Deposition of manganese in a drinking water distribution system.

L I Sly 1, M C Hodgkinson 1, V Arunpairojana 1
PMCID: PMC183397  PMID: 2317040

Abstract

The deposition of manganese in a water distribution system with manganese-related "dirty water" problems was studied over a 1-year period. Four monitoring laboratories with Robbins biofilm sampling devices fitted to the water mains were used to correlate the relationship among manganese deposition, the level of manganese in the water, and the chlorination conditions. Manganese deposition occurred by both chemical and microbial processes. Chemical deposition occurred when Mn(II) not removed during water treatment penetrated the filters and entered the distribution system, where it was oxidized by chlorine and chlorine dioxide used for disinfection. Microbial deposition occurred in areas with insufficient chlorination to control the growth of manganese-depositing biofilm. At 0.05 mg of Mn(II) per liter, the chemical deposition rate was much greater than microbial deposition. Significant deposition occurred at 0.03 mg of manganese per liter, and dirty water complaints were not eliminated until manganese levels were continuously less than 0.02 mg/liter and chlorination levels were greater than 0.2 mg/liter. A guideline level of 0.01 mg of manganese per liter is recommended.

Full text

PDF
628

Images in this article

Selected References

These references are in PubMed. This may not be the complete list of references from this article.

  1. McCoy W. F., Bryers J. D., Robbins J., Costerton J. W. Observations of fouling biofilm formation. Can J Microbiol. 1981 Sep;27(9):910–917. doi: 10.1139/m81-143. [DOI] [PubMed] [Google Scholar]
  2. SCHWEISFURTH R., MERTES R. [Microbiological and chemical research on the formation and control of manganese sludge sedimentation in a pressure pipe-line for dam water]. Arch Hyg Bakteriol. 1962 Nov;146:401–417. [PubMed] [Google Scholar]
  3. Tyler P. A., Marshall K. C. Microbial oxidation of manganese in hydro-electric pipelines. Antonie Van Leeuwenhoek. 1967;33(2):171–183. doi: 10.1007/BF02045548. [DOI] [PubMed] [Google Scholar]

Articles from Applied and Environmental Microbiology are provided here courtesy of American Society for Microbiology (ASM)

RESOURCES