms the conventional PIDD² controller across all optimization algorithms, while the PID controller fails to produce valid or stable responses (N.A.), confirming its inadequacy under the given operating conditions.

Among the evaluated schemes, the FPIDD²+PIDD² configuration achieves the best overall dynamic and steady-state performance. For instance, when optimized using the MPA algorithm, the controller yields the smallest frequency deviations, with the minimum overshoot and undershoot of approximately + 0.0006 Hz and − 0.01 Hz, respectively. Meanwhile, the PIDD² controller exhibits larger fluctuations up to ± 0.10 Hz, while the PID controller becomes unstable, resulting in rapidly growing oscillations. A similar trend is observed in the tie-line power deviations, where the (FPIDD²+PIDD²)–MPA configuration maintains minimal deviations of around 0.0006 p.u. Conversely, the PIDD² controller shows relatively higher deviations (≈ ± 0.0001 p.u.), and the PID controller again fails to ensure stability. In terms of voltage regulation, both of the PIDD2 and FPIDD²+PIDD² controllers exhibits faster settling and smoother transient behavior than the traditional PID controller, which. is unable to maintain voltage stability, leading to divergent oscillations in the AVR loop.

The Integral Time Absolute Error (ITAE) values for each of the three control schemes, tuned using the three optimization algorithms, are presented in Table 20.

Table 20.

The optimism integral time absolute error (ITAE) for all controllers.

Controller Optimization Algorithm Best ITAE
PSO GTO MPA Value Algorithm
PID > 109 > 109 > 109 N.A. N.A.
PIDD² 541.75 540.30 540.44 540.30 GTO
FPIDD²+ PIDD² 56.19 52.79 53.47 52.79 GTO

The results presented in Table 20 clearly highlight the superior performance of the proposed FPIDD²+PIDD² controller over the conventional PIDD² and PID controllers. The PID controller fails to maintain stable operation producing excessively large ITAE value (> 10⁹). In contrast, all configurations of the FPIDD²+PIDD² controller demonstrate substantial improvements in dynamic performance and error minimization. Notably, the (FPIDD²+PIDD²)–GTO configuration achieves the lowest ITAE value of 52.79. Meanwhile, the PIDD² controllers record a considerably higher ITAE value around 540, signifying slower system response and greater steady-state deviations. These results affirm that when the FPIDD²+PIDD² is coupled with advanced optimization techniques, it markedly enhances both transient and steady-state performance in interconnected LFC–AVR systems.

Results summary

Beyond renewable energy integration, this case study investigates controller performance under altered power system parameters to emulate real-world variability. The study modifies the time constants of key components, such as steam and hydro turbines, AVR exciters, generators, and the overall power network, while also incorporating nonlinearities and coupling effects typical of complex multi-area systems.

Under these challenging conditions, the classical PID controller demonstrated instability and unsatisfactory performance, yielding ITAE values exceeding billions. This outcome underscores the inherent limitations of PID control in handling nonlinear dynamics and strong inter-area coupling. In contrast, the PIDD² controller exhibited marked improvements, achieving reduced overshoot, faster rise times, and smaller steady-state errors, with a minimum ITAE of approximately 540.

Further advancements were realized through the hybrid FPIDD²+PIDD² control strategy. This configuration delivered the most stable and responsive performance across all test scenarios, achieving a 90.2% reduction in ITAE compared to the standalone PIDD² controller, along with superior damping, minimal overshoot, and strong steady-state precision.

Regarding optimization algorithms, applying the three optimization methods to PID controllers under the altered system conditions consistently produced extremely high ITAE values, reaffirming the inadequacy of the conventional PID structure under such variability. Conversely, when the same optimization algorithms were applied to the PIDD² and hybrid FPIDD²+PIDD² controllers, the outcomes were nearly identical within each control type, indicating that advanced control structures possess intrinsic robustness and adaptability, largely independent of the specific optimization technique employed.

Case study no. 4: the effect random load perturbation

System description

This case study is exactly the same as case study No.2, but Area-1 is subjected to a random load variation (RLP) as shown in Fig. 18.

Fig. 18.

Fig. 18

Random Load Perturbation (RLP) signal injected to Area-1 during Case Study No.4.

Simulation results

The convergence curves of the Integral Time Absolute Error (ITAE) are shown along with Time Absolute Error trends are illustrated in Fig. 19, while the power system dynamic responses are presented in Fig. 20.

Fig. 19.

Fig. 19

Convergence behavior of the ITAE during controller optimization in Case Study No. 4. The curves correspond to: PID–PSO (Purple), PID–GTO (Olive Green), PID–MPA (Light Brown), PIDD²–PSO (Cyan), PIDD²–GTO (Magenta), PIDD²–MPA (Yellow), (FPIDD²+PIDD²)–PSO (Light Green), (FPIDD²+PIDD²)–GTO (Red), and (FPIDD²+PIDD²)–MPA (Blue).

Fig. 20.

Fig. 20

Fig. 20

Fig. 20

Dynamic responses of the two-area system of Case Study No.4: a ∆f₁, b ∆f₂, c ΔPtie, d Vout1, e Vout2. The curves correspond to: PID–PSO (Purple), PID–GTO (Olive Green), PID–MPA (Light Brown), PIDD²–PSO (Cyan), PIDD²–GTO (Magenta), PIDD²–MPA (Yellow), (FPIDD²+PIDD²)–PSO (Light Green), (FPIDD²+PIDD²)–GTO (Red), and (FPIDD²+PIDD²)–MPA (Blue). The conventional PID controller responses were omitted from the zoomed in view to improve clarity, as they exhibit notable fluctuations.

As illustrated in Fig. 19, most controller configurations exhibit a rapid decrease in ITAE values during the initial iterations, indicating efficient early-stage learning and convergence behavior. However, conventional PID-based schemes tend to plateau at relatively high ITAE levels, reflecting limited optimization accuracy and suboptimal transient performance. Meanwhile, the PIDD2-based controllers demonstrate moderate improvements in ITAE reduction, yet they remain less effective in achieving optimal tuning and convergence compared to the proposed hybrid approach.

In contrast, the FPIDD2 + PIDD2 control configuration shows markedly superior convergence characteristics, achieving the lowest final ITAE values along with the fastest stabilization rate. This performance indicates a more robust global search capability, effectively avoiding premature convergence and enabling the identification of near-optimal controller gains delivering enhanced dynamic response and improving steady-state performance.

Figure 20 clearly illustrates that the conventional PID controllers exhibit more pronounced transient oscillations and longer settling times. Notably, the PID controller shows significant oscillatory behavior, with high peak frequency deviations, indicating suboptimal damping characteristics and delayed system recovery. In contrast, the PIDD² controllers demonstrate enhanced dynamic performance, characterized by reduced overshoot and faster stabilization. However, minor oscillations with small-amplitude fluctuations persist throughout the simulation period. The most significant performance improvement is observed in the hybrid control configuration (PIDD²+PIDD²), particularly when optimized using the MPA algorithm. This configuration achieves the lowest frequency deviations and exhibits near-instantaneous convergence to zero deviation, consistently outperforming all other schemes. These results underscore the effectiveness of the PIDD²+PIDD² hybrid control strategy in minimizing frequency fluctuations, as it demonstrates negligible overshoot, rapid settling time, and robust oscillation suppression.

Regarding tie-line power deviation (ΔPtie), the results indicate that among the conventional PID-based designs, significant oscillations and the largest peak deviations were observed. The application of PIDD² controllers leads to noticeable improvements, including a moderate reduction in peak deviations and enhanced damping characteristics compared to conventional PID controllers. However, some fluctuations persist during the simulation. The most favorable performance is achieved with the hybrid control schemes combining FPIDD² and PIDD² controllers, demonstrating negligible overshoot, and minimal oscillations. This performance highlights its superior capability in maintaining inter-area tie-line power stability and its effectiveness in suppressing tie-line power deviations.

Regarding the output voltage response, the conventional PID controllers show higher overshoot and longer settling times, indicating less effective damping of system oscillations. In contrast PIDD2, display significantly improved transient responses with reduced overshoot and faster convergence to the steady-state value. Among the evaluated approaches, the combined controller (FPIDD2 + PIDD2), demonstrates the best overall performance, achieving rapid voltage stabilization with negligible overshoot and minimal steady-state error.

In summary, the overall results confirm the superior performance of the proposed FPIDD²+PIDD² hybrid controller compared to conventional PID and standalone PIDD² schemes, as it effectively suppresses both frequency and tie-line power deviations while ensuring fast and stable voltage recovery, demonstrating its robustness and efficiency in enhancing overall system stability and control performance.

In this case, the optimal controllers’ sittings obtained for case study No.4 are shown per Table 21, and Table 22, while the power system dynamic responses are presented in Table 23.

Table 21.

Optimal controllers’ settings for the LFC loop in the first and second area.

Controller Optim. Algorithm Inline graphic Inline graphic
KP KI KD1 N 1 KD2 N 2 KE KCE KP KI KD1 N 1 KD2 N 2 KE KCE
PID PSO 0.1 1.4 1.3 0.5 - - - - 0.2 1.3 1.3 0.2 - - - -
PID GTO 0.1 0.3 1.7 0.3 - - - - 0.1 0.2 0.5 0.3 - - - -
PID MPA 0.1 1.2 1.2 0.5 - - - - 0.1 1.4 1.1 0.2 - - - -
PIDD² PSO 81.5 2.0 2.0 2.0 9.7 67.7 - - 80.5 2.0 1.7 1.5 7.9 83.1 - -
PIDD² GTO 40.0 2.0 1.8 1.3 9.2 61.1 - - 34.3 2.0 2.0 1.1 9.1 68.8 - -
PIDD² MPA 99.8 2.0 2.0 1.5 10.0 51.2 - - 100.0 2.0 2.0 2.0 10.0 49.0 - -
FPIDD²+PIDD² PSO 100.0 2.0 2.0 2.0 10.0 58.7 2.0 0.1 83.9 2.0 2.0 2.0 6.9 96.5 1.9 0.1
FPIDD²+PIDD² GTO 100.0 2.0 0.1 2.0 10.0 100.0 2.0 0.0 100.0 2.0 2.0 2.0 10.0 0.1 2.0 0.1
FPIDD²+PIDD² MPA 99.8 2.0 2.0 2.0 9.6 60.6 2.0 0.0 48.6 2.0 1.9 0.1 3.6 100.0 2.0 0.0
Table 22.

Optimal controllers’ settings for the AVR loop in the first and second area.

Controller Optimization Algorithm Inline graphic Inline graphic
KP KI KD1 N 1 KD2 N 2 KE KCE KP KI KD1 N 1 KD2 N 2 KE KCE
PID PSO 0.2 0.8 0.4 2.0 - - - - 0.7 1.2 0.4 1.0 - - - -
PID GTO 0.8 0.8 0.3 0.4 - - - - 0.5 0.6 0.6 0.7 - - - -
PID MPA 0.1 0.7 0.4 2.0 - - - - 0.7 1.2 0.3 1.0 - - - -
PIDD² PSO 1.9 2.0 1.6 1.6 1.6 100.0 - - 1.8 1.9 2.0 1.7 2.0 100.0 - -
PIDD² GTO 1.7 2.0 1.2 1.8 1.0 75.6 - - 1.5 0.9 2.0 1.6 1.7 67.4 - -
PIDD² MPA 2.0 2.0 1.9 2.0 1.7 99.6 - - 0.1 2.0 2.0 2.0 2.0 74.6 - -
FPIDD²+PIDD² PSO 1.9 1.8 2.0 2.0 1.1 100.0 - - 1.0 2.0 2.0 2.0 2.0 100.0 - -
FPIDD²+PIDD² GTO 2.0 2.0 1.3 1.3 1.7 100.0 - - 0.1 2.0 2.0 2.0 2.0 100.0 - -
FPIDD²+PIDD² MPA 1.9 1.2 2.0 0.1 0.4 0.2 - - 0.7 1.9 0.2 0.7 0.9 21.4 - -
Table 23.

Dynamic responses of the system.

Controller Optim Algorithm ∆f1 ∆f2 Ptie Vout1 Vout2
MO∆f1
(Hz)
MU∆f1
(Hz)
MO∆f2
(Hz)
MU∆f2
(Hz)
MOP
(p.u)
MUP
(p.u)
MP− V1
(p.u)
Tr−V1
(Sec.)
Ts−V1
(Sec.)
MP− V2
(p.u)
Tr−V2
(Sec.)
Ts−V2
(Sec.)
PID PSO 0.417 −1.276 0.772 −1.464 0.103 −0.162 0.471 0.531 12.073 0.699 0.252 13.652
PID GTO 0.511 −1.588 0.522 −1.574 0.077 −0.130 0.380 0.397 8.483 0.674 0.254 11.746
PID MPA 0.331 −1.170 0.746 −1.483 0.116 −0.143 0.483 0.610 12.364 0.697 0.252 12.830
PIDD² PSO 0.010 −0.079 0.009 −0.078 0.001 −0.001 0.436 0.102 2.620 0.156 0.145 3.146
PIDD² GTO 0.012 −0.086 0.009 −0.083 0.001 −0.001 0.230 0.151 2.146 0.196 0.152 2.906
PIDD² MPA 0.012 −0.064 0.008 −0.059 0.001 −0.001 0.459 0.077 3.214 0.195 0.145 3.188
FPIDD²+PIDD² PSO 0.002 −0.015 0.001 −0.016 0.000 0.000 0.423 0.111 2.971 0.183 0.170 3.009
FPIDD²+PIDD² GTO 0.028 −0.046 0.008 −0.034 0.000 −0.001 0.384 0.112 4.806 0.164 0.144 3.272
FPIDD²+PIDD² MPA 0.002 −0.015 0.011 −0.036 0.002 0.000 0.467 0.246 4.135 0.220 0.200 2.589

As presented in Table 23, the performance of the three controller configurations demonstrates the progressive enhancement in system stability and dynamic response.

In terms of frequency regulation, the conventional PID controllers exhibit the weakest performance, characterized by pronounced oscillations with overshoot and undershoot values reaching up to ± 1.5 Hz. This behavior reflects poor damping capability and slow recovery following load disturbances. The PIDD² controllers significantly enhance frequency stability by reducing both the magnitude and duration of oscillations, with the worst-case overshoot and undershoot limited to approximately 0.01 Hz and − 0.06 Hz, respectively. The hybrid FPIDD²+PIDD² controller achieves the best performance, maintaining almost negligible oscillations, with overshoot and undershoot values as low as 0.002 Hz and − 0.015 Hz, indicating exceptional damping and rapid convergence to steady state.

Regarding tie-line power deviation (ΔPtie), the PID controllers display the largest fluctuations, reaching up to 0.12 p.u., signifying weak inter-area coordination and delayed oscillation suppression. The PIDD² controllers markedly improve tie-line power stability, limiting deviations to around ± 0.001 p.u., although minor transient fluctuations remain. In contrast, the hybrid FPIDD²+PIDD² configuration demonstrates the most stable tie-line power behavior, maintaining minimal deviations and effectively suppressing inter-area oscillations.

In terms of voltage response, the PID controllers again show inferior performance, with overshoots reaching approximately 0.7 p.u. in some cases and extended settling times, indicating inadequate voltage regulation and weak transient damping. The PIDD² controllers yield notable improvement, achieving faster settling and smaller overshoot values of about 0.20 p.u., thereby enhancing voltage stability. The hybrid FPIDD²+PIDD² controller outperforms both configurations, delivering rapid voltage stabilization with minimal steady-state error. In summary, across all three performance indicators, frequency, tie-line power, and voltage, the hybrid FPIDD²+PIDD² controller consistently outperforms both the PIDD² and conventional PID configurations, delivering superior damping, faster recovery, and enhanced robustness against dynamic disturbances.

Integral Time Absolute Error (ITAE) values for each of the three control schemes, tuned using the three optimization algorithms, are presented in Table 24.

Table 24.

The optimism integral time absolute error (ITAE) for all controllers.

Controller Optimization Algorithm Best ITAE
PSO GTO MPA Value Algorithm
PID 965.45 1066.06 993.59 993.59 PSO
PIDD² 553.15 568.51 551.81 551.81 MPA
FPIDD²+ PIDD² 62.19 54.85 54.84 54.84 MPA

The results presented in Table 24 demonstrate the substantial performance improvement achieved by the proposed FPIDD2 + PIDD2 controller over both classical PID and fractional-order PIDD2 controllers. This hybrid control scheme achieved the lowest ITAE value of 54.84, indicating highly efficient error minimization and enhanced transient response. In comparison, the conventional PID controller recorded the highest ITAE, approaching 1000, reflecting poor dynamic performance and limited control accuracy. The PIDD2 controller showed moderate improvement, reducing the ITAE to approximately 550, almost half of the PID value, yet it still falls short of the performance achieved by the hybrid configuration. These findings confirm that FPIDD2 + PIDD2 significantly enhances control precision, system stability, and damping effectiveness, thereby validating the robustness and efficiency of the proposed control strategy.

Results summary

The final case study introduces a random load perturbation in Area-1, serving as a stress test to evaluate the robustness of the controller under severe dynamic disturbances. Under these challenging conditions, the conventional PID controller faced significant limitations, with the best recorded ITAE reaching approximately 965. In contrast, the PIDD² controller showed substantial improvements across all dynamic performance indicators. It effectively controlled frequency deviations, tie-line power, and terminal voltage, reducing the ITAE to about half of the PID controller’s value, with a final ITAE of around 550.

The hybrid control strategy (FPIDD² +PIDD²), delivered the most impressive results overall. This configuration demonstrated minimal steady-state error and reduced overshoot, further lowering the ITAE by 90.1% compared to the standalone PIDD² controller, and by 94.3% compared to the PID controller. These results underscore the superior resilience, precision, and dynamic performance of the hybrid FPIDD²+PIDD² approach in managing large-scale load disturbances in interconnected power systems.

Additionally, it was noted that all optimization algorithms produced nearly identical ITAE values, showing only minor differences within each control technique (PID, PIDD², and FPIDD²+PIDD). This further emphasizes that, under severe disturbance scenarios, the choice of controller architecture has a far more significant impact on system stability and performance than the specific optimizer used. A plausible explanation is that advanced controller architectures inherently exhibit greater adaptability features that are crucial for responding to unpredictable conditions such as RLP. Consequently, these findings suggest a strategic shift in focus: rather than relying primarily on sophisticated optimization techniques for conventional controllers, greater performance gains may be realized by developing more advanced control architectures.

Statistical performance evaluation

The computational effort also was quantified using the average execution time obtained through MATLAB/Simulink profiling on an Intel® Core™ i5-4300U processor (@ 1.90 GHz 2.50 GHz, 12 GB RAM). The results are summarized as shown per Table 25, which provides a comprehensive summary of the simulation results obtained from the four case studies employed to evaluate the three control strategies, including conventional PID, PIDD², and the proposed hybrid FPIDD²+PIDD² controllers, with each optimally tuned using the three metaheuristic optimization algorithms PSO, GTO, and MPA.

Table 25.

Computational complexity.

Controller Average execution time per 1 control cycle (minutes) Relative computational cost (%) Remarks
PID 13 100 Baseline reference
PIDD² 16 123 Slight increase due to extra derivative term
FPIDD²+PIDD² 22 169 Moderate cost; feasible for real-time deployment

Table 26 presents the comparative performance of PID, PIDD², and the proposed FPIDD²+PIDD² hybrid controller across four case studies, with performance evaluated using the ITAE criterion and controller parameters optimized via PSO, GTO, and MPA. The results demonstrate that the FPIDD²+PIDD² hybrid controller outperforms conventional PID and standalone PIDD² schemes in all cases, achieving notable improvements in control performance. The overall uncertainty in the results is estimated at approximately 5%, which remains within acceptable limits for control system simulations and experimental validations, and does not compromise the validity of the comparative analysis or the conclusions drawn.

Table 26.

Integral time absolute error (ITAE) for all control schemes across all four case studies.

Case Study No. Control scheme ITAE based on Statistical analysis ITAE reduction of
FPIDD²+ PIDD² compared to
Mean (µ) Standard deviation (σ) Variance (σ2) Relative Uncertainty (σ/µ × 100%)
PSO GTO MPA PID PIDD²
1 st case study PID 585.2 528.8 550.2 554.7 23.3 540.7 4.3% 90.3% 90.2%
PIDD² 549.3 549.4 548.0 548.9 0.6 0.4 0.1%
FPIDD²+ PIDD² 53.6 53.9 53.2 53.6 0.3 0.1 0.6%
2nd case study PID 1060.2 858.8 599.9 839.7 188.4 35501.2 24.2% 93.1% 89.2%
PIDD² 535.4 534.6 535.8 535.2 0.5 0.2 0.1%
FPIDD²+ PIDD² 66.1 52.2 54.8 57.7 6 36.5 10.7%
3rd case study PID > 109 > 109 > 109 N.A. N.A. N.A. N.A. 100.0% 90.0%
PIDD² 541.8 540.3 540.4 540.8 0.7 0.4 0.1%
FPIDD²+ PIDD² 56.2 52.8 53.5 54.2 1.5 2.2 2.8%
4th case study PID 965.5 1066.1 993.6 1008.4 42.4 1796.2 4.2% 94.3% 89.7%
PIDD² 553.2 568.5 551.8 557.8 7.6 57.4 1.4%
FPIDD²+ PIDD² 62.2 54.9 54.8 57.3 3.5 12 6.1%
Average 5.0% 93.9% 90.2%

Tables 27 and 28 present the comparative percentage improvements in the dynamic response parameters of the proposed hybrid (FPIDD²+PIDD²) controllers over PID and PIDD2 controllers grouped by each one of the three optimization techniques. The results highlight the capability of the hybrid controller in enhancing system stability and dynamic response across various performance indices.

Table 27.

Percentage improvement in dynamic response parameters of hybrid (FPIDD²+PIDD²) controllers compared to the PID Controller.

Controller ∆f1 (Hz) ∆f2 (Hz) Ptie (p.u) Vout1 (p.u) Vout2 (p.u)
MO∆f1 MU∆f1 MO∆f2 MU∆f2 MOP MUP MP− V1 Tr−V1 Ts−V1 MP− V2 Tr−V2 Ts−V2
PSO 97% 91% 99% 91% 98% 100% 43% 85% 38% 71% 68% 71%
GTO −25% 56% 70% 69% 74% 49% 25% 36% 49% 48% 29% 48%
MPA 71% 78% 69% 74% 46% 73% 23% −17% 53% 49% 12% 59%
Average 48% 75% 79% 78% 73% 74% 30% 35% 46% 56% 36% 59%

The results of case study # 3 have been omitted for simplicity.

Table 28.

Percentage improvement in dynamic response parameters of hybrid (FPIDD²+PIDD²) controllers compared to the PIDD2 Controller.

Controller ∆f1 (Hz) ∆f2 (Hz) Ptie (p.u) Vout1 (p.u) Vout2 (p.u)
MO∆f1 MU∆f1 MO∆f2 MU∆f2 MOP MUP MP− V1 Tr−V1 Ts−V1 MP− V2 Tr−V2 Ts−V2
PSO 43% 72% 91% 76% 36% 75% 31% 23% −73% 5% 1% 20%
GTO −3% 45% 67% 64% 50% 13% 8% 21% −14% 20% 3% 0%
MPA 94% 79% 58% 62% −150% 91% 12% −115% −8% 4% −22% 0%
Average 45% 65% 72% 67% −21% 60% 17% −24% −32% 10% −6% 7%

Conclusion

This study investigates the performance of a hybrid FPIDD²+PIDD² control strategy for coordinated load-frequency control (LFC) and automatic-voltage regulation (AVR) in complex power-system environments. Comparative analyses carried out across four progressively challenging case studies demonstrate that the proposed hybrid scheme offers superior robustness and adaptability compared with the conventional PID controller and the improved PIDD² controller under the tested conditions. The classical PID controller serves as a useful baseline but shows clear limitations such as higher overshoot, longer settling times, increased steady-state error, and occasionally oscillation or instability when confronted with system nonlinearities, inter-area coupling and dynamic uncertainties. The PIDD² controller delivers measurable improvement over the PID. Most significantly, the hybrid FPIDD²+PIDD² configuration attains the best overall performance in the considered scenarios by reducing the integral time-weighted absolute error (ITAE) by up to approximately 94% relative to the PID controller and by about 90% relative to the PIDD² controller. In addition, the study explores the influence of tuning-optimizer choice (PSO, MPA and GTO) on controller performance. Optimizer selection markedly affects the PID controller’s performance whereas its impact on the PIDD² and hybrid FPIDD²+PIDD² controllers is far less pronounced. This finding suggests that the controller architecture exerts a stronger influence on system behavior than the specific optimization method.

Although this study found that the hybrid FPIDD²+PIDD² controller demonstrated favorable dynamic characteristics and markedly improved performance across most indices, the hybrid control scheme did not outperform the PIDD² controller on all dynamic metrics which suggests potential for further refinement via offline optimization and adaptive fuzzy scaling.

In addition. The analysis was carried out under idealized system conditions with parameter variations modelled deterministically. Real-world factors such as communication delays, measurement noise, actuator nonlinearities and parameter drift were not explicitly represented. Practical implementation may thus face challenges in parameter tuning, noise sensitivity and computational load. Moreover, the real-time demands of fuzzy inference and second-derivative filtering could require hardware optimization for embedded implementation. Accordingly, future work may extend and validate the proposed FPIDD²+PIDD² control framework in larger, more complex multi-area power systems that integrate renewables. This will include real-time evaluation via hardware-in-the-loop experiments and development of adaptive online re-tuning strategies to enhance long-term robustness. Further research should establish systematic methodologies for configuring the FPIDD² controller, defining appropriate upper and lower bounds for tuning parameters, population size, iterations number, fuzzy rule-bases, membership functions and crisp ranges. To support scalability, comparability and wider adoption of intelligent control architectures, it is also recommended to develop standardized benchmarks, performance metrics and test cases.

List of symbols

∆f1

Area (1) frequency deviation (Hz)

∆f2

Area (2) frequency deviation (Hz)

∆Ptie

The power deviation of the tie-line (p.u.)

AVR

Automatic Voltage Regulator

B1, B2

Frequency bias coefficients

Bg

Valve positioner time constant

C12

Synchronization coefficient

CE

Rate of fuzzy controller error change

Cg

Gas turbine valve positioner

CL

Control law

COG

Center of gravity

E

Error of fuzzy controller

Ess

Steady state error

EV

Electrical Vehicle

FIS

Fuzzy Inference System

FPIDD2

Fuzzy Proportional Integral Derivative Double Derivative Controller

GDB

Dead Band of Governor

GRC

Constraint of Generation Rate (% p.u)

GTO

Gorilla Troops Optimization

ITAE

Integral time absolute error

Ka

AVR system amplifier gain

Ke

AVR system exciter gain

Kn

AVR system generator gain

Ks

AVR system sensor gain

KD1, KD2

Derivative gains

KE, KCE

Fuzzy controller inputs scaling factors

KEV

Electric vehicle gain

KI

Integral gain

KP

Proportional gain

Kps1, Kps2

Power system gains

Kr

Steam turbine reheat constant

LFC

Load Frequency Control

Mp-V1

Maximum overshoot magnitude of terminal voltage of Area (1)

Mp-V2

Maximum overshoot magnitude of terminal voltage of Area (2)

MO∆f1

Maximum Overshoot of Frequency Deviation of Area (1)

MO∆f2

Maximum Overshoot of Frequency Deviation of Area (2)

MO∆P

Maximum Overshoot of Tie-line Power Deviation

MU∆f1

Minimum Overshoot of Frequency Deviation of Area (1)

MU∆f2

Minimum Overshoot of Frequency Deviation of Area (2)

MU∆P

Minimum Overshoot of Tie-line Power Deviation

MPA

Marine Predator Algorithm

N1, N2

The coefficients of the filters

PFhyd

Hydro unit participation factor

PFg

Gas unit participation factor

PFTh

Thermal unit participation factor

PFPV

PV unit participation factors

PFWT

Wind turbine unit participation factor

PID

Proportional Integral Derivative Controller

PIDD2

Proportional Integral Derivative Double Derivative Controller

PSO

Particle Swarm Optimization

PV

Photovoltaics

RESs

Sources of renewable energy

RTh

Governor speed regulation parameters of thermal unit

Rhyd

Governor speed regulation parameters of hydro unit

Rg

Governor speed regulation parameters of gas unit

RLP

Random Load Perturbation

SLP

Step Load Perturbation

T12

Synchronizing coefficient

Ta

AVR system amplifier time constant

Te

AVR system exciter time constant

Tn

AVR system generator time constant

Ts

AVR system sensor time constant

Tcd, Trh

Compressor discharge volume, and transient droop time constants

Tcr

The gas turbine combustion reaction’s time delay

TEV

Electric vehicle time constant

Tgh

Hydro turbine governor time constant

Tf

Gas turbine fuel time constant

Tps1, Tps2

Time constants of power system

Tr-V1

Rise time of terminal voltage of Area (1) in seconds

Tr-V2

Rise time of terminal voltage of Area (2) in seconds

Trs

Reset time of speed governor of the Hydro turbine

Ts-V1

Settling time of terminal voltage of Area (1) in seconds

Ts-V2

Settling time of terminal voltage of Area (2) in seconds

Tsimulation

Simulation time

Tt

Time constant of steam turbines

Tsg

Governor time constant of steam turbine

Tr

Reheat time constant of Steam turbine

Tw

Water starting time in hydro turbine

Va

Amplifier output in AVR loop

Ve

Exciter terminal voltage in AVR loop

Vg

AVR terminal voltage

Vout1

Area (1) output terminal voltage (p.u.)

Vout2

Area (2) output terminal voltage (p.u.)

Vref

AVR reference voltage

Vs

Feedback signal in AVR loop

Xg

The gas turbine governor’s lead time constant

Author contributions

Mohamed H. T. Omar: Conceptualization, Methodology, Investigation, Writing - Original Draft.Ragi A. Hamdy: Validation, Formal Analysis, Data Curation, Writing - Review & Editing.Hossam Kotb: Conceptualization, Methodology, Software, Formal Analysis, Writing - Review & Editing, Visualization, Supervision.All authors contributed to manuscript revision, approved the final version, and agreed to be accountable for all aspects of the work.

Funding

Open access funding provided by The Science, Technology & Innovation Funding Authority (STDF) in cooperation with The Egyptian Knowledge Bank (EKB). This research received no external funding.

Data availability

The datasets used and/or analyzed during the current study available from the corresponding author on reasonable request.

Declarations

Competing interests

The authors declare no competing interests.

Footnotes

Publisher’s note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

References

  • 1. Impram, S., Neşe, S. V. & Oral, B. Challenges of renewable energy penetration on power system flexibility: A survey. IEEE Access.8, 211965–211988 (2020). [Google Scholar]
  • 2.Kumar, A. et al. Renewable integration challenges in Two-Area power systems. IEEE Trans. Power Syst.38 (2), 1123–1135 (2023). [Google Scholar]
  • 3.Prusty, B. N. & Sahoo, S. R. Cascading failures in interconnected grids: A review, renew. Sustain. Energy Rev. 172 (2023).
  • 4.Zhang, J. et al. Nonlinear dynamics in modern power systems. IEEE Access11, 45672–45685 (2023). [Google Scholar]
  • 5.Islam, M. R. et al. Voltage collapse mitigation in Renewable-Rich grids. IEEE Trans. Power Del.38 (4), 2456–2468 (2023). [Google Scholar]
  • 6.Mishra, S. P. & Yadav, D. K. Frequency stability in low-inertia power systems. Appl. Energy, 342 (2023).
  • 7.Wang, Y. et al. Tie-Line power oscillations in Multi-Area systems. IEEE Trans. Smart Grid. 14 (3), 1987–1999 (2023). [Google Scholar]
  • 8.Ali, T. et al. Load frequency control and automatic voltage regulation in four-area interconnected power systems using a gradient-based optimizer. Energies16(5), 2086. 10.3390/en16052086 (2023). [Google Scholar]
  • 9.Ma, Y., Niculescu, S. I., Tang, Y. & Qiu, L. Beyond linear limits: Design of robust nonlinear PID control. Automatica168, 110568. 10.1016/j.automatica.2024.110568 (2024). [Google Scholar]
  • 10.Rakhshani, E. et al. Adaptive PID for LFC in dynamic grids. IEEE Syst. J.17 (1), 512–523 (2023). [Google Scholar]
  • 11.Liu, X., Qiao, S. & Liu, Z. A survey on load frequency control of multi-area power systems: Recent challenges and strategies. Energies16(5), 2323. 10.3390/en16052323 (2023). [Google Scholar]
  • 12.Singh, A. K. & Pindoriya, N. M. AI in power system control: trends and gaps. IEEE Trans. Ind. Inf.19 (5), 4567–4579 (2023). [Google Scholar]
  • 13.Xie, L. et al. Deep reinforcement learning for grid control. Nat. Energy8, 743–755 (2023). [Google Scholar]
  • 14.Sharma, R. et al. Unified Voltage-Frequency-Tie-Line control: A review. IEEE Trans. Energy Convers.38 (2), 1234–1245 (2023). [Google Scholar]
  • 15.Li, G. et al. Real-time adaptive control for power systems. Appl. Energy 342 (2023).
  • 16.Nguyen, T. & Wang, Q. Hybrid control architectures for power systems. IEEE Trans. Power Syst.39 (1), 521–534 (2024). [Google Scholar]
  • 17.Liu, Z. et al. Cyber-Resilient distributed control for smart grids. IEEE Trans. Smart Grid. 15 (2), 1456–1469 (2024). [Google Scholar]
  • 18.Gu, J. et al. Modern control architectures for resilient power grids: A survey. IEEE Syst. J., 16 (3) (2022).
  • 19.Sahu, R. K. et al. Design and Analysis of PIDD² Controller for LFC in Deregulated Power Systems. IET Generation, Transmission & Distribution 15 (10) (2021).
  • 20.Ray, P. K. & Paital, S. R. A robust PIDD² controller for frequency regulation in hybrid power systems. IEEE Trans. Industr. Inf., 18 (5) (2022).
  • 21.Dash, P. K., Panda, R. C. & Panigrahi, B. K. Impact of advanced thyristor-controlled series capacitor on load frequency control and automatic voltage regulator dual area system with interval type-2 fuzzy sets-PID usage. Processes12 (12), 2647. 10.3390/pr12122647 (2024). [Google Scholar]
  • 22.Gupta, D. K. Fractional-Order PID controller for load frequency control in Multi-Area deregulated hybrid power systems. ISA Trans.124, 45–58. 10.1016/j.isatra.2024.04.009 (2024). [Google Scholar]
  • 23.Wang, P., Chen, X., Zhang, Y., Zhang, L. & Huang, Y. Fractional-Order load frequency control of an interconnected power system with a hydrogen Energy-Storage unit. Fractal Fract.8 (3), 126. 10.3390/fractalfract8030126 (2024). [Google Scholar]
  • 24.Alnefaie, S., Sakr, N. & Mahmoud, H. A. Optimizing load frequency control of Multi-Area power systems integrated with renewables using advanced cascaded controllers. Dynamics Continuous Discrete Impulsive Syst. Ser. B: Appl. Algorithms. 31 (4), 1123–1145 (2024). [Google Scholar]
  • 25.[25]Zadeh, L. A. Fuzzy logic in control systems: Past, Present, and future. IEEE Comput. Intell. Mag. 17 (1) (2022).
  • 26.Mishra, S. & Das, D. C. Adaptive fuzzy logic-based LFC for renewable-integrated power systems. Appl. Energy 306 (2022).
  • 27.Hannan, M. A. et al. Fuzzy logic controllers for smart grid applications: A critical review. Renew. Sustain. Energy Rev.168 (2022).
  • 28.Ali, A., Biru, G. & Bantyirga, B. Design the potential application of fuzzy logic-based AGC and AVR for multi-area interconnected power systems: A case study on Ethiopia. Int. J. Eng. Trends Technol.71 (5), 84–97. 10.14445/22315381/IJETT-V71I5P208 (2023). [Google Scholar]
  • 29.Khan, M. U., Wang, J. & Zhang, L. Fuzzy logic-based automatic voltage regulator integrated adaptive vehicle-to-grid controller for ancillary services support. Energy Inf.8 (1), 515. 10.1186/s42162-025-00515-7 (2025). [Google Scholar]
  • 30.Mansour, S., Attia, M. A., Badr, A. O. & Shaaban, M. F. Enhancement of LFC–AVR combined system by using fuzzy PID controller. In Proc. 2024 6th Int. Youth Conf. on Radio Electronics, Electrical and Power Engineering (REEPE 2024), Moscow, Russia (2024). 10.1109/REEPE60449.2024.10479895
  • 31.Kalyan, C. N. S. et al. Hybrid fuzzy PID control with HAEFA optimization for combined LFC and AVR systems. Cogent Eng.11(1), 2391958. 10.1080/23311916.2024.2391958 (2024). [Google Scholar]
  • 32.Gad, A. G. Particle swarm optimization algorithm and its applications: A systematic review. Arch. Comput. Methods Eng.29 (5), 2531–2561. 10.1007/s11831-021-09694-4 (2022). [Google Scholar]
  • 33.Houssein, E. H., Gad, A. G., Talpur, K. & Suganthan, P. N. Major advances in particle swarm optimization: theory, analysis, and application. Swarm Evol. Comput.63, 100868 (2021). [Google Scholar]
  • 34.Fang, J. et al. A survey of algorithms, applications and trends for particle swarm optimization. Int. J. Netw. Dyn. Intell.2(1), 24–50 (2023). [Google Scholar]
  • 35.Sengupta, S., Basak, S. & Peters, R. A. II, Particle Swarm Optimization: A Survey of Historical and Recent Developments with Hybridization Perspectives. arXiv preprint arXiv:1804.05319 (2018). Available: https://arxiv.org/abs/1804.05319
  • 36.Grassi, S., Huang, H., Pareschi, L. & Qiu, J. Mean-field Particle Swarm Optimization, arXiv preprint arXiv:2108.00393 (2021). Available: https://arxiv.org/abs/2108.00393
  • 37.Sienz, J. & Innocente, M. S. Particle Swarm Optimization: Fundamental Study and Its Application to Optimization and to Jetty Scheduling Problems. arXiv preprint arXiv:2101.11096 (2021). Available: https://arxiv.org/abs/2101.11096
  • 38.Izci, D., Ekinci, S. & Hekimoğlu, B. Dynamic load frequency control in power systems using a filtered/advanced PID controller optimized by hybrid metaheuristics. Sci. Rep.14, 77247. 10.1038/s41598-024-77247-3 (2024). [Google Scholar]
  • 39.Nguyen, N. K. & Diem-Vuong Doan and Novel Multi-Stage Hybrid-Smart Load-Frequency controller to an interconnected power system considering HVDC and renewable energy sources. SSRG Int. J. Electr. Electron. Eng.11 (6), 197–204. 10.14445/23488379/IJEEE-V11I6P122 (2024). [Google Scholar]
  • 40.Faramarzi, F., Fesanghary, M. & Shahrabi, A. H. M. Marine predator algorithm: A novel optimization technique. Soft Comput.24(11), 8971–8985 (2020). [Google Scholar]
  • 41.Singh, H. B., Sharma, R. & Tiwari, A. Optimization techniques using marine predator algorithms for solving engineering problems. Comput. Intell. Neurosci.2021, 6715847 (2021). [Google Scholar]
  • 42.Su, G. Y., Wu, Z. H. & Jiang, X. Y. Hybrid marine predator algorithm with Lévy flights and Brownian motion for solving complex engineering problems. Swarm Evol. Comput.55, 145–160 (2020). [Google Scholar]
  • 43.Jang, K. Z., Chen, P. H. & Liao, Y. H. A review on the marine predator algorithm: Variants and applications. Eng. Appl. Artif. Intell.92, 103656 (2020). [Google Scholar]
  • 44.Xie, M., Yang, Z. X. & Liu, X. D. Optimization of complex functions using an enhanced marine predator algorithm. J. Optim. Theory Appl.184 (2), 312–330 (2021). [Google Scholar]
  • 45.Zadeh, P. G., Sim, K. R. Y. & Mohamad, M. K. M. Marine predator algorithm for global optimization: A comparative study and performance evaluation. Comput. Mater. Continua66(1), 451–470 (2021). [Google Scholar]
  • 46.Zhang, L., Zhao, W. & Zhang, C. F. Impact of environmental factors on the performance of the marine predator algorithm. J. Comput. Sci.47, 38–52 (2020). [Google Scholar]
  • 47.Mirjalili, S. & Kazem, S. M. A. The gorilla troops optimizer: A new metaheuristic algorithm inspired by the social structure of gorilla troops. Swarm Evol. Comput.61, 100851 (2021). [Google Scholar]
  • 48.Fard, M. M. T. & Wang, J. Hybridizing the gorilla troops optimizer with genetic algorithms for complex optimization problems. Appl. Soft Comput.97, 106718 (2021). [Google Scholar]
  • 49.Chen, H., Wei, J. & Xu, L. Optimization of multi-modal problems using the gorilla troops optimizer. Eng. Appl. Artif. Intell.99, 104056 (2021). [Google Scholar]
  • 50.Zhang, Y., Li, W. & Guo, L. Enhancing the exploration-exploitation balance of the Gorilla troops optimizer. J. Comput. Sci.51, 100823 (2021). [Google Scholar]
  • 51.Wang, B., Song, X. & Choi, M. Y. Performance analysis and application of Gorilla troops optimizer in engineering design optimization. Comput. Ind. Eng.158, 107358 (2021). [Google Scholar]
  • 52.Araujo, R. J. W. & Andrade, F. C. G. S. Hybridizing the Gorilla troops optimizer with particle swarm optimization for multi-objective optimization. Soft. Comput.25 (2), 55–65 (2022). [Google Scholar]
  • 53.Yadav, P. N. & Bhavsar, V. C. A comparative study of optimization algorithms: The case of gorilla troops optimizer. Comput. Intell. Neurosci.2022, 7461712 (2022). [Google Scholar]
  • 54.Mishra, S. et al. Adaptive load frequency control for Multi-Area power systems with energy storage. IEEE Trans. Sustain. Energy. 15 (1), 123–135 (2024). [Google Scholar]
  • 55.Wang, Y. & Li, K. Coordinated LFC and AVR in Renewable-Integrated power systems. Int. J. Electr. Power Energy Syst.155, 109543 (2024). [Google Scholar]
  • 0.Kumar, R. S., Venkata Prasanth, B. & Srinivasa Rao, R. A critical review on smart control techniques for load frequency control in an interconnected power system. J. Nanosci. Mater. Eng. Syst.10.14447/jnmes.v27i4.a07 (2024). [Google Scholar]
  • 57.Zhang, J. et al. Complexity management in modern power systems: challenges and solutions. IEEE Trans. Power Syst.39 (2), 1456–1472 (2024). [Google Scholar]
  • 58.Gupta, A. & Chakrabarti, S. Power system modeling approaches for stability analysis: A comparative study. Int. J. Electr. Power Energy Syst.156, 109632 (2024). [Google Scholar]
  • 59.Alam, M. R. & Saha, T. K. Two-Area power system models for renewable integration studies: validation and applications. IEEE Access.12, 11245–11260 (2024). [Google Scholar]
  • 60.Wang, L. et al. Simplified power system models for stability and control analysis. Electr. Power Syst. Res.225, 109876 (2024). [Google Scholar]
  • 61.Pandey, R. K. & Bansal, H. O. Reduced-order modeling techniques for large-scale power system analysis. Renew. Sustain. Energy Rev.191, 114123 (2024). [Google Scholar]
  • 62.Chen, S. et al. Interconnection dynamics in modern power grids: from Two-Area to Multi-Area systems. IEEE Syst. J.18 (1), 567–578 (2024). [Google Scholar]
  • 63.Fernandez, E. et al. Power flow coordination in interconnected systems: a two-area case study. IET Gener. Transm. Distrib.18(3), 345–359 (2024). [Google Scholar]
  • 64.Li, K. & Mi, Y. Frequency regulation challenges in interconnected power areas. Appl. Energy355, 122345 (2024). [Google Scholar]
  • 65.Kundur, P. & Morison, G. K. Fundamental behaviors of interconnected power systems: lessons from Two-Area models. IEEE Trans. Power Delivery. 39 (2), 987–1001 (2024). [Google Scholar]
  • 66.Bevrani, H. & Hiyama, T. Balancing accuracy and complexity in power system modeling. Energy Rep.10, 2345–2360 (2023). [Google Scholar]
  • 67.Sharma, D. R. et al. Computationally efficient power system models for dynamic analysis. Int. J. Emerg. Electr. Power Syst.25 (1), 45–62 (2024). [Google Scholar]
  • 68.Eltamaly, A. M. et al. Framework for power system simulation: from Two-Area to Large-Scale models. Sustain. Energy Technol. Assess.61, 103456 (2024). [Google Scholar]
  • 69.Sharma, R. K. & Patel, M. A comprehensive review of load frequency control technologies. Energies17 (12), 2915. 10.3390/en17122915 (2024). [Google Scholar]
  • 70.Doan, D. V., Nguyen, N. K. & Thai, Q. V. A novel load-frequency control scheme applying fuzzy logic technique for two-area interconnected power systems with renewable energy sources. Meas. Control Autom.4 (1), 160. 10.64032/mca.v4i1.160 (2024). [Google Scholar]
  • 71.Khamari, S. Photovoltaic generation systems modeling and performance prediction: A review. Renew. Energy. 146, 234–246 (2020). [Google Scholar]
  • 72.Bhatti, H. C., Akhtar, A. & Khan, M. A. Dynamic modeling of governor dead band and its effects on power system stability. IEEE Trans. Power Syst.35 (2), 1204–1212 (2020). [Google Scholar]
  • 73.Hou, Y. & Xiong, H. Modeling of generation rate constraints in multi-area power systems. Int. J. Electr. Power Energy Syst.109, 124–131 (2019). [Google Scholar]
  • 74.Morsali, M., Shama, M. S. S. R., Rezaei, M. R. B. & Naghshbandi, M. Z. M. A. Modeling and control of multi-area power systems with hybrid generation using time-domain simulations. IEEE Access.6, 61792–61802 (2018). [Google Scholar]
  • 75.Parmar, S., Yadav, S. & Yadav, S. S. Nonlinear modeling and controller design for power systems with renewable energy integration. IEEE Trans. Power Syst.33 (4), 4352–4361 (2018). [Google Scholar]
  • 76.Nahas, M., Kermani, M. F. & Khorasani, H. F. Design and implementation of an automatic voltage regulator in power systems with renewable energy sources. IEEE Trans. Energy Convers.36 (4), 3111–3121 (2021). [Google Scholar]
  • 77.Khamari, M., Sahoo, S. K. & Mishra, R. K. Dynamic modeling of PV power generation systems considering weather impacts. Renew. Sustain. Energy Rev.115, 109393 (2020). [Google Scholar]
  • 78.Elkasem, M., Al-Maadeed, O. A. D. & Ibrahim, S. M. Wind power generation modeling and simulation using a white noise process. Renew. Energy145, 1136–1143 (2021). [Google Scholar]
  • 79.Saikia, N. & Das, N. K. Load frequency control of a two area Multi-source power system with electric vehicle. J. Control Autom. Electr. Syst.34 (4), 394–406. 10.1007/s40313-022-00974-3 (2023). [Google Scholar]
  • 80.Aly, M. et al. Optimized non-integer load frequency control scheme for interconnected microgrids in remote areas with high renewable energy and electric vehicle penetrations. Mathematics11(9), 2080. 10.3390/math11092080 (2023). [Google Scholar]
  • 81.Manousakis, N. M., Karagiannopoulos, P. S., Tsekouras, G. J. & Kanellos, F. D. Integration of renewable energy and electric vehicles in power systems: a review. Processes11(5), 1544. 10.3390/pr11051544 (2023). [Google Scholar]
  • 82.Kumar, N., Datta, P., Sharma, K., Mehrotra, R. & Singh, J. Controlling load frequency in a hybrid power system including electrical vehicles. In Modern Electronics Devices and Communication Systems 435–445 (Springer, 2023). 10.1007/978-981-19-6383-4_35. [Google Scholar]
  • 83.Irfan, M., Deilami, S., Huang, S., Tahir, T. & Veettil, B. P. Optimizing load frequency control in microgrid with vehicle-to-grid integration in Australia: Based on an enhanced control approach. Appl. Energy10.1016/j.apenergy.2024.123317 (2024). [Google Scholar]
  • 84.Aly, M. et al. Smart frequency control of a multicarrier microgrid in the presence of V2G electric vehicles. Int. Trans. Electr. Energy Syst.33 (5), e6205326. 10.1155/2023/6205326 (2023). [Google Scholar]
  • 85.Nayak, A., Rana, R. & Mishra, S. Frequency regulation by electric vehicle during grid restoration using adaptive optimal control. IFAC-Papers Online52(1), 270–275. 10.1016/j.ifacol.2019.03.050 (2019). [Google Scholar]
  • 86.Saikia, N. & Das, N. K. Electric vehicle participation for optimized load frequency control in a multi-area restructured power system. Int. J. Model. Simul.10.1080/02286203.2024.2327640 (2024). [Google Scholar]
  • 87.Abubakr, H., Lashab, A., Vasquez, J. C., Mohamed, T. H. & Guerrero, J. M. Novel V2G regulation scheme using dual-PSS for PV islanded microgrid. Appl. Energy340, 121012. 10.1016/j.apenergy.2023.121012 (2023). [Google Scholar]
  • 88.Khalil, A., Rajab, Z., Alfergani, A. & Mohamed, O. The impact of the time delay on the load frequency control system in microgrid with plug-in-electric vehicles. Sustain. Cities Soc.35, 365–377. 10.1016/j.scs.2017.08.012 (2017). [Google Scholar]
  • 89.Mohanty, D. & Panda, S. Modified salp swarm algorithm optimized fractional-order adaptive fuzzy PID controller for frequency regulation of hybrid power system with electric vehicle. J. Control Autom. Electr. Syst.32 (2), 416–438. 10.1007/s40313-020-00683-9 (2021). [Google Scholar]
  • 90.Gupta, T. S. D., Salgado, M. D. S. & Sanchez, J. L. J. Optimization and application of PIDD² controller for power system frequency regulation. IET Gener Transm Distrib.14 (13), 1291–1302. 10.1049/iet-gtd.2019.0936 (2020). [Google Scholar]
  • 91.Shankar, A. R. & Mallick, L. K. Performance analysis of a PIDD² controller for robotic motion control. IEEE Trans. Robot. Autom.36 (4), 819–828 (2021). [Google Scholar]
  • 92.AboRas, K. M., Ragab, M., Shouran, M., Alghamdi, S. & Kotb, H. Voltage and frequency regulation in smart grids via a unique fuzzy PIDD² controller optimized by gradient-based optimization algorithm. Energy Rep.9, 1201–1235 (2023). [Google Scholar]
  • 93.Bouaddi, A., Rabeh, R. & Ferfra, M. A fuzzy-PID controller for load frequency control of a two-area power system using a hybrid algorithm. Int. J. Electr. Comput. Eng. (IJECE). 14 (4), 3580–3591 (2024). [Google Scholar]
  • 94.Lima, J. F., Patiño-León, A., Orellana, M. & Zambrano-Martinez, J. L. Evaluating the impact of membership functions and defuzzification methods in a fuzzy system: case of air quality levels. Appl. Sci.15(4), 1934. 10.3390/app15041934 (2025). [Google Scholar]
  • 95.Djari, A. Influence of the membership functions number of fuzzy logic controller on the performances of dynamic systems. Romanian J. Inform. Technol. Automatic Control. 33 (1), 93–106 (2023). [Google Scholar]
  • 96.Zhang, K. Interpretable research of fuzzy methods: A literature survey. Inf. Fusion 103524 (2025).
  • 97.Romanov, A. A., Filippov, A. A. & Yarushkina, N. G. An approach to generating fuzzy rules for a fuzzy controller based on the decision tree interpretation. Axioms14(3), 196. 10.3390/axioms14030196 (2025). [Google Scholar]
  • 98.Kumar, S., Gupta, A. & Bindal, R. K. Load-frequency and voltage control for power quality enhancement in a SPV/wind utility-tied system using GA and PSO optimization. Results Control Optim.16, 100442. 10.1016/j.rieo.2024.100442 (2024). [Google Scholar]
  • 99.Hussein, M. M. et al. Advanced frequency control technique using GTO with balloon effect for microgrids with photovoltaic source to lower harmful emissions and protect environment. Sustainability16(2), 831. 10.3390/su16020831 (2024). [Google Scholar]
  • 100.Shahzad, M. I. et al. Load Frequency Control of Hybrid Power System Using Marine Predator Algorithm Tuned Cascaded Controller. In 2024 13th International Conference on Renewable Energy Research and Applications (ICRERA), Nagasaki, Japan, 946–951 (2024). 10.1109/ICRERA62673.2024.10815456
  • 101.[101]Islam, M. S., Roy, T. K. & Bushra, I. J. Marine predators algorithm-based robust composite controller for enhanced power sharing and real-time voltage stability in DC–AC microgrids. Algorithms18 (8), 531. 10.3390/a18080531 (2025). [Google Scholar]
  • 102.Kunya, A. B., Argin, M., Jibril, Y. & Shaaban, Y. A. Improved model predictive load frequency control of interconnected power system with synchronized automatic generation control loops. Beni-Suef Univ. J. Basic. Appl. Sci.10.1186/s43088-020-00072-w (2020). [Google Scholar]
  • 103.Kalyan, C. N. S. et al. Comparative performance assessment of different energy storage devices in combined LFC and AVR analysis of multi-area power system. Energies15, 629. 10.3390/en15020629 (2022). [Google Scholar]
  • 104.Ali, T. et al. Load frequency control and automatic voltage regulation in a Multi-Area interconnected power system using Nature-Inspired Computation-Based control methodology. Sustainability14, 12162. 10.3390/su141912162 (2022). [Google Scholar]
  • 105.Magdy, G. et al. Optimized coordinated control of LFC and SMES to enhance frequency stability of a real multi-source power system considering high renewable energy penetration. Prot. Control Mod. Power Syst.3, 39. 10.1186/s41601-018-0112-2 (2018). [Google Scholar]
  • 106.Hu, X., Tan, W. & Hou, G. Tuning of PID/PIDD² controllers for second-order oscillatory systems with time delays. Electronics12(14), 3168. 10.3390/electronics12143168 (2023). [Google Scholar]
  • 107.Mostafa, I. & Hassanein, W. Proportional double derivative linear quadratic regulator controller using an improvised grey Wolf optimization technique to control a quadcopter. Appl. Sci.11 (6), 2699. 10.3390/app11062699 (2024). [Google Scholar]
  • 108.Hu, N. The limitations of traditional PID controllers and modern optimization methods. Appl. Comput. Eng.147, 238–244. 10.54254/2755-2721/2025.22912 (2025). [Google Scholar]
  • 109.Abdillah, M. et al. Enhancement of frequency transient response using fuzzy-PID controller considering high penetration of doubly fed induction generators. Bull. Electr. Eng. Inf.13 (4), 2260–2268. 10.11591/eei.v13i4.6481 (2024). [Google Scholar]
  • 110.Mohanty, P. K., Sahu, B. K., Pati, T. K., Kar, S. K. & Panda, S. K. A novel fuzzy PID controller for load frequency control of multi-area interconnected power system. Int. J. Electr. Power Energy Syst.144, 108589. 10.1016/j.ijepes.2022.108589 (2023). [Google Scholar]
  • 111.Jha, D., Ahmed, A., Kumar, S. & Roy, D. Fuzzy-PID and interpolation: a novel synergetic approach to process control. Int. J. Optim. Control: Theor. Appl.14 (4), 355–364. 10.11121/ijocta.1483 (2024). [Google Scholar]
  • 112.Sahin, A. K., Cavdar, B. & Ayas, M. S. An adaptive fractional controller design for automatic voltage regulator system: sigmoid-based fractional-order PID controller. Neural Comput. Appl.36, 14409–14431. 10.1007/s00521-024-09816-6 (2024). [Google Scholar]
  • 113.Fernández-Jorquera, M., Zepeda-Rabanal, M., Aguila-Camacho, N. & Bárzaga-Martell, L. Design, tuning, and experimental validation of switched fractional-order PID controllers for an inverted pendulum system. Fractal Fract.9(4), 234. 10.3390/fractalfract9040234 (2025). [Google Scholar]
  • 114.Brahimi, T., Benalia, A. & Ameur, I. Flatness-based fractional-order PID control for constrained point tracking in unicycle mobile robots. J. Eng. Sci. Appl.58(8). 10.18280/jesa.580815 (2025). [Google Scholar]
  • 115.Başak, H. & Doğan, K. Effective fractional order PID control design of DC motors using the Walrus optimization algorithm. Pamukkale Univ. Eng. Sci. J.31 (4), 625–632 (2025). [Google Scholar]
  • 116.Kumar, K., Das, M. & Karn, A. K. ANFIS robust control application and analysis for load frequency control with nonlinearity. J. Electr. Syst. Inform. Technol.11, 65. 10.1186/s43067-024-00175-9 (2024). [Google Scholar]
  • 117.Sekyere, Y. O. M., Effah, F. B. & Okyere, P. Y. A. A novel ANFIS controller for LFC in RES-integrated three-area power system. J. Electron. Electr. Eng.10.37256/jeee.3220244886 (2024). [Google Scholar]
  • 118.Nguyen, C. H. et al. ANFIS-based LQR control for rotary double parallel inverted pendulum. J. Fuzzy Syst. Control. 2 (2), 109–116 (2024). [Google Scholar]
  • 119.Saravanan, G. Performance improvement of DC motor control system using ITAE-based PID tuning. Heliyon10.1016/j.heliyon.2024.e40033 (2025).40535861 [Google Scholar]
  • 120.Wang, H. Artificial bee colony algorithm based PID controller for steel rolling mill speed control — ITAE outperforming other indices. Eng. Appl. Artif. Intell.116, 105732. 10.1016/j.engappai.2022.105732 (2022). [Google Scholar]

Associated Data

This section collects any data citations, data availability statements, or supplementary materials included in this article.

Data Availability Statement

The datasets used and/or analyzed during the current study available from the corresponding author on reasonable request.


Articles from Scientific Reports are provided here courtesy of Nature Publishing Group

RESOURCES