Abstract
The inclined air-curtain technology was applied to build an inclined air-curtain range hood. A draft generator was applied to affect the inclined air-curtain range hood in three directions: lateral (θ=0°), oblique (θ=45°), and front (θ=90°). The three suction flow rates provided by the inclined air-curtain range hood were 10.1, 10.9, and 12.6 m3/min. The laser-assisted flow visualization technique and the tracer-gas test method were used to investigate the performance of the range hood under the influence of a draft. The results show that the inclined air-curtain range hood has a strong ability to resist the negative effect of a front draft until the draft velocity is greater than 0.5 m/s. The oblique draft affected the containment ability of the inclined air-curtain range hood when the draft velocity was larger than 0.3 m/s. When the lateral draft effect was applied, the capture efficiency of the inclined air-curtain range hood decreased quickly in the draft velocity from 0.2 m/s to 0.3 m/s. However, the capture efficiencies of the inclined air-curtain range hood under the influence of the front draft were higher than those under the influence of the oblique draft from 0.3 m/s to 0.5 m/s.
Keywords: Kitchen ventilation, Inclined air-curtain, Flow visualization, Draft effect, Capture efficiency
Introduction
Many recent studies have focused on indoor air quality issues in public and residential kitchens1,2,3,4). Cooking and cooking burners can emit combustion products, pollutants, and excess moisture that may adversely impact indoor air quality in residences. Especially, frying, grilling, stove use, toasting, etc., can increase the indoor sub-micrometer particle concentration levels and PM2.5 concentrations by more than 5 to 90 times higher than normal5). Previous studies reported that sub-micrometer particles and chemical compounds generated by cooking or cooking burners resulted in respiratory system problems6, 7). Ventilation systems play an important role in the energy consumption of heating and cooling, defining the hydrothermal conditions and air quality of dwellings. Among other functions, ventilation systems are necessary to ensure the oxygen levels needed for household combustion appliances8). Kitchen ventilation is an important topic in modern building9). Exhaust ventilation can be provided via any of the following designs: a range hood or other exhaust devices.
The main purpose of kitchen ventilation is to remove moisture and pollutants from local areas within a house. A range hood, a well-placed wall, or a ceiling exhaust fan can be much more effective than an exhaust fan placed elsewhere in the kitchen or home. Range hoods are important appliances for reducing the amount of cooking-induced harmful materials capable of accumulating in residential sites. The conventional exhaust apparatuses in the kitchens include types of canopy hoods, exterior hoods, and variations. Up-suction, side-suction, and inclined-suction hoods are typical examples. The main structures of a conventional range hood are holes or slots for suction, and fans supply an active pressure gradient for ventilation. The buoyancy force generated by stoves or other heating components and the driving force from blowers or fans, exhaust the contaminant, which includes particles, odors, gases, and heat, outdoors. In a previous study, the capture efficiency was a factor for evaluating the performance of a range hood or a kitchen ventilation system10,11,12). Some studies reported that the flow visualization technique was used to investigate the airflow around the stove under range hoods13). Some studies reported an improvement in kitchen ventilation by modifying kitchen ceilings14, 15). Other studies reported that improving range hoods was a method for controlling pollutants in kitchens. Abanto and Reggio16) reported that the characteristic curves of a ventilator were built based on numerical results. The hood model has been incorporated into a full-scale kitchen to predict airflow conditions in the space in a kitchen. Yi et al.12) reported that a concurrent supply and exhaust ventilation system was developed to effectively exhaust heat and contamination from the kitchen. Liu et al.17) reported that air curtains on range hoods control the escape of oil fumes from kitchen hoods. Huang et al.18) investigated the performance of a wall-mounted range hood with laser-assisted flow visualization in static conditions (the draft of the environment was controlled) and dynamic conditions (humans walking by). A novel design of a range hood was reported by Huang et al20, 21). A range hood with the installed inclined air-curtain was called the inclined air-curtain range hood. The inclined air-curtain was installed in front of the range hood to separate the cook and the pollutant generated from the pans of heating oil. For static tests20), the detected tracer-gas concentration of the conventional range hood was larger than that of the air-curtain range hood by about three orders of magnitude around the front edge of countertop. No significant spillages of oil fumes or tracer-gas concentration was observed or detected around the front and lateral planes of the air-curtain range hood. The inclined air-curtain range hood presented excellent hood performance by isolating the oil mists from the mannequin with an air curtain and therefore could reduce spillages out into the atmosphere and the mannequin’s breathing zone21).
The important parameter affected the performance of the range hoods in kitchens was the uncontrolled draft in the environment. The uncontrolled draft was induced from air conditioners, fans, or the wind got into the space through windows or doors of kitchens. The draft effect was a kind of continuous disturbance of airflow in kitchens. It was different from the effect of walk-by mentioned by Huang et al18, 21). Chen et al.19) presented the containment of conventional range hoods operating under the effect of a cross draft. When the velocity of the cross draft was greater than 0.2 m/s, the pollutant spillage was increased with the increasing draft velocity.
The performance of the inclined air-curtain range hood was higher than the conventional range hood was represented20, 21). We expected that the performance of the inclined air-curtain range hood was higher than that of the conventional range hoods in the draft effect. We investigated the performance of an inclined air-curtain range hood in a steadily and continuously draft supplied by a homemade draft generator. Using the laser-assisted smoke flow visualization technique and the tracer-gas method, the relation between the flow behaviors and the containment of the inclined air-curtain range hood was studied.
Material and Methods
Experimental space
The test room was a room with dimensions 19 m (length) × 16 m (width) × 5 m (height). The velocity of the environmental draft in the space was less than 5 cm/s. Turbulence and interference from external sources such as an air supply diffuser, doors, and traffic in the room were restricted.
Inclined air-curtain range hood
The inclined air-curtain range hood was assembled with three components: one suction slot, one slot jet, and two guard plates. The stainless-steel suction hood shown in Fig. 1 (a) was installed on the test platform made of aluminum extrusion. The inlet of the suction hood was designed to be a narrow slot 2 cm wide and 70 cm long. In general, entry loss of a slot hood is larger than that of a rectangular opening hood (W/L>0.2, the ratio of width over length of the suction inlet). However, the width of the suction inlet was larger than 14 cm if the W/L>0.2 was adopted. The width of the suction hood was increased to 14 cm so that the area of the inlet of the suction hood was increased. The velocity at the inlet of the suction hood was decreased with the increasing area of the inlet of the suction hood if the suction flow rate was constant. The effective capture velocity was too low to decrease the performance of exhaust the contaminant generated in cooking. Therefore, the width of the inlet of the suction hood was 2 cm (W/L=0.028) for the high capture velocity of the suction hood. The exhaust outlet of the suction hood was a circular hole with a 15 cm diameter. The flange was 48 cm wide and 90 cm long. The flange, which was bent at two sides at a 15° angle, was installed on the inlet of the suction hood. As shown in Fig. 1 (b), the height of the hood was 55 cm in this study.
Fig. 1.
Configuration of inclined air-curtain range hood. (a) isometric view, (b) side view, (c) top view, (d) guard plate.
The slot jet was assembled with three cross-flow fans to form a plan jet. The slot jet was installed 50 cm from the rear wall on the countertop of the test platform. As shown in Fig. 1 (c), the width and length of the slot jet were 2 cm and 60 cm, respectively. According to the result represented by Huang et al.21), the parameters Vb=1 m/s and θ=15° were suggested that the inclined air-curtain effectively isolated the contaminant from the mannequin. So, the same values of the velocity of the slot jet and the inclined angle of the slot jet shown in Fig. 1 (b) were used in the experiments of the study. The distance ΔY, the offset between the centerline of the suction slot and the centerline of the oil pan, was specified to be 5 cm. The plan jet and the slot suction formed a special flow pattern called the inclined air curtain. The guard plates were 10 cm × 15 cm rectangular plates made of acrylic. Each guard plate was 5 cm thick. The angle of each installed guard plate on the rear wall was 70°.
The characteristic velocities at the inlet of the suction of the inclined air-curtain range hood were 12 m/s, 13 m/s, and 15 m/s. The flow rates of the suction velocities were 10.1 m3/min, 10.9 m3/min, and 12.6 m3/min.
Flow visualization
Two electric heaters were installed on the countertop to simulate the burners. Each of the electric heaters was applied 450 W to heat the plate on the heater. The temperature of the hot plate on each electric heater was 360° to 370°. The mineral oil in the oil pans was heated to 210° to 220° by the electric heaters to generate an oil mist for the flow visualization. The diameter of the oil mist droplet, measured with a particle analyzer (Model 2600C, Malvern Instrument Ltd., Malvern, Worcestershire, UK), was 1.7 ± 0.2 μm.
A green laser beam with a wavelength of 532 nm was generated from a 100 mW Nd-YAG laser. The laser-light sheet was formed when the laser beam passed through a homemade laser-light expander. The thickness of the laser-light sheet was 0.5 mm. The oil mist generated from heated oil pans scattered the laser light and made the images of the mist in the plane of the laser-light sheet visible. The images were recorded with a charge-coupled device (CCD) camera. The framing rate was 30 frames/s, and the exposure time was 1/60 s.
Draft generator
As shown in Fig. 2 (a), the draft generator consisted of an axial fan, a section of honeycombs, and a section of multi-stage screens. The airflow that exited the axial fan had swirl and fluctuation components. At the exit of the draft generator, the degree of swirl was decreased to a negligibly small value, and the turbulence fluctuation was less than 0.5%. Table 1 shows the nominal draft velocities and the range of centerline velocities within the effective distances. At each rotating speed of the axial flow fan, the centerline velocity values remained somewhat constant at each axial distance from the exit of the draft generator up to some effective distance. Beyond this effective distance, the centerline velocities decayed quickly. We named the persisting centerline velocity before fast decay the “nominal draft velocity,” Vd. The axial distance measured from the exit of the draft generator before the centerline velocity decayed quickly was named the “effective distance.” The draft generator was installed at three locations (lateral θ=0°, oblique θ=45°, frontal θ=90°) to provide a cross draft, as shown in Fig. 2 (b). The horizontal distance between the exit of the draft generator and the center of the countertop was 1 m. The vertical distance from the center of the draft generator to the surface of the countertop was 0.21 m.
Fig. 2.
Draft generator and deployment of draft test. (a) draft generator, (b) deployment of hood and draft generator.
Table 1. Nominal velocity (Vd) of draft generator.
| Nominal draft velocity Vd (m/s) | Effective distance (m) | Velocity range (m/s) |
|---|---|---|
| 0.1 | 0.80–1.03 | 0.09–0.13 |
| 0.2 | 0.08–1.06 | 0.19–0.20 |
| 0.3 | 0.75–1.00 | 0.27–0.32 |
| 0.4 | 0.07–1.10 | 0.39–0.41 |
| 0.5 | 0.60–1.07 | 0.48–0.50 |
| 0.6 | 0.75–1.30 | 0.57–0.61 |
| 0.7 | 0.35–1.40 | 0.70–0.72 |
Tracer-gas concentration tests
Sulfur hexafluoride (SF6) was used as the tracer gas in the experiment. Using the tracer-gas concentration method, the capture efficiency (η) of the inclined air-curtain range hood was evaluated. SF6 at a concentration of 99.99999% was released from two homemade gas-release rings. As shown in Fig. 3, each homemade gas-release ring, with a diameter of 18 cm, was made of a copper tube. The outer diameter of the copper tube was 0.4 cm, and the copper wall was 0.5 mm thick. Each gas-release ring had 20 holes 0.2 cm in diameter. The flow rate released from each gas-release ring was 3 L/min. The ejected velocity of each hole on the ring was 0.8 m/s. The influence of the tracer-gas jet was negligible in the experiments. The flow was controlled by a homemade system of the flow rate measurement that consisted of a pressure gauge, a needle valve, and a calibrated rotameter. The gas-release rings were attached to the hot plates (which were heated to 380 °C) of the electric heaters so that the SF6 gas would receive heat and buoyancy from the hot plates. A Miran SapphIRe Portable Ambient Analyzer (Thermo Electron Corp., Franklin, MA, USA) was used to measure the concentration of SF6 gas. The resolution of the analyzer was 0.001 ppm for measurement of the concentration of SF6 gas, and the sampling rate was 20 readings per second.
Fig. 3.
Sulfur hexafluoride gas-release ring.
For the static condition (i.e., the velocity of the airflow in the space was controlled at slower than 5 cm/s), the definition of the capture efficiency was the ratio of the contaminants captured by the hood to the total contaminants produced at the source22). Two gas-release rings were inserted into the suction slot of the inclined air-curtain range hood to ensure that the total released SF6 was injected into the piping system. The total flow rate of SF6 from the two gas-release rings was 6 L/min for 12 min. The SF6 concentration was measured at the location about 1.0 m upstream of the end of the piping system (20 m long).
As shown in Fig. 4, the average value over
t=t4−t3 is
denoted as C1. The average value over time
t=t2−t1 is
denoted as C2. The capture efficiency η is
calculated by
(1)
Fig. 4.
Typical time history of SF6 gas concentration detected at exhaust pipe of range hood for capture index measurement.
For the draft condition, the measurement method for C2 was the same as that of the static condition; however, the measurement of C1 was a little different. The gas-release rings were placed on the hot plates of the electric heaters, and the SF6 concentration in the exhaust pipe was measured from time zero for 12 min. During the lead-in period of 8 min, the draft was not applied; the draft was then applied for the next 3 min and stopped at t=11 min. The typical time-varying SF6 concentration for transition from the “no draft” to the “draft” condition is shown in Fig. 4. When the draft was applied at t=8 min, the SF6 concentration dropped quickly within 1 min and fluctuated in terms of a low time-averaged level C1. After the draft was stopped at t=11 min, the SF6 concentration recovered to normal values at t >11.5 min.
Results and Discussion
In the study reported by Huang et al.20), the flow formed by the oil mist generated by heating the oil pans on the countertop was restricted stably within the range between the guard plates in a test under static conditions.
The laser-light sheet shown in Fig. 5 was located at the plane of z=40 cm, and the distribution of the oil mist was formed by the effect of the draft velocity of 0.2 m/s from three directions. The results showed that Vd=0.2 m/s was too weak to affect the flow structure of the inclined air-curtain range hood. However, the variations of the oil mist distribution were observed with the different directions of the draft effect. When the draft blown from the lateral direction (θ=0°), there was no air curtain to resist the draft in the lateral direction so that the oil mist was moved to the right of Fig. 5 (a). When the draft blown from the oblique direction (θ=45°), some part of the draft was resisted by the inclined air-curtain so that the oil mist was moved toward the real wall and the right of Fig. 5 (c). When the draft blown from the front direction (θ=90°), the draft was resisted by the inclined air-curtain. Although, the draft was resisted by the inclined air-curtain, the oil mist was pushed by the airflow came from the front direction. Therefore, it was observed that the oil mist was moved toward the rear wall of the range hood. When the suction flow rate was increased, the obvious improvement of the oil mist distribution was shown in Fig. 5 (b).
Fig. 5.
Images of oil mist in horizontal plane at z=40 cm. Vd=0.2 m/s. (a)Qs=10.1 m3/min and θ = 0°, (b)Qs=12.6 m3/min and θ=0°, (c)Qs=10.1 m3/min and θ=45°, (d)Qs=12.6 m3/min and θ=45°, (e)Qs=10.1 m3/min and θ=90°, (f)Qs=12.6 m3/min and θ=90°.
As shown in Fig. 6, for the draft velocity 0.3 m/s, the flow structure was different from that in Fig. 5. The dispersion zone of the oil mist in Fig. 5 was expanded, especially in Fig. 6 (c), 6 (d), and 6 (e). At the 0.3 m/s draft velocity, the flow of the oil mist was dispersed at a low flow rate, i.e., Qs=10.1 m3/min. The increased draft velocity from the lateral direction (θ=0°) forced the oil mist to move to the right, as shown in Fig. 6 (a), when the flow rate of the range hood was 10.1 m3/min. When the flow rate was increased to 12.6 m3/min, the oil mist shown in Fig. 6 (b) was stably restricted under the hood. When the draft was applied from the oblique direction (θ=45°), the oil mist, shown in Fig. 6 (c), was dispersed, and the zone of the oil mist was larger than that shown in Fig. 5 (c). When the draft was applied from the oblique direction, the oil mist was attached to the rear wall, and the right part of the oil mist moved to an area close to the edge of the flange of the range hood. The compact structure of the oil mist, as shown in Fig. 5 (d), was destroyed to disperse slightly, as shown in Fig. 6 (d), due to the draft velocity of 0.3 m/s even if the oil mist was still restricted under the range hood. When the front draft (θ=90°) was applied, the flow of the oil mist, shown in Fig. 6 (e), moved to attach on the rear wall of the range hood at a low flow rate of 10.1 m3/min. The flow, shown in Fig. 6 (f), was stable at the 12.6 m3/min flow rate.
Fig. 6.
Images of oil mist in horizontal plane at z=40 cm. Vd=0.3 m/s. (a)Qs=10.1 m3/min and θ=0°, (b)Qs=12.6 m3/min and θ=0°, (c)Qs=10.1 m3/min and θ = 45°, (d)Qs=12.6 m3/min and θ=45°, (e)Qs=10.1 m3/min and θ=90°, (f)Qs=12.6 m3/min and θ=90°.
The draft velocity increased to 0.5 m/s, as shown in Fig. 7. As shown in Fig. 7 (a) and 7 (b), the oil mist dispersed to the right side and leaked out of the flange when the draft was applied from the direction of θ=0° even though the flow rate was increased to 12.6 m3/min. When the applied draft was in the direction of θ=45°, the containment of the flow rate of 12.6 m3/min was better than that of the flow rate of 10.1 m3/min. Although the higher flow rate was used, leakage was found around the front of the flange, as shown in Fig. 7 (d). As shown in Fig. 7 (e), the flow rate of 10.1 m3/min was too low to restrict the oil mist even though there was an inclined air curtain in front of the range hood. However, the oil mist, shown in Fig. 7 (f), was restricted under the area of the flange of the range hood at the flow rate of 12.6 m3/min when the draft velocity 0.5 m/s was applied in the front direction.
Fig. 7.
Images of oil mist in horizontal plane at z=40 cm. Vd=0.5 m/s. (a)Qs=10.1 m3/min and θ=0°, (b)Qs=12.6 m3/min and θ=0°, (c)Qs=10.1 m3/min and θ=45°, (d)Qs=12.6 m3/min and θ=45°, (e)Qs = 10.1 m3/min and θ=90°, (f)Qs=12.6 m3/min and θ=90°.
Figure 8 shows the capture efficiency η varying with the draft velocity Vd. For the cases of θ=0°, the variation of η decreased rapidly when Vd varied from 0.2 m/s to Vd=0.3 m/s. In Fig. 8, the capture efficiency was little changed for the cases of θ=45° in the section of the draft of 0.2 m/s to 0.3 m/s. When the draft velocity was higher than 0.3 m/s, the capture efficiency of the range hood decreased an average of 18.8% when the draft velocity increased from 0.3 m/s to 0.4 m/s. As shown in Fig. 8, the trend of the cases of θ=90° changed moderately in the range from 0.2 m/s to 0.4 m/s and changed rapidly in the range from 0.4 m/s to 0.5 m/s. For the cases of θ=90°, the variation of the capture efficiency in the three flow rates was a maximum of 2%, when the draft velocity was in the section from 0.2 m/s to 0.4 m/s. However, the variation increased 8.6% on average when the draft velocity increased from 0.4 m/s to 0.5 m/s.
Fig. 8.
Capture efficiencies of inclined air-curtain range hood with respect to influences of draft from various directions and suction flow rates.
As shown in Fig. 8, the draft effect began to be active to the inclined air-curtain range hood was the draft velocity of 0.3 m/s. In the draft velocity of 0.3 m/s, the capture efficiency of the cases of θ=0° was lowest among the draft effect of the three directions. In the case of θ=45°, the maximum of the variation of the capture efficiency was recorded in the range from 0.3 m/s to 0.4 m/s. For all cases, the increased suction flow rate was efficient for the containment of the inclined air-curtain range hood. Especially, the capture efficiency was higher than 90% in the effect of the draft velocity of 0.5 m/s when the suction flow rate was 12.6 m3/min in the case of θ=90°.
To compare the results represented by Chen et al.19), the performances of the conventional and jet-isolated range hoods were obviously decreased when the draft velocity was higher than 0.3 m/s. The same result shown in Fig. 8 was found on the inclined air-curtain range hood. When the draft velocity was 0.3 m/s in any direction of the three directions, the capture efficiencies of the inclined air-curtain range hood and the conventional range hood were on the same level in 12.6 m3/min of the suction flow rate. When the draft velocity was lower than 0.3 m/s in any direction of the three directions, the capture efficiency of the inclined air-curtain range hood was higher than that of the conventional range hood in 12.6 m3/min of the suction flow rate. In the oblique and front directions, the capture efficiency of the inclined air-curtain range hood in 12.6 m3/min of the suction flow rate was higher than that of the jet-isolated range hood in 15.0 m3/min of the suction flow rate when the draft velocity was smaller than 0.3 m/s.
Conclusions
The containment ability of the inclined air-curtain range hood was tested in the draft effect. The capture efficiency was the index to evaluate the performance of the containment of the range hood. From the results, low capture efficiency was observed when the draft effect was applied from the lateral direction. High capture efficiency was observed when the draft effect was applied from the front direction. If the draft effect was applied from the oblique direction, the capture efficiency of the inclined air-curtain range hood did not decrease at a draft velocity less than 0.4 m/s. Increasing the suction flow rate of the hood was efficient to improve the capture efficiency of the inclined range hood. The capture efficiency was higher than 90% at the flow rate of 12.6 m3/min and the draft velocity of 0.5 m/s in the case of θ=90°. Using air-curtain technology, the capture efficiency became low at the draft velocity higher than 0.5 m/s. The draft effect in a kitchen affects the air quality in that room. The results of the study pointed out that the containment ability of the inclined air-curtain range hood was weak when the draft came from the lateral direction. The containment ability of the inclined air-curtain range hood was strong when the draft came from the front direction.
Acknowledgments
The authors gratefully acknowledge the financial support provided to this study by the National Science Council of Taiwan under Grant No. NSC 102-2221-E-011-053.
References
- 1.Chowdhury Z, Le LT, Masud AA, Chang KC, Alauddin M, Hossain M, Zakaria ABM, Hopke PK. (2012) Quantification of indoor air pollution from using cookstoves and estimation of its health effects on adult women in northwest Bangladesh. Aerosol Air Qual Res 12, 463–75. [Google Scholar]
- 2.Saha S, Guha A, Roy S. (2012) Experimental and computational investigation of indoor air quality inside several community kitchens in a large campus. Build Environ 52, 177–90. [Google Scholar]
- 3.Li A, Zhao Y, Jiang D, Hou X. (2012) Measurement of temperature, relative humidity, concentration distribution and flow field in four typical Chinese commercial kitchens. Build Environ 56, 139–50. [Google Scholar]
- 4.Gao J, Cao C, Zhang X, Luo Z. (2013) Volume-based size distribution of accumulation and coarse particles (PM0.1–10) from cooking fume during oil heating. Build Environ 59, 575–80. [Google Scholar]
- 5.He C, Morawska L, Hitchins J, Gilbert D. (2004) Contribution from indoor sources to particle number and mass concentrations in residential houses. Atmos Environ 38, 3405–15. [Google Scholar]
- 6.Svendsen K, Sjaastad AK, Sivertsen I. (2003) Respiratory symptoms in kitchen workers. Am J Ind Med 43, 436–9. [DOI] [PubMed] [Google Scholar]
- 7.Sisti J, Boffetta P. (2012) What proportion of lung cancer in never-smokers can be attributed to known risk factors? Int J Cancer 131, 265–75. [DOI] [PMC free article] [PubMed] [Google Scholar]
- 8.Pinto M, Viegas J. (2013) The influence of ventilation systems on domestic gas appliances: an experimental study. Build Environ 69, 1–13. [Google Scholar]
- 9.Lee H, Lee YJ, Park SY, Kim YW, Lee Y. (2012) The improvement of ventilation behaviours in kitchens of residential buildings. Indoor Built Environ 21, 48–61. [Google Scholar]
- 10.Li Y, Delsante A, Symons J. (1997) Residential kitchen range hoods—buoyancy-capture principle and capture efficiency revisited. Indoor Air 7, 151–7. [Google Scholar]
- 11.Zhao YJ, Li AG, Tao PF, Gao R. (2013) The impact of various hood shapes, and side panel and exhaust duct arrangements, on the performance of typical Chinese style cooking hoods. Build Simul-China 6, 139–49. [Google Scholar]
- 12.Delp WW, Singer BC. (2012) Performance assessment of U.S. residential cooking exhaust hoods. Environ Sci Technol 46, 6167–73. [DOI] [PubMed] [Google Scholar]
- 13.Hargather MJ, Settles GS. (2011) Background-oriented schlieren visualization of heating and ventilation flows: HVAC-BOS. HVAC R Res 17, 771–80. [Google Scholar]
- 14.Kosonen R, Mustakallio P. (2003) The influence of a capture jet on the efficiency of a ventilated ceiling in a commercial kitchen. Int J Vent 1, 189–99. [Google Scholar]
- 15.Kosonen R. (2007) The effect of supply air systems on the efficiency of a ventilated ceiling. Build Environ 42, 1613–23. [Google Scholar]
- 16.Abanto J, Reggio M. (2006) Numerical investigation of the flow in a kitchen hood system. Build Environ 41, 288–96. [Google Scholar]
- 17.Liu X, Wang X, Xi G. (2014) Orthogonal design on range hood with air curtain and its effects on kitchen environment. J Occup Environ Hyg 11, 186–99. [DOI] [PubMed] [Google Scholar]
- 18.Huang RF, Dai GZ, Chen JK. (2010) Effects of mannequin and walk-by motion on flow and spillage characteristics of wall-mounted and jet-isolated range hoods. Ann Occup Hyg 54, 625–39. [DOI] [PubMed] [Google Scholar]
- 19.Chen JK, Huang RF, Peng KL. (2012) Flow characteristics and spillage mechanisms of wall-mounted and jet-isolated range hoods subject to influence from cross draft. J Occup Environ Hyg 9, 36–45. [DOI] [PubMed] [Google Scholar]
- 20.Huang RF, Nian YC, Chen JK. (2010) Static condition differences in conventional and inclined air-curtain range hood flow and spillage characteristics. Environ Eng Sci 27, 513–22. [Google Scholar]
- 21.Huang RF, Nian YC, Chen JK, Peng KL. (2011) Improving flow and spillage characteristics of range hoods by using an inclined air-curtain technique. Ann Occup Hyg 55, 164–79. [DOI] [PubMed] [Google Scholar]
- 22.Li Y, Delsante A. (1996) Derivation of capture efficiency of kitchen range hoods in a confined space. Build Environ 31, 461–8. [Google Scholar]