Abstract
A study was conducted to determine the bactericidal effects of ozone and hydrogen peroxide relative to that of free chlorine on Legionella pneumophila serogroup 1. In laboratory batch-type experiments, organisms seeded at various densities were exposed to different concentrations of these biocides in demand-free buffers. Bactericidal effects were measured by determining the ability of L. pneumophila to grow on buffered charcoal-yeast extract agar supplemented with alpha-ketoglutarate. Ozone was the most potent of the three biocides, with a greater than 99% kill of L. pneumophila occurring during a 5-min exposure to 0.10 to 0.30 micrograms of O3 per ml. The bactericidal action of O3 was not markedly affected by changes in pH or temperature. Concentrations of 0.30 and 0.40 micrograms of free chlorine per ml killed 99% of the L. pneumophila after 30- and 5-min exposures, respectively. A 30-min exposure to 1,000 micrograms of H2O2 per ml was required to effect a 99% reduction of the viable L. pneumophila population. However, no viable L. pneumophila could be detected after a 24-h exposure to 100 or 300 micrograms of H2O2 per ml. Attempts were made to correlate the biocidal effects of O3 and H2O2 with the oxidation of L. pneumophila fatty acids. These tests indicated that certain biocidal concentrations of O3 and H2O2 resulted in a loss or severe reduction of L. pneumophila unsaturated fatty acids.
Full text
PDF






Selected References
These references are in PubMed. This may not be the complete list of references from this article.
- Broadwater W. T., Hoehn R. C., King P. H. Sensitivity of three selected bacterial species to ozone. Appl Microbiol. 1973 Sep;26(3):391–393. doi: 10.1128/am.26.3.391-393.1973. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Cherry W. B., Pittman B., Harris P. P., Hebert G. A., Thomason B. M., Thacker L., Weaver R. E. Detection of Legionnaires disease bacteria by direct immunofluorescent staining. J Clin Microbiol. 1978 Sep;8(3):329–338. doi: 10.1128/jcm.8.3.329-338.1978. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Cordes L. G., Fraser D. W., Skaliy P., Perlino C. A., Elsea W. R., Mallison G. F., Hayes P. S. Legionnaires' disease outbreak at an Atlanta, Georgia, Country Club: evidence for spread from an evaporative condenser. Am J Epidemiol. 1980 Apr;111(4):425–431. doi: 10.1093/oxfordjournals.aje.a112917. [DOI] [PubMed] [Google Scholar]
- Dondero T. J., Jr, Rendtorff R. C., Mallison G. F., Weeks R. M., Levy J. S., Wong E. W., Schaffner W. An outbreak of Legionnaires' disease associated with a contaminated air-conditioning cooling tower. N Engl J Med. 1980 Feb 14;302(7):365–370. doi: 10.1056/NEJM198002143020703. [DOI] [PubMed] [Google Scholar]
- Edelstein P. H., Whittaker R. E., Kreiling R. L., Howell C. L. Efficacy of ozone in eradication of Legionella pneumophila from hospital plumbing fixtures. Appl Environ Microbiol. 1982 Dec;44(6):1330–1333. doi: 10.1128/aem.44.6.1330-1333.1982. [DOI] [PMC free article] [PubMed] [Google Scholar]
- England A. C., 3rd, Fraser D. W., Mallison G. F., Mackel D. C., Skaliy P., Gorman G. W. Failure of Legionella pneumophila sensitivities to predict culture results from disinfectant-treated air-conditioning cooling towers. Appl Environ Microbiol. 1982 Jan;43(1):240–244. doi: 10.1128/aem.43.1.240-244.1982. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Fliermans C. B., Cherry W. B., Orrison L. H., Smith S. J., Tison D. L., Pope D. H. Ecological distribution of Legionella pneumophila. Appl Environ Microbiol. 1981 Jan;41(1):9–16. doi: 10.1128/aem.41.1.9-16.1981. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Fliermans C. B., Cherry W. B., Orrison L. H., Thacker L. Isolation of Legionella pneumophila from nonepidemic-related aquatic habitats. Appl Environ Microbiol. 1979 Jun;37(6):1239–1242. doi: 10.1128/aem.37.6.1239-1242.1979. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Fliermans C. B., Harvey R. S. Effectiveness of 1-bromo-3-chloro-5,5-dimethylhydantoin against Legionella pneumophila in a cooling tower. Appl Environ Microbiol. 1984 Jun;47(6):1307–1310. doi: 10.1128/aem.47.6.1307-1310.1984. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Fraser D. W., Deubner D. C., Hill D. L., Gilliam D. K. Nonpneumonic, short-incubation-period Legionellosis (Pontiac fever) in men who cleaned a steam turbine condenser. Science. 1979 Aug 17;205(4407):690–691. doi: 10.1126/science.462175. [DOI] [PubMed] [Google Scholar]
- Haley C. E., Cohen M. L., Halter J., Meyer R. D. Nosocomial Legionnaires' disease: a continuing common-source epidemic at Wadsworth Medical Center. Ann Intern Med. 1979 Apr;90(4):583–586. doi: 10.7326/0003-4819-90-4-583. [DOI] [PubMed] [Google Scholar]
- Kaufmann A. F., McDade J. E., Patton C. M., Bennett J. V., Skaliy P., Feeley J. C., Anderson D. C., Potter M. E., Newhouse V. F., Gregg M. B. Pontiac fever: isolation of the etiologic agent (Legionella pneumophilia) and demonstration of its mode of transmission. Am J Epidemiol. 1981 Sep;114(3):337–347. doi: 10.1093/oxfordjournals.aje.a113200. [DOI] [PubMed] [Google Scholar]
- Klaucke D. N., Vogt R. L., LaRue D., Witherell L. E., Orciari L. A., Spitalny K. C., Pelletier R., Cherry W. B., Novick L. F. Legionnaires' disease: the epidemiology of two outbreaks in Burlington, Vermont, 1980. Am J Epidemiol. 1984 Mar;119(3):382–391. doi: 10.1093/oxfordjournals.aje.a113756. [DOI] [PubMed] [Google Scholar]
- Kuchta J. M., States S. J., McGlaughlin J. E., Overmeyer J. H., Wadowsky R. M., McNamara A. M., Wolford R. S., Yee R. B. Enhanced chlorine resistance of tap water-adapted Legionella pneumophila as compared with agar medium-passaged strains. Appl Environ Microbiol. 1985 Jul;50(1):21–26. doi: 10.1128/aem.50.1.21-26.1985. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Kuchta J. M., States S. J., McNamara A. M., Wadowsky R. M., Yee R. B. Susceptibility of Legionella pneumophila to chlorine in tap water. Appl Environ Microbiol. 1983 Nov;46(5):1134–1139. doi: 10.1128/aem.46.5.1134-1139.1983. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Kurtz J. B., Bartlett C. L., Newton U. A., White R. A., Jones N. L. Legionella pneumophila in cooling water systems. Report of a survey of cooling towers in London and a pilot trial of selected biocides. J Hyg (Lond) 1982 Jun;88(3):369–381. doi: 10.1017/s0022172400070248. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Locksley R. M., Jacobs R. F., Wilson C. B., Weaver W. M., Klebanoff S. J. Susceptibility of Legionella pneumophila to oxygen-dependent microbicidal systems. J Immunol. 1982 Nov;129(5):2192–2197. [PubMed] [Google Scholar]
- Macfarlane J. T., Finch R. G., Ward M. J., Macrae A. D. Hospital study of adult community-acquired pneumonia. Lancet. 1982 Jul 31;2(8292):255–258. doi: 10.1016/s0140-6736(82)90334-8. [DOI] [PubMed] [Google Scholar]
- Menzel D. B. Oxidation of biologically active reducing substances by ozone. Arch Environ Health. 1971 Aug;23(2):149–153. doi: 10.1080/00039896.1971.10665973. [DOI] [PubMed] [Google Scholar]
- Morris G. K., Patton C. M., Feeley J. C., Johnson S. E., Gorman G., Martin W. T., Skaliy P., Mallison G. F., Politi B. D., Mackel D. C. Isolation of the Legionnaires' disease bacterium from environmental samples. Ann Intern Med. 1979 Apr;90(4):664–666. doi: 10.7326/0003-4819-90-4-664. [DOI] [PubMed] [Google Scholar]
- Orrison L. H., Cherry W. B., Milan D. Isolation of Legionella pneumophilia from cooling tower water by filtration. Appl Environ Microbiol. 1981 May;41(5):1202–1205. doi: 10.1128/aem.41.5.1202-1205.1981. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Roehm J. N., Hadley J. G., Menzel D. B. Oxidation of unsaturated fatty acids by ozone and nitrogen dioxide. A common mechanism of action. Arch Environ Health. 1971 Aug;23(2):142–148. doi: 10.1080/00039896.1971.10665972. [DOI] [PubMed] [Google Scholar]
- Stout J. E., Yu V. L., Best M. G. Ecology of Legionella pneumophila within water distribution systems. Appl Environ Microbiol. 1985 Jan;49(1):221–228. doi: 10.1128/aem.49.1.221-228.1985. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Taylor R. J., Schwentker F. N., Hakala T. R. Opportunistic lung infections in renal transplant patients: a comparison of Pittsburgh pneumonia agent and legionnaires' disease. J Urol. 1981 Mar;125(3):289–292. doi: 10.1016/s0022-5347(17)55013-2. [DOI] [PubMed] [Google Scholar]
- Wadowsky R. M., Yee R. B., Mezmar L., Wing E. J., Dowling J. N. Hot water systems as sources of Legionella pneumophila in hospital and nonhospital plumbing fixtures. Appl Environ Microbiol. 1982 May;43(5):1104–1110. doi: 10.1128/aem.43.5.1104-1110.1982. [DOI] [PMC free article] [PubMed] [Google Scholar]
- Wang W. L., Blaser M. J., Cravens J., Johnson M. A. Growth, survival, and resistance of the Legionnaires' disease bacterium. Ann Intern Med. 1979 Apr;90(4):614–618. doi: 10.7326/0003-4819-90-4-614. [DOI] [PubMed] [Google Scholar]
- Yoshpe-Purer Y., Eylan E. Disinfection of water by hydrogen peroxide. Health Lab Sci. 1968 Oct;5(4):233–238. [PubMed] [Google Scholar]