The number of bacteria in air, before filtration with five different easily available filters in the low positive-pressure type of airconditioning system of the Winnipeg General Hospital, was between 3 and 4/cu. ft., and after filtration between 1 and 2/cu. ft. with all types of filters. Cl. welchii contributed about 1% and Staph. pyogenes about 0.1% of this total. Sampling the exhaust air from an operating room during an operation showed that the bacterial count fluctuated with the degree of activity in the room and was from two to 10 times as high as in the air delivered to the room.

Atlhough every reasonable attempt should be made to diminish the bacterial count of air in hospitals, if much energy and money is to be spent it would probably be wiser to investigate sources of hospital infection other than the type of air-conditioning system described in this report.

Full text

PDF
416

Selected References

These references are in PubMed. This may not be the complete list of references from this article.

  1. BARBER M., KUPER S. W. A. Identification of Staphylococcus pyogenes by the phosphatase reaction. J Pathol Bacteriol. 1951 Jan;63(1):65–68. doi: 10.1002/path.1700630108. [DOI] [PubMed] [Google Scholar]
  2. LOWBURY E. J., LILLY H. A. A selective plate medium for Cl. welchii. J Pathol Bacteriol. 1955 Jul;70(1):105–109. doi: 10.1002/path.1700700110. [DOI] [PubMed] [Google Scholar]

Articles from Canadian Medical Association Journal are provided here courtesy of Canadian Medical Association

RESOURCES