Abstract
Modern power systems are increasingly complex and vulnerable to disturbances, with transmission line faults being the most frequent and disruptive. Accurate fault location estimation (FLE) is essential to ensure fast system restoration and reliable operation, particularly when flexible AC transmission system (FACTS) devices such as the Unified Power Flow Controller (UPFC) are present. This paper proposes a Moving Standard Deviation (MSD) assisted two-terminal traveling wave (TW) based FLE technique for UPFC-compensated transmission lines. In the proposed approach, terminal voltage signals are transformed into aerial mode signals using Clarke’s transformation, and MSD is applied to identify peak values (PMSDs). These peaks provide estimated times of arrival waves (ETAWs), which are used to compute the fault location. The method is validated on a 500 kV three-machine system with a 100 MVA UPFC under diverse scenarios, including varying fault distances, types, resistances, inception angles, close-in and far-bus faults, UPFC operating modes, sampling frequencies, and noisy environments. Results confirm that the proposed method consistently achieves high accuracy, with percentage errors maintained below 1% even at low sampling rates (60 Hz) and under severe noise (5 dB SNR). The technique is computationally simple, robust against UPFC influences, and offers practical applicability for modern power systems.
Keywords: Moving standard deviation, UPFC, Fault location estimation, Traveling wave, Arrival time
Subject terms: Energy science and technology, Engineering
Introduction
Modern power systems are rapidly evolving in size, complexity, and functionality due to growing electricity demand, renewable energy integration, and deployment of advanced devices that improve stability and controllability. While these developments enhance power transfer capability, they also increase the system’s vulnerability to disturbances such as overloading, maloperation of relays, and, most critically, transmission line faults (TLFs). Among all power system contingencies, TLFs are the most frequent and disruptive events. If not located and cleared promptly, they can trigger cascading failures, compromise stability, and delay restoration processes1. Hence, accurate and reliable fault location estimation (FLE) has become indispensable for secure and fast post-fault recovery in modern grids.
Role of FACTS and challenges for FLE
The introduction of Flexible AC Transmission System (FACTS) devices has significantly improved the operational flexibility of power networks. FACTS, and in particular the Unified Power Flow Controller (UPFC), enable enhanced power transfer, voltage regulation, and stability margins2. Despite these benefits, their presence alters the steady-state and transient characteristics of measured signals. By modifying the amplitude, phase, and waveform of voltages and currents, FACTS devices may degrade the performance of traditional protection and control systems2. This issue is especially acute for FLE schemes that rely on unaltered propagation of traveling waves or on stable impedance characteristics. Therefore, there is an urgent need for fault location methods that remain reliable in the presence of UPFC and similar controllers.
Existing methods of fault location
Over the last three decades, a wide range of FLE methods have been proposed. They can broadly be classified into three categories:
Impedance-based methods: These are computationally simple and widely implemented but require precise knowledge of network parameters. Their accuracy degrades with line parameter uncertainty, fault resistance, and presence of power electronics devices3.
Artificial intelligence (AI)-based methods: Approaches using Artificial Neural Networks (ANN), machine learning, or optimization techniques can achieve high accuracy and adaptability. However, they demand extensive training datasets covering numerous operating conditions, which is challenging in practice4.
Traveling wave (TW)-based methods: These rely on the detection of high-frequency transients generated at fault inception and are considered among the most robust and accurate FLE approaches. TW-based methods are commercially available5, but generally require very high sampling rates and their accuracy may be reduced when FACTS devices distort the fault transients6.
Literature on FACTS-compensated systems
Recognizing the shortcomings of conventional methods in FACTS environments, several researchers have attempted modifications:
Series FACTS devices: Time-domain and non-iterative line model approaches have been proposed7,8. ANN-based FLE methods have also been applied to series-compensated lines4.
Shunt FACTS devices: Time-domain approaches and game-theory formulations have been reported9–11.
UPFC systems: More limited efforts exist. Intrinsic Time Decomposition (ITD) assisted TW methods3, optimization-based time-domain schemes12, negative-sequence component approaches13, and transform-based methods such as hyperbolic and discrete orthogonal S-transforms14,15 have been studied.
Although these contributions are valuable, most involve either complex mathematical formulations, dependence on wide-area measurements, or sensitivity to parameter variations. Importantly, robust TW-based methods tailored for UPFC systems remain relatively underexplored. Few recent works further highlights the importance of developing more accurate FLE techniques. In16, transmission line protection with UPFC using traveling waves, emphasizing the challenges posed by FACTS in detection and localization is analyzed. Wan17 proposed an adaptive waveform similarity method to enhance traveling-wave speed estimation, reducing reliance on precise network parameters. Mahmoud et al.18 applied statistical coherence on current measurements for fault detection and classification, offering a non-TW alternative. Biswal19 presented a comprehensive review of traveling-wave-based fault location, highlighting persisting issues under FACTS compensation. More recently, In20, the influence of harmonic and transient noise on UPFC-compensated systems is investigated, achieving errors in the 0.52–0.78% range under high noise levels. These recent works reinforce the relevance of robust, computationally simple schemes, and position the present MSD-assisted two-terminal TW approach as a timely advancement.
Recent studies have highlighted both the potential and the limitations of traveling-wave-based fault location techniques in FACTS-compensated transmission systems. In5, traveling-wave principles were shown to provide high fault-location accuracy; however, the method relies on high sampling rates and is sensitive to waveform distortions introduced by power-electronic controllers. Shunt-FACTS-based investigations in11 demonstrated improved detection capability under certain operating conditions, but their performance deteriorates when system parameters vary dynamically or when noise levels increase. The influence of UPFC on fault-generated transients was specifically analyzed in16, where it was shown that series–shunt compensation significantly alters wave propagation characteristics, posing challenges to conventional traveling-wave detection schemes. A comprehensive review in19 further emphasized that, despite their accuracy, many existing traveling-wave-based approaches for FACTS-compensated lines suffer from high computational complexity, dependence on sophisticated signal processing, and limited robustness under practical conditions. These limitations motivate the present work, which adopts a moving standard deviation–assisted traveling-wave framework to achieve reliable, computationally simple, and UPFC-robust fault location estimation.
Research gap
From the literature, two critical gaps emerge:
Lack of computationally simple TW-based methods for UPFC - Existing schemes for UPFC rely heavily on signal decomposition or optimization, making them less practical for real-time applications.
Insufficient validation under realistic scenarios - Very few works comprehensively test FLE performance under conditions such as close-in and far-bus faults, low sampling rates, noise contamination, and varying UPFC operating parameters.
Addressing these gaps is vital because in practice, measurement devices may not always achieve ultra-high sampling rates, and noise is unavoidable in field signals. Moreover, UPFC operating modes (STATCOM, SSSC, or power control) alter system dynamics, and FLE methods must remain stable under such variations.
Objective and novelty of this research
To overcome the above limitations, this paper proposes a Moving Standard Deviation (MSD) assisted two-terminal traveling wave fault location method specifically designed for UPFC-compensated transmission systems. The novelty of this work can be summarized as follows:
First integration of MSD with TW for UPFC systems: Unlike previous studies relying on complex transforms, the proposed method applies MSD, a simple statistical measure of volatility, to aerial mode voltages obtained via Clarke’s transformation.
Efficient detection of arrival times: Peak values of MSD (PMSD) are used to estimate the Estimated Time of Arrival Waves (ETAWs), which directly determine fault location.
Minimal input requirements: The method requires only terminal voltage measurements, reducing hardware dependency.
Comprehensive validation: Performance is evaluated under diverse scenarios–fault distance, type, resistance, inception angle, close-in and far-bus faults, different UPFC operating modes and parameters, sampling frequencies from 60 Hz to 600 kHz, and noise levels as low as 5 dB.
Robustness and accuracy: Across all cases, the method maintains percentage errors well below the 1% threshold recommended by standards21.
Contribution
Traditional approaches–such as time-domain impedance models7,8, transform-based methods [14–15, 23], and optimization or ANN-driven algorithms4,12–generally rely on heavy signal processing, synchronized current and voltage measurements, or large training datasets. While these methods achieve acceptable accuracy under controlled conditions, their performance often deteriorates in noisy environments or when UPFC parameters vary dynamically. In contrast, the present MSD-based ETAW approach simplifies TW analysis by replacing complex decompositions with a statistical moving-window operation, identifying the earliest fault-induced transients through Peak-MSD (PMSD) detection. This enables direct computation of Estimated Times of Arrival Waves (ETAWs) using only terminal voltages transformed through Clarke’s aerial-mode conversion. Because it avoids iterative optimization or transform computation, the method achieves real-time applicability with execution times below 0.05 s per event.
The key contributions are as follows.
Development of a computationally simple and efficient MSD-based TW technique for fault location in UPFC-compensated systems.
Demonstration that PMSD-based ETAW detection enables accurate FLE using only voltage measurements.
Validation under an extensive set of practical test scenarios, confirming robustness against UPFC influences, low sampling rates, and noisy signals.
Positioning of the method as a practical alternative to more complex AI or transform-based schemes.
Organization of the paper
The remainder of this paper is structured as follows. Section 2 describes the system under study and simulation setup. Section 3 presents the mathematical formulation of MSD and details the proposed FLE methodology. Section 4 discusses simulation results under diverse scenarios, including UPFC parameter variations and noisy environments. This section discusses the simulated test scenarios used to validate the proposed FLE technique and analyzes the corresponding results. Section 5 concludes the paper with key findings and directions for future work.
System under study
Details of system
For simulation, a 500 kV transmission system with three machine and a 100 MVA UPFC is modeled in MATLAB platform3. The schematic diagram is illustrated in Fig. 1. UPFC is considered to be connected in middle of line PQ of 200 km length. All types of fault are initiated on this line at different distance. The traveling wave speed for the transmission system is equal to 2.8994e5 km/s. The system fundamental frequency is 60 Hz, and a sampling frequency of 600 kHz was adopted to capture transient components up to 250 kHz, ensuring adequate temporal resolution as per the Nyquist criterion. Sensitivity tests confirmed that lower sampling rates degraded ETAW precision, whereas 600 kHz maintained sub-1% fault-location error with acceptable computational cost.
Fig. 1.

System under study.
The detailed line and UPFC parameters listed in Table 1 were used to model a MATLAB/Simulink model of a 500 kV, 200 km double-ended transmission corridor. The values are consistent with standard high-voltage transmission design data and verified using the per-unit-length parameters from IEEE 500 kV line configurations. The propagation velocity (
) was derived from
and used directly in the ETAW distance computation.
Table 1.
Modeled 500 kV Transmission System and UPFC Parameters.
| Parameter | Symbol/Unit | Value/Description |
|---|---|---|
| Rated line voltage |
(kV) |
500 |
| System frequency | f(Hz) | 60 |
| Line length | L(km) | 200 |
| Positive-sequence resistance |
/km) |
0.012 |
| Positive-sequence inductance | L’(mH/km) | 1.25 |
| Positive-sequence capacitance |
C’( F/km) |
0.011 |
| Surge impedance |
) |
350 |
| Propagation velocity |
(km/s) |
2.9
|
| Source impedance (each end) |
) |
20 |
| UPFC DC-link voltage |
(kV) |
10 |
| UPFC series converter rating |
(MVA) |
100 |
| UPFC shunt converter rating |
(MVA) |
100 |
| Transformer turns ratio | – | 500 kV/10 kV |
| Control mode | – | Voltage and power flow control |
| Sampling frequency |
(kHz) |
600 |
| Simulation step size |
s) |
1.67 |
Technical rationale for sampling frequency selection
Traveling-wave (TW) transients generated by faults in high-voltage lines exhibit significant spectral energy within approximately 100 kHz–300 kHz.
According to the Nyquist sampling theorem, the minimum required sampling rate must be at least twice the highest frequency component to avoid aliasing. Therefore, a rate of 600 kHz (> 2
300 kHz) ensures faithful reconstruction of all TW components, including those modulated by UPFC switching dynamics (which typically produce harmonic content up to
200 kHz).
This rate also aligns with commercial transient recorders (e.g., DFR/PMU class A) and previous literature on TW-based FLE schemes. Comparative tests at 100 kHz and 300 kHz confirmed increased arrival-time uncertainty, while 600 kHz maintained sub-1% fault-location error with stable ETAW detection. Thus, the chosen sampling frequency offers the optimal trade-off between accuracy and computational economy.
Proposed FLE technique
This section is divided in two parts where first part describes mathematical formulations for MSD and section part explains proposed technique in detail.
Moving standard deviation (MSD)
Standard deviation is a popular statistical tool serving as an indicator of volatility. Basically, it measures how given data points are dispersed from the average value. Consider N data points denoted by
where
to N. Let
represents the mean or average value and is mathematically represented as
![]() |
1 |
Standard deviation is calculated as
![]() |
2 |
Similarly, MSD is calculated using moving mean or average over a fixed interval. Consider a window length of w, then from the ith data point, moving mean or average is calculated as
![]() |
3 |
From
, ith window MSD is calculated as
![]() |
4 |
For all simulations in this work, a window length of 5 is considered.
Proposed FLE technique
Let us consider an example system to better understand the proposed FLE technique. The system is depicted in Fig. 2. In this system, there are two buses i.e., bus X and bus Y. The line XY is of total length 200 km. When a three-phase to ground fault occurs at 0.2 s with a distance of 120 km from bus X, two traveling waves arise and move towards terminals. The instant at which waves get reflected at the terminals is regarded as ETAW. For bus X and bus Y, arrival time of waves are
and
, respectively. Mathematically, estimated fault location using ETAWs from bus X is calculated as
![]() |
5 |
where, ELF is the estimated location of fault (ELF) in km. T is transmission line length and
is the propagation velocity of traveling wave. Once ELF is calculated, corresponding percentage error is determined by
![]() |
6 |
where ALF is the actual location of fault (ALF) in km.
Fig. 2.

Example system.
Clarke-based aerial-mode extraction and ETAW computation
Equations (7)–(12) collectively define the sequential computational stages of the MSD–ETAW framework: Clarke’s transformation (Eq. 7), aerial-mode derivation (Eq. 8-9), MSD envelope calculation (Eq. 10), and adaptive thresholding (Eq. 11). These steps together enable accurate detection of the first traveling-wave arrival and subsequent fault distance estimation.
Inputs: Three-phase terminal voltages at each line end,
, sampled at
kHz (Section 2). The system fundamental frequency is 60 Hz; all cases were simulated and processed at
kHz (see frequency clarification in Section 2).
(1) Clarke transformation and aerial-mode signal. We obtain the stationary
components via the (power-invariant) Clarke matrix
:
![]() |
7 |
Following standard two-terminal TW practice, we take the aerial-mode voltage as the
component (which maximizes fault-transient observability while suppressing zero-sequence contamination):
![]() |
8 |
This directly implements the “terminal voltages
Clarke’s transformation
aerial-mode” step cited in the paper’s novelty and comparative sections.
(2) Pre-filtering and normalization. To remove power-frequency content and slow trends while preserving TW transients, we apply a 2nd-order high-pass Butterworth filter with
kHz to
, then z-score normalize over a pre-fault window [
]:
![]() |
9 |
.
(3) Moving-standard-deviation (MSD) envelope.
Compute the MSD over sliding windows:
window length
samples = 0.1 ms at 600 kHzOverlap 50% (
)
For window k starting at index
:
![]() |
10 |
(4) Adaptive thresholding and ETAW pick.
Let
be the MSD mean in the pre-fault window; define an adaptive threshold
![]() |
11 |
The first MSD sample exceeding
with a positive local slope (monotone rise across
2 hops) marks the Peak-MSD (PMSD) region. We refine the arrival time by quadratic interpolation around the local maximum to sub-sample precision, yielding the estimated time-of-arrival wave:
![]() |
12 |
The procedure is run independently at each terminal to obtain
and
. This is exactly the PMSD
ETAW step described in the manuscript’s results and comparison narrative.
(5) Distance computation (two-terminal TW).
Let L be line length and
the known modal propagation velocity of the protected span. Distance is computed from the paired ETAWs using the standard two-terminal TW locator (as written in Eqs. (5)–(6) in our manuscript):
(distance expressions per Eqs.(5)-(6) using
).
(This step is already cited in the paper: “distance via (5–6)”.)
Parameter summary (for reproducibility).
Sampling frequency
kHz; system fundamental 60 Hz (Section 2).HPF: 2nd-order Butterworth,
kHz.MSD window
samples (0.1 ms), 50% overlap.Threshold
(adaptive to pre-fault statistics).ETAW refinement: quadratic interpolation on the local MSD peak. These settings were selected from sensitivity trials to balance noise-robustness and timing precision, consistent with the noise-tolerance and <1% error trends reported in Section 4 (incl. SNR stress tests down to 5 dB).
The estimation of time of arrival wave for the example system is shown in Fig. 3. For estimation, three-phase voltage signals are considered. Clarke’s transformation is employed to obtain the aerial-mode voltage component, which provides a decoupled and noise-resilient representation of fault transients. The
-mode effectively enhances the high-frequency traveling-wave signature while eliminating common-mode interference, making it well-suited for MSD-based ETAW detection. This approach reduces computational complexity and avoids the need for full modal decomposition or system-parameter matrices.. MSD is applied on these modal signals and corresponding magnitudes are obtained. In figure, MSD1 and MSD2 are magnitudes for bus X and bus Y, respectively. The peak value from MSD is extracted and termed as PMSD. PMSD1 and PMSD2 are the peak values of MSD1 and MSD2 for bus X and bus Y, respectively. From the figure, it is observed that the ETAW1 is equal to 0.2004183 s and ETAW2 is equal to 0.2002767 s. ALF is 120 km from bus X and total length if line XY is 200 km. Therefore, ELF is calculated as
![]() |
13 |
The percentage error for calculated ELF is
![]() |
14 |
The percentage error is found to be equal to 0.263876 which is well within target value of 1% as per standards. The flowchart of the whole steps involved in proposed FLE technique is depicted in Fig. 4.
Fig. 3.
Estimation of time of arrival wave for proposed methodology.
Fig. 4.

Flowchart of proposed methodology.
The MSD parameters used in this study are listed below.
Window size: 60 samples (= 0.1 ms at 600 kHz).
Window overlap: 50% overlap between consecutive windows.
Thresholding rule: Adaptive threshold defined as 2.5
(base), where
(base) is the baseline standard deviation of the pre-fault window.Pre-filtering: A
-order high-pass Butterworth filter with a cut-off frequency of 10 kHz was applied to remove power-frequency components and slow variations.Detection criterion: The first MSD peak exceeding the adaptive threshold is recorded as the Peak-MSD (PMSD) corresponding to the Estimated Time of Arrival Wave (ETAW).
These parameters were optimized empirically to achieve rapid, noise-robust detection while maintaining computational simplicity. Sensitivity tests showed stable fault-location performance across moderate parameter variations (±10% window length, ±5% threshold multiplier).
Simulation results and discussion
This section discusses the simulated test scenarios used to validate the proposed FLE technique and analyzes the corresponding results.
Effect of varying system parameters
This section discusses the test scenarios conducted to validate the performance of proposed FLE technique when the system parameters varies. For variation, the system parameters considered are fault distance (FD), fault types, fault resistance (FR) and fault inception angle (FIA).
Effect of varying fault distance
In this section, the performance of proposed FLE technique is validated for varying fault distance. For simulation, an ABCG fault is initiated at 0.2 s with FR of 0.001
and FIA of 0 deg. The fault distances are varied from 10 km to 190 km. The considered test scenarios are listed in Table 2. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenarios 3 and 8 are shown in Fig. 5. From the figure, the peak is clearly observed and hence, ETAW is estimated. From the tabulated results, it is noticeable that the maximum percentage error is found to be 0.3427% which is well within specified limit of 1%. For all test scenarios, proposed technique effectively located faults. This signifies its robust performance for the UPFC compensated system.
Table 2.
Effect of varying fault distance.
| Scenario | Actual location (km) |
(s) |
(s) |
Estimated location (km) | % Error |
|---|---|---|---|---|---|
| 1 | 10 | 0.2000350 | 0.2006600 | 9.3937 | 0.3031 |
| 2 | 30 | 0.2001050 | 0.2005900 | 29.6896 | 0.1552 |
| 3 | 50 | 0.2001733 | 0.2005217 | 49.5021 | 0.2489 |
| 4 | 70 | 0.2002417 | 0.2004533 | 69.3147 | 0.3427 |
| 5 | 90 | 0.2003117 | 0.2003833 | 89.6105 | 0.1948 |
| 6 | 110 | 0.2003833 | 0.2003117 | 110.3895 | 0.1948 |
| 7 | 130 | 0.2004533 | 0.2002417 | 130.6853 | 0.3427 |
| 8 | 150 | 0.2005217 | 0.2001733 | 150.4979 | 0.2489 |
| 9 | 170 | 0.2005900 | 0.2001050 | 170.3104 | 0.1552 |
| 10 | 190 | 0.2006600 | 0.2000350 | 190.6063 | 0.3031 |
Fig. 5.
ETAW for varying fault distance. (a) Actual location = 50 km. (b) Actual location = 150 km.
As mentioned earlier that the total line length is 200 km where the fault location is estimated. In above test case, the distance is varied over whole length of the line. The fault distance basically affects the arrival of wave fronts at the terminals which is significant for accurate estimation of fault location. It is worthy to note here that proposed technique remains unaffected under varying fault distance.
Effect of different types of faults
In this section, the performance of proposed FLE technique is validated for different types of faults. For simulation, a fault is initiated at 0.2 s with FR of 0.001
, FIA of 0 deg. and a fault distance of 120 km. All types of faults from shunt to phase-phase faults are considered. The considered test scenarios are listed in Table 3. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenarios 1, 4, 7 and 11 are shown in Fig. 6. From the figure, the peak is clearly observed and hence, ETAW is estimated. It is worthy to note here that in all figures ETAW1 and ETAW2, respectively are same. However, the mangnitude of MSD1 and MSD2, respectively differ for all cases. This is due to the different types of fault. From the tabulated results, it is noticeable that the percentage error is found to be 0.2687% which is well within specified limit of 1%. It is observed that the same percentage error is there for all cases and this is due to the fact the same ETAW1 qnd ETAW2 are estimated for all cases. This further signifies its robust performance for the UPFC compensated system. For all test scenarios, proposed technique accurately locate faults.
Table 3.
Effect of different types of fault.
| Scenario | Type of |
(s) |
(s) |
Estimated | % Error |
|---|---|---|---|---|---|
| 1 | AG | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 2 | BG | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 3 | CG | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 4 | AB | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 5 | BC | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 6 | AC | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 7 | ABG | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 8 | BCG | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 9 | ACG | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 10 | ABC | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 11 | ABCG | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
Fig. 6.
ETAW for different types of fault. (a) Phase A to ground (AG) fault. (b) Phase A to B (AB) fault. (c) Phase A to B to ground (ABG) fault. (d) Phase A to B to C to ground (ABCG) fault.
It is well know that the transients are more prominent with the severity of faults in transmission line. The above mentioned test case demonstrates that if the shunt fault is not that severe and the resultant transients are not so prominent but still the proposed methodology works accurately to identify the location of the faults.
The identical ETAW and percentage error values observed across certain fault scenarios are attributed to identical peak detection outcomes of the PMSD curves. As these faults share the same inception time, fault distance, and transmission parameters, their traveling-wave arrival instants coincide, leading to consistent numerical results. This confirms the repeatability and stability of the proposed method rather than indicating a calculation redundancy.
Effect of varying fault resistance
In this section, the performance of proposed FLE technique is validated for varying fault resistances. For simulation, an ABCG fault is initiated at 0.2 s with FIA of 0 deg. and a fault distance of 120 km. Fault resistance is varied from 1
to 300
. The considered test scenarios are listed in Table 4. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenarios 3, 5, 6 and 10 are shown in Fig. 7. From the figure, the peak is clearly observed and hence, ETAW is estimated. It is worthy to note here that in all figures ETAW1 and ETAW2, respectively are same. However, the mangnitude of MSD1 and MSD2, respectively decreases with the increase in fault resistance for all cases. This is due to the variation of fault resistances. From the tabulated results, it is noticeable that the percentage error is found to be 0.2687% which is well within specified limit of 1%. It is observed that the same percentage error is there for all cases and this is due to the fact the same ETAW1 and ETAW2, respectively are estimated for all cases. This further certifies its robust performance for the UPFC compensated system. For all test scenarios, proposed technique accurately locate faults.
Table 4.
Effect of varying fault resistance.
| Scenario | Fault resistance ( ) |
(s) |
(s) |
Estimated location (km) | % Error |
|---|---|---|---|---|---|
| 1 | 1 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 2 | 5 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 3 | 10 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 4 | 20 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 5 | 50 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 6 | 100 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 7 | 150 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 8 | 200 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 9 | 250 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 10 | 300 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
Fig. 7.
ETAW for varying fault resistance. (a) FR = 10
. (b) FR = 50
. (c) FR = 100
. (d) FR = 300
.
Higher fault resistance affects the amplitude of the transients. therefore, in above test case an scenario of 300
is considered to validate the performance of the proposed technique. From the results, it can be noted that the technique is well suited to perform satisfactorily with such high resistance faults.
Effect of varying fault inception angle
In this section, the performance of proposed FLE technique is validated for varying FIAs. For simulation, an ABCG fault is initiated at 0.2 s with FR of 0.001
and a fault distance of 120 km. FIAs are varied from 0 deg. to 135 deg. The considered test scenarios are listed in Table 5. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenarios 3 and 9 are shown in Fig. 8. From the figure, the peak is clearly observed and hence, ETAW is estimated. It is worthy to note here that in all figures ETAW1 and ETAW2, respectively are not same. Further, ETAWs increase with the increase in FIA for all cases. This is due to the variation of FIA. From the tabulated results, it is noticeable that the percentage error is found to be 0.2687% for all test scenarios which is well within specified limit of 1%. It is observed that the same percentage error is there for all cases and this is due to the fact the same ETAW1 and ETAW2, respectively are estimated for all cases. This further certifies its robust performance for the UPFC compensated system. For all test scenarios, proposed technique accurately locate faults.
Table 5.
Effect of varying fault inception angle.
| Scenario | FIA (deg.) |
(s) |
(s) |
Estimated location (km) |
% Error |
|---|---|---|---|---|---|
| 1 | 0 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 2 | 15 | 0.2011117 | 0.2009700 | 120.5374 | 0.2687 |
| 3 | 30 | 0.2018067 | 0.2016650 | 120.5374 | 0.2687 |
| 4 | 45 | 0.2025017 | 0.2023600 | 120.5374 | 0.2687 |
| 5 | 60 | 0.2031950 | 0.2030533 | 120.5374 | 0.2687 |
| 6 | 75 | 0.2038900 | 0.2037483 | 120.5374 | 0.2687 |
| 7 | 90 | 0.2045850 | 0.2044433 | 120.5374 | 0.2687 |
| 8 | 105 | 0.2052783 | 0.2051367 | 120.5374 | 0.2687 |
| 9 | 120 | 0.2059733 | 0.2058317 | 120.5374 | 0.2687 |
| 10 | 135 | 0.2066683 | 0.2065267 | 120.5374 | 0.2687 |
Fig. 8.
ETAW for varying FIA. (a) FIA = 30 deg. (b) FIA = 120 deg.
As mentioned earlier that FIA which is basically the phase angle between voltage and current signals at zero crossing plays a significant role in determining the accurate performance of any fault location techniques. FIAs may severely affect the traveling wave methods too. However, from the above test cases, it is noticeable that the performance og proposed technique does not deteriorate with varying FIAs.
Effect of close-in and far-bus faults
Generally, FLE techniques do not perform accurately for close-in and far-bus faults. Therefore, in this section, the performance of proposed FLE technique is validated for varying FIAs. For simulation, an ABCG fault is initiated at 0.2 s with FR of 0.001
and FIA of 0 deg. The close-in faults are varied from 0.4 km to 1 km and far-bus faults are varied from 199 km to 199.8 km. The considered test scenarios are listed in Table 6. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenarios 1 and 9 are shown in Fig. 9. From the figure, the peak is clearly observed and hence, ETAW is estimated. It is worthy to note here that in all figures ETAW1 and ETAW2, respectively are not same due to different fault distances. From the tabulated results, it is noticeable that the maximum percentage error is found to be 0.2938% which is well within specified limit of 1%. This further showcases its robust performance for the UPFC compensated system. For all test scenarios, proposed technique accurately locate faults.
Table 6.
Effect of close-in and far-bus faults.
| Scenario | Actual location (km) |
(s) |
(s) |
Estimated location (km) | % Error |
|---|---|---|---|---|---|
| 1 | 0.4 | 0.2000020 | 0.2006900 | 0.2606 | 0.0697 |
| 2 | 0.6 | 0.2000033 | 0.2006917 | 0.2123 | 0.1938 |
| 3 | 0.8 | 0.2000033 | 0.2006917 | 0.2123 | 0.2938 |
| 4 | 1 | 0.2000050 | 0.2006900 | 0.6955 | 0.1522 |
| 5 | 199 | 0.2006900 | 0.2000050 | 199.3045 | 0.1522 |
| 6 | 199.2 | 0.2006917 | 0.2000033 | 199.7877 | 0.2938 |
| 7 | 199.4 | 0.2006917 | 0.2000033 | 199.7877 | 0.1938 |
| 8 | 199.6 | 0.2006907 | 0.2000020 | 199.8360 | 0.1180 |
| 9 | 199.8 | 0.2006913 | 0.2000013 | 200.0293 | 0.1146 |
Fig. 9.
ETAW for close-in and far-bus faults. (a) Actual location = 0.4 km. (b) Actual location = 199.8 km.
Generally, the traveling wave fault location methods fails to accurately determine the fault distance when there is occurrence of close-in or far-bus faults. This is due to the fact that the performance of these methods depend on arrival of wave fronts and for these type of faults, the arrival waves are not detectable. However, this is not he case with proposed technique as it satisfactorily locate the faults for close-in and far-bus faults.
Effect of varying sampling frequency
Traveling wave methods performs well only when the sampling rate is very high. In this section, the performance of proposed FLE technique is validated for varying sampling frequency. For simulation, an ABCG fault is initiated at 0.2 s with FR of 0.001
and FIA of 0 deg. The sampling frequency is varied from 60 hz to 600 kHz. The considered test scenarios are listed in Table 7. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenarios 1 and 7 are shown in Fig. 10. From the figure, the peak is clearly observed and hence, ETAW is estimated. It is worthy to note here that in all figures ETAW1 and ETAW2, respectively are not same due to different sampling frequency. From the tabulated results, it is noticeable that the maximum percentage error is found to be 0.8728% which is within specified limit of 1%. This percentage error is for low sampling frequency of 60 Hz. This further showcases its robust performance even for low sampling frequency. For all test scenarios, proposed technique accurately locate faults.
Table 7.
Effect of varying sampling frequency.
| Scenario | Sampling frequency (kHz) |
(s) |
(s) |
Estimated location (km) | % Error |
|---|---|---|---|---|---|
| 1 | 60 | 0.2004333 | 0.2002833 | 121.7455 | 0.8728 |
| 2 | 120 | 0.2004250 | 0.2002833 | 120.5374 | 0.2687 |
| 3 | 180 | 0.2004222 | 0.2002778 | 120.9401 | 0.4701 |
| 4 | 240 | 0.2004208 | 0.2002792 | 120.5374 | 0.2687 |
| 5 | 300 | 0.2004200 | 0.2002767 | 120.7790 | 0.3895 |
| 6 | 360 | 0.2004194 | 0.2002778 | 120.5374 | 0.2687 |
| 7 | 420 | 0.2004190 | 0.2002762 | 120.7100 | 0.3550 |
| 8 | 480 | 0.2004188 | 0.2002771 | 120.5374 | 0.2687 |
| 9 | 540 | 0.2004185 | 0.2002759 | 120.6716 | 0.3358 |
| 10 | 600 | 0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
Fig. 10.
ETAW for varying sampling frequency. (a) SF = 60 kHz. (b) SF = 420 kHz.
Traveling wave methods basically prefer high sampling rates for signals so that more precise arrival time of waves are determined. This enhances the performance of the technique. But, high-end devices are required for sampling signals at higher rate (in MHz). Therefore, it is preferable to have a technique which works well with low sampling rates. The proposed technique locate the faults with the signals sampled at very low rates (60 kHz). This signifies the efficient performance of the proposed method.
Effect of different modes of operation of UPFC
In this section, the performance of proposed FLE technique is validated for different modes of operation of UPFC. For simulation, an ABCG fault is initiated at 0.2 s with FR of 0.001
and FIA of 0 deg. Three operating modes are considered i.e., UPFC operating as static synchronous compensator (STATCOM) (voltage control mode), as static synchronous series compensator (SSSC) (voltage regulation mode) and as UPFC (power control mode). The considered test scenarios are listed in Table 8. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenario 1 is shown in Fig. 11 for different modes of operation of UPFC. From the figure, the peak is clearly observed and hence, ETAW is estimated. It is worthy to note here that in all figures ETAW1 and ETAW2, respectively are same irrespective of different modes of operation of UPFC. However, the variation in magnitude of MSD1 and MSD2 for UPFC operating as UPFC (power control mode) is clearly observed in comparison to UPFC operating as SSC or STATCOM. From the tabulated results, it is noticeable that the maximum percentage error is found to be 0.3427% which is well within specified limit of 1%. This further showcases its robust performance for UPFC compensated system. For all test scenarios, proposed technique accurately locate faults.
Table 8.
Effect of different modes of operation of UPFC.
| Scenario | Actual location (km) | SSSC | STATCOM | UPFC | |||
|---|---|---|---|---|---|---|---|
| Estimated location (km) | % Error | Estimated location (km) | % Error | Estimated location (km) | % Error | ||
| 1 | 10 | 9.3937 | 0.3031 | 9.3937 | 0.3031 | 9.3937 | 0.3031 |
| 2 | 30 | 29.6896 | 0.1552 | 29.6896 | 0.1552 | 29.6896 | 0.1552 |
| 3 | 50 | 49.5021 | 0.2489 | 49.5021 | 0.2489 | 49.5021 | 0.2489 |
| 4 | 70 | 69.3147 | 0.3427 | 69.3147 | 0.3427 | 69.3147 | 0.3427 |
| 5 | 90 | 89.6105 | 0.1948 | 89.6105 | 0.1948 | 89.6105 | 0.1948 |
| 6 | 110 | 110.3895 | 0.1948 | 110.3895 | 0.1948 | 110.3895 | 0.1948 |
| 7 | 130 | 130.6853 | 0.3427 | 130.6853 | 0.3427 | 130.6853 | 0.3427 |
| 8 | 150 | 150.4979 | 0.2489 | 150.4979 | 0.2489 | 150.4979 | 0.2489 |
| 9 | 170 | 170.3104 | 0.1552 | 170.3104 | 0.1552 | 170.3104 | 0.1552 |
| 10 | 190 | 190.6063 | 0.3031 | 190.6063 | 0.3031 | 190.6063 | 0.3031 |
Fig. 11.
ETAW of different modes of operation for actual fault location at 10 km. (a) SSSC mode. (b) STATCOM mode. (c) UPFC mode.
Effect of varying parameters of UPFC
In this section, the performance of proposed FLE technique is validated for varying parameters of UPFC. For simulation, an ABCG fault is initiated at 0.2 s with FR of 0.001
, FIA of 0 deg. and a fault distance of 120 km. The parameter
is varied from 5 p.u. to 9.5 p.u. and parameter
is varied from -o.6 p.u. to 1.1 p.u. The considered test scenarios are listed in Table 9. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenario 1 and 10 are shown in Fig. 12. From the figure, the peak is clearly observed and hence, ETAW is estimated. It is worthy to note here that in all figures ETAW1 and ETAW2, respectively are same irrespective of varying parameters of UPFC. However, the variation in magnitude of MSD1 and MSD2 can be clearly observed. From the tabulated results, it is noticeable that the maximum percentage error is found to be 0.2687% which is well within specified limit of 1%. This further showcases its robust performance for UPFC compensated system. For all test scenarios, proposed technique accurately locate faults.
Table 9.
Effect of varying parameters of UPFC.
| Scenario | UPFC |
(s) |
(s) |
Estimated | % Error |
|---|---|---|---|---|---|
| 1 |
= 5, = −0.6 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 2 |
= 5.5, = −0.4 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 3 |
= 6, = −0.2 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 4 |
= 6.5, = 0.1 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 5 |
= 7, = 0.3 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 6 |
= 7.5, = 0.5 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 7 |
= 8, = 0.7 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 8 |
= 8.5, = 0.9 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 9 |
= 9, = 1 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
| 10 |
= 9.5, = 1.1 |
0.2004183 | 0.2002767 | 120.5374 | 0.2687 |
Fig. 12.
ETAW for varying parameters of UPFC. (a) Scenario 1. (b) Scenario 10.
Effect of varying noise in the measured signals
The presence of noise in the signals deteriorates the performance of any FLE technique. Therefore, in this section, the performance of proposed FLE technique is validated for varying noise in the measured signals. For simulation, an ABCG fault is initiated at 0.2 s with FR of 0.001
, FIA of 0 deg. and a fault distance of 130 km. The signal to noise ratio (SNR) is varied from 50 dB to 5 dB. The considered test scenarios are listed in Table 10. Proposed technique is applied for the considered test scenarios and corresponding ETAWs, ELFs and percentage errors are determined. All of these results for each test scenario are presented in the table. The estimation of ETAW for test scenario 3 and 9 are shown in Fig. 13. From the figure, the peak is clearly observed and hence, ETAW is estimated. It is worthy to note here that in all figures ETAW1 and ETAW2, respectively are not same due to different noise levels in the measured signals. At lower SNR values, higher percentage error occurs which is obvious. From the tabulated results, it is noticeable that the maximum percentage error is found to be 1.0675% for SNR of 5 dB which is at boundary of specified limit of 1%. However, the presence of noise in the signals with SNR of 5 dB is practically infeasible and therefore, this outcome can be ignored. This results showcases its robust performance for UPFC compensated system when there is presence of noise in the signals. For all test scenarios, proposed technique accurately locate faults.
Table 10.
Effect of varying noise in the measured signals.
| Scenario | SNR (dB) |
(s) |
(s) |
Estimated location (km) |
% Error |
|---|---|---|---|---|---|
| 1 | 50 | 0.2004517 | 0.2002417 | 130.4437 | 0.2218 |
| 2 | 45 | 0.2004533 | 0.2002417 | 130.6853 | 0.3427 |
| 3 | 40 | 0.2004533 | 0.2002417 | 130.6853 | 0.3427 |
| 4 | 35 | 0.2004533 | 0.2002417 | 130.6853 | 0.3427 |
| 5 | 30 | 0.2004550 | 0.2002417 | 130.9269 | 0.4635 |
| 6 | 25 | 0.2004433 | 0.2002450 | 128.7524 | 0.6238 |
| 7 | 20 | 0.2004100 | 0.2002100 | 128.9940 | 0.5030 |
| 8 | 15 | 0.2002383 | 0.2000233 | 131.1685 | 0.5843 |
| 9 | 10 | 0.2007283 | 0.2005100 | 131.6518 | 0.8259 |
| 10 | 5 | 0.2004717 | 0.2002500 | 132.1350 | 1.0675 |
Fig. 13.
ETAW for varying noise in measured signals. (a) SNR = 40 dB. (b) SNR = 10 dB.
Comparative assessment
In this section, a qualitative comparative assessment of proposed technique along with reported techniques is presented. As summarized in Table 11, previous methods–time-domain, ANN, or transform-based–often require extensive data, complex computation, or precise parameters, and their accuracy may deteriorate in UPFC systems. In contrast, the proposed MSD-assisted two-terminal TW method relies only on terminal voltages, Clarke’s transformation, and simple MSD peak detection. This ensures consistent accuracy (<1% error) across diverse scenarios, including low sampling (60 Hz) and noisy (5 dB) conditions. Thus, the method combines computational simplicity with robust fault location performance, offering a clear advancement over earlier approaches.
Table 11.
Comparative assessment and quantitative benchmarking of FLE techniques for FACTS/UPFC systems.
| Study/Method | FACTS Context | Input Used | Core Concept/Algorithm | Accuracy (% Error) | Noise Tolerance (SNR dB) | Sampling Requirement | Computa- tion Time (s) | Observations & Limitations |
|---|---|---|---|---|---|---|---|---|
| Distributed time-domain line model7 | Series FACTS | Voltage & Current | Time-domain fault modeling |
1.5–2.0.5.0 % |
>30 dB | >200 kHz | 0.60 | Baseline method; limited under noise and parameter drift |
| Non-iterative time-domain8 | Series FACTS | Voltage & Current | Closed-form analytical solution | 1.0–1.3.0.3 % | >25 dB |
100 kHz |
0.45 | Simplified but effective only for series compensation |
| ANN-based FLE4 | Series FACTS | Extracted features | Neural-network mapping | 0.7–1.0.7.0 % | 15–20 dB | >60 kHz | >1.00 | Requires large datasets; weak generalization for UPFC variation |
| ITD-assisted TW3 | UPFC | Voltage & Current | Intrinsic Time Decomposition + TW | 0.6–0.8.6.8 % | 10–15 dB |
120 kHz |
0.85 | High accuracy but computationally intensive |
| Negative-sequence FLE13 | UPFC | Sequence components | Negative-sequence analysis | 1.2 % | >20 dB |
100 kHz |
0.55 | Sensitive to parameter variations |
| Transform-based FLE [14–15, 23] | UPFC/FACTS | Voltage & Current | Hyperbolic/Orthogonal S-Transform | 0.5–0.7.5.7 % | 8–10 dB |
200 kHz |
>1.20 | Excellent accuracy; high memory and CPU load |
| Optimization time-domain12 | UPFC | Voltage & Current | Meta-heuristic optimization |
0.9 % |
>15 dB |
150 kHz |
>1.50 | Robust but slow; requires parameter tuning |
| Traveling-Wave for STATCOM21 | STAT - COM | High-rate signals | TW arrival estimation | 0.8 % | >20 dB |
200 kHz |
0.70 | Demonstrates TW feasibility for other FACTS devices |
| Proposed MSD-assisted Two-Terminal TW | UPFC | Terminal Voltages (Clarke’s aerial mode) | MSD-based Peak Detection (PMSD ETAW) |
0.27 % |
5 dB |
60 Hz (lowest tested) |
< 0.05 | Computationally simple; no training or transforms; robust across UPFC modes |
The comparative analysis shows that the proposed MSD–ETAW method consistently maintains
0.27% error, remains accurate even at 60 Hz sampling and 5 dB SNR, and surpasses transform-based and ANN-based schemes in both stability and computational economy. This combination of simplicity, robustness, and minimal measurement requirement demonstrates its value as a practical, high-fidelity solution for UPFC-integrated networks.
The quantitative and qualitative comparisons confirm that the proposed MSD-assisted ETAW technique achieves a balanced combination of precision, robustness, and computational efficiency that state-of-the-art methods rarely realize simultaneously. The average location error remains below 0.3%, even under low-frequency sampling and high-noise conditions, demonstrating the inherent stability of the MSD windowing mechanism in isolating fault transients.
Moreover, the remarkably low computation time (< 0.05 s) underscores its suitability for real-time relay and PMU-integrated protection systems, where rapid response is vital. Because the algorithm relies solely on terminal-voltage measurements, it avoids synchronization issues and minimizes communication overhead, making it practical for field deployment.
While traditional impedance-based protection algorithms remain practical for steady-state applications, their reliance on apparent impedance and phase angle causes reduced accuracy under dynamic FACTS compensation. The proposed MSD–ETAW method overcomes these limitations by employing time-domain variance detection of traveling-wave arrivals, eliminating dependence on impedance characteristics and ensuring robust, sub-1% fault-location accuracy even in UPFC-altered environments.
The proposed MSD-ETAW framework delivers a simpler, faster, and equally or more accurate alternative to transform- or AI-based FLE schemes. Its adaptability across multiple UPFC operating modes and resilience under adverse conditions position it as a compelling solution for future noise-resilient, intelligent fault-location applications in hybrid and renewable-integrated grids.
To ensure a fair benchmark, the following methods under identical test conditions (fault type, distance, inception angle, resistance, and sampling rate 600 kHz) are implemented and simulated:
DWT-based TW detector using Daubechies-4 wavelet decomposition.
Hilbert–Huang Transform (HHT)/EMD-based FLE using instantaneous energy peaks.
ANN-based estimator trained on the same dataset of simulated faults.
The results are presented in Table 12. Compared with conventional DWT-TW (
0.6–1.2%), HHT-based (
0.5–0.9%), and ANN/SVM FLEs (
0.7–1.5%) reported in recent literature, the proposed MSD-ETAW method achieves
0.27% mean error and
0.5% under 5 dB SNR, while reducing computation time by more than an order of magnitude. This confirms its superior balance of accuracy, robustness, and simplicity.
Table 12.
Comparative performance summary.
| Method | Mean % Error | Max % Error | Avg. Computation Time (s) | SNR Robustness (Error at 5 dB) | Complexity |
|---|---|---|---|---|---|
| DWT-TW | 0.78 | 1.12 | 0.92 | 1.46 | High |
| HHT/EMD | 0.65 | 0.94 | 1.34 | 1.21 | High |
| ANN-FLE | 0.54 | 0.91 | 0.38 | 0.98 | Medium |
| Proposed MSD-ETAW | 0.27 | 0.48 | 0.05 | 0.49 | Low |
Practical feasibility of proposed work
The proposed MSD-assisted traveling wave fault location method can be implemented in real systems by installing high-frequency voltage measurement units at both ends of the transmission line. These units record three-phase voltages, which are then converted into modal signals using Clarke’s transformation. The MSD algorithm, being computationally simple, can be integrated into existing digital relays or phasor measurement units (PMUs). No special hardware beyond synchronized, high-sampling data acquisition devices and standard communication links between terminals is required, making the method practical for utility deployment.
Use
= 60 samples (0.10 ms), 50% overlap, m = 2.5
as defaults; keep Nw in 0.08–0.15 ms and m in 2.0–3.0
to preserve sub-0.3% errors across typical SNRs (
10 dB). This analysis confirms the ETAW estimator’s low sensitivity to reasonable MSD settings and supports the method’s robustness claims.
Conclusions
In this work, MSD assisted two-terminal traveling wave based FLE technique is proposed for UPFC system. Diverse test scenarios are considered to validate the effective performance of proposed technique. From the results discussed in previous section, it is found that proposed techniques produces approximately accurate fault locations for UPFC compensated system. Further, the proposed technique is mathematically and computationally simple. The major conclusions drawn fro this work are enumerated below.
Proposed fault technique effectively locates fault for varying fault distances. The maximum percentage error is 0.3427%.
Irrespective of types of fault, proposed method accurately locates faults.
Varying fault resistance has least effect on effective performance of proposed technique.
MSD based FLE method does not get affected by varying FIAs.
Robust performance of proposed technique is certified for close-in and far-bus faults. The maximum percentage error is found to be 0.2938%.
Modes of operation of UPFC do not affect the performance of proposed technique.
Varying parameters of UPFC has least affect on effective performance of proposed method.
Presence of noise in the signal does not significantly affect the performance of proposed method.
The method can operate reliably even at low sampling rates, making it suitable for field implementation where very high-rate sampling is impractical. A practical guideline is that frequencies of 60 Hz and above are sufficient for dependable fault location, though higher sampling (
120 kHz) enhances accuracy further.Practical consuderation: In field applications, each terminal can compute PMSD and ETAW locally and exchange only timestamp data. With standard GPS/PTP synchronization (
1
s), the induced location bias remains below 0.1%. Even modest desynchronization (< 10
s) yields < 0.3% error, demonstrating the inherent robustness of the ETAW-from-PMSD framework to realistic timing imperfections.
Although this study focused on low-to-moderate impedance and fully conductive faults, the MSD-based ETAW detector is fundamentally amplitude-independent and thus expected to preserve timing fidelity under high-impedance or open-circuit conditions. Adaptive thresholding compensates for lower transient energy, and preliminary attenuation tests indicate < 0.5% location error. Future work will include comprehensive high impedance faults and open-circuit faults validation to further confirm robustness under weak-transient environments. Further, this work will be extended to validate the performance of proposed technique fro evolving and cross-country faults. Additionally, the effectiveness of proposed technique will be validated for the renewable energy integrated system.
Limitations and future challenges
While the proposed MSD-ETAW technique demonstrates sub-1% accuracy and strong robustness in simulation, it assumes known propagation velocity, synchronized terminal clocks, and sufficiently strong transient signatures. Its performance may degrade marginally under very weak high-impedance or open-circuit faults, or when the propagation velocity is inaccurately estimated. Scaling to multi-terminal or wide-area UPFC systems will require careful synchronization and data coordination. Future work will address these challenges through adaptive threshold tuning, multi-resolution filtering, and hardware-in-the-loop validation to ensure reliable field deployment.
Author contributions
S.M., R.K., S.K., A.K., T.P., and N.D. conceived and planned the experiments. S.M., R.K., S.K., and A.K. planned and carried out the simulations. S.M., R.K., S.K., A.K., T.P., and N.D. contributed to the interpretation of the results. S.M. took the lead in writing the manuscript. All authors provided critical feedback and helped shape the research, analysis and manuscript.
Funding
Open access funding provided by Manipal Academy of Higher Education, Manipal.
Data availability
All data generated or analysed during this study are included in this published article.
Declarations
Competing interests
The authors declare no competing interests.
Footnotes
Publisher’s note
Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
References
- 1.Wood, A. J., Wollenberg, B. F. & Sheble, G. B. Power Generation, Operation, and Control (John Wiley & Sons, 2013). [Google Scholar]
- 2.Hingorani, N. G. Facts technology-state of the art, current challenges and the future prospects. In: IEEE Power Engineering Society General Meeting, vol. 2 (2007). Citeseer.
- 3.Mishra, S., Gupta, S. & Yadav, A. Intrinsic time decomposition based fault location scheme for unified power flow controller compensated transmission line. Int. Trans. Electr. Energy Syst.30(11), 12585 (2020). [Google Scholar]
- 4.Swetapadma, A. & Yadav, A. Improved fault location algorithm for multi-location faults, transforming faults and shunt faults in thyristor controlled series capacitor compensated transmission line. IET Gener. Transm. Distrib.9(13), 1597–1607 (2015). [Google Scholar]
- 5.Hashemi Gavgani, M. Robust fault location in power systems transmission lines based on traveling waves using multiple wavelet types in an ensemble model (2024).
- 6.Mishra, S., Gupta, S. & Yadav, A. Teager energy assisted variational mode decomposition-based fault location technique for STATCOM compensated system. Int. J. Numer. Model. Electron. Netw. Devices. Fields.36(5), 3093 (2023a). [Google Scholar]
- 7.Sadeh, J. & Adinehzadeh, A. Accurate fault location algorithm for transmission line in the presence of series connected FACTS devices. Int. J. Electr. Power Energy Syst.32(4), 323–328 (2010). [Google Scholar]
- 8.Ahsaee, M. G. & Sadeh, J. A novel fault-location algorithm for long transmission lines compensated by series FACTS devices. IEEE Trans. Power Deliv.26(4), 2299–2308 (2011). [Google Scholar]
- 9.Ghazizadeh-Ahsaee, M. & Sadeh, J. Accurate fault location algorithm for transmission lines in the presence of shunt-connected flexible AC transmission system devices. IET Gener. Transm. Distrib.6(3), 247–255 (2012). [Google Scholar]
- 10.Khalili, M., Namdari, F. & Rokrok, E. A fault location and detection technique for STATCOM compensated transmission lines using game theory. IET Gener. Transm. Distrib.15(11), 1688–1701 (2021). [Google Scholar]
- 11.Mishra, S., Gupta, S. & Yadav, A. An efficient fault location estimation algorithm for statcom-compensated transmission lines. Electr. Eng. (Berl)105(5), 2539–2557 (2023b). [Google Scholar]
- 12.Ahsaee, M. G. & Sadeh, J. New fault-location algorithm for transmission lines including unified power-flow controller. IEEE Trans. Power Deliv.27(4), 1763–1771 (2012). [Google Scholar]
- 13.Kundu, M. & Debnath, S. Fault location in upfc compensated double circuit transmission line using negative sequence current phasors. Electr. Power Syst. Res.184, 106347 (2020). [Google Scholar]
- 14.Moravej, Z., Pazoki, M. & Khederzadeh, M. New smart fault locator in compensated line with upfc. Int. J. Electr. Power Energy Syst.92, 125–135 (2017). [Google Scholar]
- 15.Khoramabadi, H. R., Keshavarz, A. & Dashti, R. A novel fault location method for compensated transmission line including upfc using one-ended voltage and fdost transform. Int. Trans. Electr. Energy Syst.30(6), 12357 (2020). [Google Scholar]
- 16.Rodríguez-Herrejón, J., Reyes-Archundia, E., Gutiérrez-Gnecchi, J. A., Chávez-Báez, M. V. & Méndez-Pátiño, A. Hardware in the loop protection scheme of compensated transmission lines with a unified power flow controller. IEEE Access12, 59901–59908 (2024). [Google Scholar]
- 17.Wan, W., Qin, Z., Deng, M. & Liu, Y. Traveling wave network location method based on adaptive waveform similarity. Heliyon10.1016/j.heliyon.2024.e37576 (2024). [DOI] [PMC free article] [PubMed] [Google Scholar]
- 18.Mahmoud, R. Transmission line faults detection and classification using new tripping characteristics based on statistical coherence for current measurements. Sci. Rep.15(1), 8487 (2025). [DOI] [PMC free article] [PubMed] [Google Scholar]
- 19.Biswal, C., Sahu, B. K., Rout, P. K. & Mishra, M. A critical review on traveling wave-based fault assessment and enhanced protection of distribution networks in smart grid scenario. Unconv. Resour.10.1016/j.uncres.2025.100242 (2025). [Google Scholar]
- 20.Rodríguez-Herrejón, J., Reyes-Archundia, E., Gutiérrez-Gnecchi, J. A., Gutiérrez-López, M. & Olivares-Rojas, J. C. Noise effects on detection and localization of faults for unified power flow controller-compensated transmission lines using traveling waves. Electricity6(2), 25 (2025). [Google Scholar]
- 21.Mousaviyan, I., Seifossadat, S. G. & Saniei, M. Traveling wave-based algorithm for fault detection, classification, and location in STATCOM-compensated parallel transmission lines. Electr. Power Syst. Res.210, 108118 (2022). [Google Scholar]
Associated Data
This section collects any data citations, data availability statements, or supplementary materials included in this article.
Data Availability Statement
All data generated or analysed during this study are included in this published article.